Fujitsu ASMA18FUTA Bruksanvisning
Fujitsu
Luftkonditionering
ASMA18FUTA
Läs nedan 📖 manual på svenska för Fujitsu ASMA18FUTA (21 sidor) i kategorin Luftkonditionering. Denna guide var användbar för 9 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare
Sida 1/21

En-1
Note: This manual describes how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
1. SAFETY PRECAUTIONS
1
• Be sure to read this manual thoroughly before installation.
• The warnings and precautions indicated in this manual contain important informa-
tion pertaining to your safety. Be sure to observe them.
• Hand this manual, together with the operation manual, to the customer. Request
the customer to keep them on hand for future use, such as for relocating or repair-
ing the product.
WARNING Indicates a potentially or imminently hazardous situation which,
if not avoided, could result in death or serious injury.
Installation of this product must be done by experienced service technicians
or professional installers only in accordance with this manual. Installation by
nonprofessional or improper installation of the product may cause serious accidents
such as injury, water leakage, electric shock, or fire. If the product is installed in
disregard of the instructions in this Manual, it will void the manufacturer’s warranty.
Do not turn on the power until all work has been completed. Turning on the power before
the work is completed can cause serious accidents such as electric shock or re.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is
exposed to a direct ame, it may produce a toxic gas.
Do not use this equipment with air or any other unspecied refrigerant in the refrigerant
lines. Excess pressure can cause a rupture.
The air conditioner must be installed accordance with electrical installation standard for
Thailand of The Engineering Institute of Thailand Under H.M. The King’s Patronage.
Do not touch the ns of the heat exchanger. Touching the heat exchanger ns could
result in damage to the ns or personal injury such as skin rupture.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
CAUTION Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
Read carefully all safety information written in this manual before you install or use the
air conditioner.
Install the product by following local codes and regulations in force at the place of
installation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be
installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable
combined with an Earth Leakage Circuit Breaker (ELCB).
The product is not explosion proof, and therefore should not be installed in explosive
atmosphere.
To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned o. After turning o the power, always wait 5 minutes or
more before you touch the electrical components.
This product contains no user-serviceable parts. Always consult experienced service
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or
malfunction of the property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant (R22)
models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22)
models, some of the piping and installation and service tools are special. (See the table
below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant
R410A model, always replace the conventional piping and are nuts with the R410A
piping and are nuts.
Models that use refrigerant R410A have a dierent charging port thread diameter
to prevent erroneous charging with conventional refrigerant (R22) and for safety.
Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2-20 UNF]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by
pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of
the gas and liquid phases. And always charge from the liquid phase where refrigerant
composition is stable.
1
2.2. Special tools for R410A refrigerant
Tool name Changes
Gauge manifold
Pressure is high and cannot be measured with a conventional
(R22) gauge. To prevent erroneous mixing of other refriger-
ants, the diameter of each port has been changed.
It is recommended to use the gauge with seals-0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
Charge hose To increase pressure resistance, the hose material and base
size were changed.
Vacuum pump A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Gas leakage detector Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of re-
sidual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed
or discoloured portion (especially on the interior surface). Otherwise, the expansion value
or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is neces-
sary to choose adequate materials.
AIR CONDITIONER
INDOOR UNIT (Wall Mounted Type) INSTALLATION MANUAL
PART No. 9387082654-01
For authorized service personnel only.
Contents
1. SAFETY PRECAUTIONS 1 .................................................................
2. ABOUT THIS PRODUCT.................................................................. 1
3. GENERAL SPECIFICATION 2 ............................................................
4. SELECTING THE INSTALLATION LOCATION 3 ................................
5. INSTALLATION WORK .................................................................... 3
6. ELECTRICAL WIRING ..................................................................... 5
7. FINISHING........................................................................................ 6
8. FRONT PANEL REMOVAL AND INSTALLATION 7 ...........................
9. REMOTE CONTROLLER INSTALLATION 7 .......................................
10. OPTIONAL KIT INSTALLATION 8 .......................................................
11. FUNCTION SETTING...................................................................... 8
12. CHECK LIST 9 .....................................................................................
13. TEST RUN 9 ........................................................................................
14. CUSTOMER GUIDANCE 9 .................................................................
15. ERROR CODES ............................................................................ 10
English
ไทย

