Fujitsu ASGA18FUTD-B Bruksanvisning

Fujitsu Splitter ASGA18FUTD-B

Läs nedan 📖 manual på svenska för Fujitsu ASGA18FUTD-B (12 sidor) i kategorin Splitter. Denna guide var användbar för 9 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/12
En-1
Note: This manual describes how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
1. SAFETY PRECAUTIONS
1
x Be sure to read this manual thoroughly before installation.
x The warnings and precautions indicated in this manual contain important informa-
tion pertaining to your safety. Be sure to observe them.
x Hand this manual, together with the operating manual, to the customer. Request
the customer to keep them on hand for future use, such as for relocating or repair-
ing the product.
WARNING Indicates a potentially or imminently hazardous situation which,
if not avoided, could result in death or serious injury.
Installation of this product must be done by experienced service technicians
or professional installers only in accordance with this manual. Installation by
nonprofessional or improper installation of the product may cause serious accidents
such as injury, water leakage, electric shock, or fire. If the product is installed in
disregard of the instructions in this Manual, it will void the manufacturer’s warranty.
Do not turn on the power until all work has been completed. Turning on the power before
WKHZRUNLVFRPSOHWHGFDQFDXVHVHULRXVDFFLGHQWVVXFKDVHOHFWULFVKRFNRU¿UH
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is
H[SRVHGWRDGLUHFWÀDPHLWPD\SURGXFHDWR[LFJDV
'RQRWXVHWKLVHTXLSPHQWZLWKDLURUDQ\RWKHUXQVSHFL¿HGUHIULJHUDQWLQWKHUHIULJHUDQW
lines. Excess pressure can cause a rupture.
Installation must be performed in accordance with regulations, codes, or standards for
electrical wiring and equipment in each country, region, or the installing place.
'RQRW WRXFKWKH ¿QVRI WKHKHDW H[FKDQJHU7RXFKLQJWKH KHDWH[FKDQJHU ¿QV FRXOG
UHVXOWLQGDPDJHWRWKH¿QVRUSHUVRQDOLQMXU\VXFKDVVNLQUXSWXUH
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
CAUTION Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
Read carefully all safety information written in this manual before you install or use the
air conditioner.
Install the product by following local codes and regulations in force at the place of
installation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be
installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable
combined with an Earth Leakage Circuit Breaker (ELCB).
The product is not explosion proof, and therefore should not be installed in explosive
atmosphere.
To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned off. After turning off the power, always wait 5 minutes or
more before you touch the electrical components.
This product contains no user-serviceable parts. Always consult experienced service
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or
malfunction of the property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant (R22)
models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22)
models, some of the piping and installation and service tools are special. (See the table
below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant
5$PRGHODOZD\VUHSODFHWKHFRQYHQWLRQDOSLSLQJDQGÀDUHQXWVZLWKWKH5$
SLSLQJDQGÀDUHQXWV
Models that use refrigerant R410A have a different charging port thread diameter
to prevent erroneous charging with conventional refrigerant (R22) and for safety.
Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2-20 UNF]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by
pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of
the gas and liquid phases. And always charge from the liquid phase where refrigerant
composition is stable.
1
2.2. Special tools for R410A refrigerant
Tool name Changes
Gauge manifold
Pressure is high and cannot be measured with a conventional
(R22) gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended to use the gauge with seals-0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
Charge hose To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of re-
sidual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed
or discoloured portion (especially on the interior surface). Otherwise, the expansion value
or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials.
AIR CONDITIONER
INDOOR UNIT (Wall Mounted Type) INSTALLATION MANUAL
PART No. 9387082241
For authorized service personnel only.
Refer to the rating label with the serial number.
