Eastron SDM230-Modbus Bruksanvisning

Eastron Mätutrustning SDM230-Modbus

Läs nedan 📖 manual på svenska för Eastron SDM230-Modbus (13 sidor) i kategorin Mätutrustning. Denna guide var användbar för 8 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/13
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -1
SDM230-Modbus
Single-Phase Two Module DIN rail Meters
Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounng 35 mm
100A direct connecon
Beer than Class 1 / B accuracy
User Manual V1.4
2015
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -2
Applicaon
The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residenal, Ulity and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communicaon port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.
PART 1 Specicaon
General Specicaons
Voltage AC (Un) 230V
Voltage Range 176~276V AC
Base Current (Ib) A 10
Max. Current (Imax) 100A
Mini Current (Imin) 5A 0.
Starting current 0.4% of Ib
Power consumpon <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
1000/100/10/1 imp/kWh/kVarh (congurable)
Display LCD with blue backlit
Max. Reading 999999.9kWh
Accuracy
Voltage 0.5% of range maximum
Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Acve power 1% of range maximum
Reacve power 1% of range maximum
Apparent power 1% of range maximum
Acve energy Class 1 IEC62053- 21
Class B EN50470-3
Reacve energy 1% of range maximum
Eastron SDM230-Modbus User Manual
Jiaxing Eastron Electronic Instruments Co.,Ltd Tel: 0086-573- 82 Fax: 0086-573- . 83698881 / 836988 83698883
Add:No.1369, Chengnan Road, Jiaxing, Zhejiang, 314001, China. Web: www.eastron.com.cn Email: sales@eastrongroup.com
- -3
Environment
Operang temperature - to +5525℃ ℃
Storage and transportaon temperature - to +70 40℃ ℃
Reference temperature 23℃±2
Relave humidity 0 to 95%, non-condensing
Altude up to 2500m
Warm up me 10s
Installaon category CAT III
Mechanical Environment M1
Electromagnec environment E2
Degree of polluon 2
Output
Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is congurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-congurable. It is xed up with import kWh. The constant is 1000imp/kWh.
RS485 output for Modbus RTU
The meter provides a RS485 port for remote communicaon. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communicaon parameters can be congured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247
Mechanics
Din rail dimensions 36x99x63 (WxHxD) DIN 43880
Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0

Produktspecifikationer

Varumärke: Eastron
Kategori: Mätutrustning
Modell: SDM230-Modbus
Färg på produkten: Zwart
Kraftkälla: AC
På / Av knapp: Ja
Fjärrkontroll: Bedraad
Genomsnittlig effekt: 45 W
Volymkontroll: Digitaal
Plug and play: Ja
Stöder Windows: Ja
siffra: 1
Rekommenderad användning: Universeel
Stöder Mac-operativsystem: Ja
Ljudutgångskanaler: 2.1 kanalen
Fjärrstyrd: Ja
Stöder Linux: Ja
Subwoofertyp: Actieve subwoofer
Trådlös subwoofer: Nee
Antal satelliter: 2
Medium power satellithögtalare: - W
AC-ingångsspänning: 220-240 V
AC-ingångsfrekvens: 50 - 60 Hz
Förstärkningsenhet ingår: Ja

Behöver du hjälp?

Om du behöver hjälp med Eastron SDM230-Modbus ställ en fråga nedan och andra användare kommer att svara dig




Mätutrustning Eastron Manualer

Mätutrustning Manualer

Nyaste Mätutrustning Manualer