En-2
CONNECTION PIPE REQUIREMENT
WARNING
Do not use the existing (for R22) piping and are nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise
and cause failure, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other
than the specied refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise
to an abnormally high value and cause failure, injury, etc.
2.3. Accessories
The following installation accessories are supplied. Use them as required.
Name and Shape Q’ty Name and Shape Q’ty
Operation manual
1
Remote controller
holder
1
Installation Manual
2
Insulation (Drain hose)
1
Specication Manual
1
Cloth tape
1
Wall hook bracket
1
Tapping screw (large)
8
Remote controller
1
Tapping screw (small)
2
Battery
2
2.4. Optional parts
Refer to each installation manual for the method of installing optional parts.
Parts name Model No. Application
Wired Remote Controller* UTY-RNN*M For air conditioner operation
Apple-catechin lter UTR-FA13-1
Ion deodorization lter UTR-FA13-2
External connect kit* UTY-XWZXZ5 For control input/output port
Communication kit UTY-XCBXZ3 For the installation of optional
parts
* Optional communication kit is necessary for the installation.
2.5. Additional materials required for installation
The following items are necessary to install this air conditioner. (The items are not includ-
ed with the air conditioner and must be purchased separately.)
Name
Connection pipe assembly Saddle
Connection cable Drain hose
Wall pipe Tapping screws
Decorative tape Sealant
Vinyl tape M10 bolt, nut
Wall cap
3. GENERAL SPECIFICATION
This Installation manual briefly outlines where and how to install the air conditioning
system. Please read over the entire set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the system before beginning.
3.1. Type of copper pipe and insulation material
]1
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe
length and height dierence.
Diameter
Liquid pipe Gas pipe
30/36 type 9.52 mm (3/8 in.) 15.88 mm (5/8 in.)
18/24 type 6.35 mm (1/4 in.) 15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. Reverse cycle model only
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70%, install heat insulation around the refrigerant piping. If the
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specied, condensation may form on the
surface of the insulation. In addition, use heat insulation with heat conductivity of
0.045 W/(m•K) or less (at 20 °C).
3.2. Electrical requirement
The indoor unit is powered from the outdoor unit or branch box. Do not power indoor unit
from separate power source.
WARNING
Refer to local codes for acceptable cable type.
Cable
Cable size (mm
2
)
Type
Remarks
Connection cable
1.5 ~ 2.5 Type 60245 IEC 57 *Refer to “Outdoor unit installation
manual”
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage
drop is 2% or more.
• Before starting work check that power is not being supplied to all poles of the indoor
unit and outdoor unit.
• Install all electrical works in accordance to standard.
• Install the disconnect device with a contact gap of at least 3mm in all poles nearby the
units. (Both indoor unit and outdoor unit)
• Wiring size must comply with the applicable local and national code.