Contents
1. SAFETY PRECAUTIONS ................................................................. 1
2. ABOUT THIS PRODUCT.................................................................. 1
3. GENERAL SPECIFICATION ............................................................ 2
4. SELECTING THE INSTALLATION LOCATION ................................ 3
5. INSTALLATION WORK .................................................................... 3
6. ELECTRICAL WIRING ..................................................................... 5
7. FINISHING........................................................................................ 6
8. FRONT PANEL REMOVAL AND INSTALLATION ........................... 7
9. REMOTE CONTROLLER INSTALLATION ....................................... 7
10. OPTIONAL KIT INSTALLATION ....................................................... 8
11. FUNCTION SETTING...................................................................... 8
12. CHECK LIST ..................................................................................... 9
13. TEST RUN ........................................................................................ 9
14. CUSTOMER GUIDANCE ................................................................. 9
15. ERROR CODES ............................................................................ 10
English
En-2
CONNECTION PIPE REQUIREMENT
WARNING
'RQRWXVHWKHH[LVWLQJIRU5SLSLQJDQGÀDUHQXWV
If the existing materials are used, the pressure inside the refrigerant cycle will rise
and cause failure, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other
WKDQWKHVSHFL¿HGUHIULJHUDQW5$WRHQWHUWKHUHIULJHUDQWF\FOH
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise
to an abnormally high value and cause failure, injury, etc.
2.3. Accessories
The following installation accessories are supplied. Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Operating Manual
1
Remote controller
holder
1
Installation Manual
2
Insulation (Drain hose)
1
6SHFL¿FDWLRQ0DQXDO
1
Cloth tape
1
Wall hook bracket
1
Tapping screw (large)
8
Remote controller
1
Tapping screw (small)
2
Battery
2
2.4. Optional parts
Refer to each installation manual for the method of installing optional parts.
Parts name Model No. Application
Wired Remote Controller* UTY-RNN*M For air conditioner operation
$SSOHFDWHFKLQ¿OWHU UTR-FA13-1
,RQGHRGRUL]DWLRQ¿OWHU UTR-FA13-2
External connect kit* UTY-XWZXZ5 For control input/output port
Communication kit UTY-XCBXZ3 For the installation of optional
parts
* Optional communication kit is necessary for the installation.
2.5. Additional materials required for installation
The following items are necessary to install this air conditioner. (The items are not includ-
ed with the air conditioner and must be purchased separately.)
Name
Connection pipe assembly Saddle
Connection cable Drain hose
Wall pipe Tapping screws
Decorative tape Sealant
Vinyl tape M10 bolt, nut
Wall cap
3. GENERAL SPECIFICATION
This Installation manual briefly outlines where and how to install the air conditioning
system. Please read over the entire set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the system before beginning.
3.1. Type of copper pipe and insulation material
]1
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe
length and height difference.
Diameter
Liquid pipe Gas pipe
30/36 type 9.52 mm (3/8 in.) 15.88 mm (5/8 in.)
18/24 type 6.35 mm (1/4 in.) 15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. Reverse cycle model only
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70%, install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
,IKHDWLQVXODWLRQLVXVHGWKDWLVQRWDVWKLFNDVVSHFL¿HGFRQGHQVDWLRQPD\IRUPRQWKH
surface of the insulation. In addition, use heat insulation with heat conductivity of
:P.RUOHVVDW&
3.2. Electrical requirement
The indoor unit is powered from the outdoor unit or branch box. Do not power indoor unit
from separate power source.
WARNING
Refer to local codes for acceptable cable type.
Cable
Cable size (mm
2
)
Type
Remarks
Connection cable
1.5 ~ 2.5 Type 60245 IEC 57 *Refer to “Outdoor unit installation
manual”
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage
drop is 2% or more.
 Before starting work check that power is not being supplied to all poles of the indoor
unit and outdoor unit.
 Install all electrical works in accordance to standard.
 Install the disconnect device with a contact gap of at least 3mm in all poles nearby the
units. (Both indoor unit and outdoor unit)
 Wiring size must comply with the applicable local and national code.
En-3
4. SELECTING THE INSTALLATION LOCATION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the weight of the indoor unit
and which will not amplify sound or vibration. If the installation location is not strong
enough, the indoor unit may fall and cause injuries.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the unit in the following areas:
$UHDZLWKKLJKVDOWFRQWHQWVXFKDVDWWKHVHDVLGH,WZLOOGHWHULRUDWHPHWDOSDUWV
causing the parts to fail or the unit to leak water.
$UHD¿OOHGZLWKPLQHUDORLORUFRQWDLQLQJDODUJHDPRXQWRIVSODVKHGRLORUVWHDP
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
$UHDWKDWJHQHUDWHVVXEVWDQFHVWKDWDGYHUVHO\DIIHFWWKHHTXLSPHQWVXFKDV
sulphuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
$UHDWKDWFDQFDXVHFRPEXVWLEOHJDVWROHDNFRQWDLQVVXVSHQGHGFDUERQ¿EUHVRU
ÀDPPDEOHGXVWRUYRODWLOHLQÀDPPDEOHVVXFKDVSDLQWWKLQQHURUJDVROLQH
,IJDVOHDNVDQGVHWWOHVDURXQGWKHXQLWLWFDQFDXVHD¿UH
$UHDZKHUHDQLPDOVPD\XULQDWHRQWKHXQLWRUDPPRQLDPD\EHJHQHUDWHG
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
'RQRWLQVWDOOWKHXQLWQHDUDVRXUFHRIKHDWVWHDPRUÀDPPDEOHJDV
Install the unit where drainage does not cause any trouble.
Install the unit where ambient temperature does not reach 6C or more. Take a
measure such as ventilation for an environment in which heat is retained.
If children under 10 years old may approach the unit, take preventive measures so
that they cannot reach the unit.
,QVWDOOWKHLQGRRUXQLWRQWKHZDOOZKHUHWKHKHLJKWIURPWKHÀRRUVPRUHWKDQP
(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all
over the room.
(3) Install the unit at a place near an power outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown in “5.1. Installation
GLPHQVLRQV´$OVRLQVWDOOWKHXQLWZKHUHWKH¿OWHUFDQEHUHPRYHG
&RUUHFWLQLWLDOLQVWDOODWLRQORFDWLRQLVLPSRUWDQWEHFDXVHLWLVGLI¿FXOWWRPRYHXQLWDIWHULWLV
installed.
5. INSTALLATION WORK
]1
5.1. Installation dimensions
(Wall cap)
1.5 m or over
60 mm or over**
80 mm or over* Wall hook bracket
130 mm
or over**
1.8 m or over
* The distance between the wall hook
bracket and the ceiling should be
80 mm or more.
** The side next to the sidewall must
IROORZWKHVL]HLQGLFDWHGLQ¿JXUH
]1
5.2. Indoor unit piping direction
7KHSLSLQJFDQEHFRQQHFWHGLQWKHGLUHFWLRQVLQWKH¿JXUH:KHQWKHSLSLQJLVFRQ-
nected in direction (B), (C), (D) or (E), cut along the piping groove in the side of the front
panel with a hacksaw.
(B) Right
outlet (A) Rear
outlet
(C) Bottom
outlet
(D) Left bottom
outlet
(E) Left
outlet
(Rear)
(F) Centre
outlet
(G) Left rear
outlet
5.3. Cutting the hole in the wall for the connecting pipes
&XWDPPGLDPHWHUKROHLQWKHZDOODWWKHSRVLWLRQVKRZQLQWKH¿JXUH
(2)
When cutting the wall hole at the inside of the wall hook bracket, cut the hole to a point of
intersection of centre marks.
When cutting the wall hole at the outside of the wall hook bracket, cut the hole at a
point of 10 mm below.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(4) Always align the centre of the wall hole. If misaligned, water leakage will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole.
)RUOHIW SLSLQJDQGULJKW SLSLQJ FXWWKH KROHD OLWWOHORZHU VRWKDWGUDLQZDWHUZLOOÀRZ
freely.
Wall hook bracket Centring marks
LowerLower
10 mm
or more
80 mm hole 10 mm
or more
Fasten with vinyl tape
5~10 mm
Wall pipe
(Field supply)
Wall cap
(Field supply)
(Inside) (Outside)
Wall
80 mm hole
WARNING
If the wall pipe is not used, the cable interconnecting the indoor unit(s) and outdoor unit
or branch box may touch metal and cause electric discharge.
]1
5.4. Installing the wall hook bracket
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically.
,IWKHZDOOKRRNEUDFNHWLVWLOHGZDWHUZLOOGULSWRWKHÀRRU
(2) Install the wall hook bracket so that it is strong enough to support the weight of the
unit.
Ɣ 
Fasten the wall hook bracket to the wall with 6 or more screws through the holes near the
outer edge of the bracket
.
Ɣ &KHFNWKDWWKHUHLVQRUDWWOHDWWKHZDOOKRRNEUDFNHW
Wall hook bracket Tapping screw (large)
(Accessory, 8 pcs)
CAUTION
Install the wall hook bracket by levelling, both horizontally and vertically.

Produktspecifikationer

Varumärke: Fujitsu
Kategori: Splitter
Modell: ASGA18FUTD-B

Behöver du hjälp?

Om du behöver hjälp med Fujitsu ASGA18FUTD-B ställ en fråga nedan och andra användare kommer att svara dig




Splitter Fujitsu Manualer

Splitter Manualer

Nyaste Splitter Manualer