En-3
4. SELECTING THE INSTALLATION LOCATION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the weight of the indoor unit
and which will not amplify sound or vibration. If the installation location is not strong
enough, the indoor unit may fall and cause injuries.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts,
causing the parts to fail or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
• Area that generates substances that adversely aect the equipment, such as
sulphuric gas, chlorine gas, acid, or alkali.
It will cause the copper pipes and brazed joints to corrode, which can cause
refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon bres or
ammable dust, or volatile inammables such as paint thinner or gasoline.
If gas leaks and settles around the unit, it can cause a re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble.
Install the unit where ambient temperature does not reach 60°C or more. Take a
measure such as ventilation for an environment in which heat is retained.
If children under 10 years old may approach the unit, take preventive measures so
that they cannot reach the unit.
Install the indoor unit on the wall where the height from the oors more than 1.8 m.
(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all
over the room.
(3) Install the unit at a place near an power outlet or special branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown in “5.1. Installation
dimensions”. Also install the unit where the lter can be removed.
Correct initial installation location is important because it is dicult to move unit after it is
installed.
5. INSTALLATION WORK
]1
5.1. Installation dimensions
(Wall cap)
1.5 m or over
60 mm or over**
80 mm or over* Wall hook bracket
130 mm
or over**
1.8 m or over
* The distance between the wall hook
bracket and the ceiling should be
80 mm or more.
** The side next to the sidewall must
follow the size indicated in gure.
]1
5.2. Indoor unit piping direction
The piping can be connected in the 7 directions in the gure. When the piping is con-
nected in direction (B), (C), (D) or (E), cut along the piping groove in the side of the front
panel with a hacksaw.
(B) Right
outlet (A) Rear
outlet
(C) Bottom
outlet
(D) Left bottom
outlet
(E) Left
outlet
(Rear)
(F) Centre
outlet
(G) Left rear
outlet
5.3. Cutting the hole in the wall for the connecting pipes
(1) Cut a 80 mm diameter hole in the wall at the position shown in the gure.
(2)
When cutting the wall hole at the inside of the wall hook bracket, cut the hole to a point of
intersection of centre marks.
When cutting the wall hole at the outside of the wall hook bracket, cut the hole at a
point of 10 mm below.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(4) Always align the centre of the wall hole. If misaligned, water leakage will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole.
(6) For left piping and right piping, cut the hole a little lower so that drain water will ow
freely.
Wall hook bracket Centring marks
LowerLower
10 mm
or more
80 mm hole 10 mm
or more
Fasten with vinyl tape
5~10 mm
Wall pipe
(Field supply)
Wall cap
(Field supply)
(Inside) (Outside)
Wall
80 mm hole
WARNING
If the wall pipe is not used, the cable interconnecting the indoor unit(s) and outdoor unit
or branch box may touch metal and cause electric discharge.
]1
5.4. Installing the wall hook bracket
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically.
If the wall hook bracket is tiled, water will drip to the oor.
(2) Install the wall hook bracket so that it is strong enough to support the weight of the
unit.
●
Fasten the wall hook bracket to the wall with 6 or more screws through the holes near the
outer edge of the bracket
.
● Check that there is no rattle at the wall hook bracket.
Wall hook bracket Tapping screw (large)
(Accessory, 8 pcs)
CAUTION
Install the wall hook bracket by levelling, both horizontally and vertically.
Produktspecifikationer
Varumärke: | Fujitsu |
Kategori: | Luftkonditionering |
Modell: | ASMA18FUTA |
Behöver du hjälp?
Om du behöver hjälp med Fujitsu ASMA18FUTA ställ en fråga nedan och andra användare kommer att svara dig
Luftkonditionering Fujitsu Manualer

25 Februari 2025

25 Februari 2025

25 Februari 2025

25 Februari 2025

25 Februari 2025

9 Januari 2025

9 Januari 2025

9 Januari 2025

9 Januari 2025

9 Januari 2025
Luftkonditionering Manualer
- Luftkonditionering Zibro
- Luftkonditionering Candy
- Luftkonditionering Electrolux
- Luftkonditionering Samsung
- Luftkonditionering LG
- Luftkonditionering Bosch
- Luftkonditionering AEG
- Luftkonditionering Panasonic
- Luftkonditionering Bauknecht
- Luftkonditionering BEKO
- Luftkonditionering Delonghi
- Luftkonditionering Daewoo
- Luftkonditionering Grundig
- Luftkonditionering Honeywell
- Luftkonditionering Inventum
- Luftkonditionering Medion
- Luftkonditionering Siemens
- Luftkonditionering Toshiba
- Luftkonditionering Whirlpool
- Luftkonditionering Zanussi
- Luftkonditionering Vaillant
- Luftkonditionering Adler
- Luftkonditionering Airlux
- Luftkonditionering Aermec
- Luftkonditionering Acson
- Luftkonditionering Airwell
- Luftkonditionering Akai
- Luftkonditionering Apc
- Luftkonditionering Amcor
- Luftkonditionering Amana
- Luftkonditionering Andrews
- Luftkonditionering Argo
- Luftkonditionering Ariston
- Luftkonditionering Arcelik
- Luftkonditionering Airview
- Luftkonditionering Aertesi
- Luftkonditionering Bartscher
- Luftkonditionering OneConcept
- Luftkonditionering Tosot
- Luftkonditionering Eurom
- Luftkonditionering GE
- Luftkonditionering Orbegozo
- Luftkonditionering Princess
- Luftkonditionering Ozito
- Luftkonditionering Sharp
- Luftkonditionering Klarstein
- Luftkonditionering Telefunken
- Luftkonditionering Gorenje
- Luftkonditionering Hitachi
- Luftkonditionering Nedis
- Luftkonditionering Thomson
- Luftkonditionering Korona
- Luftkonditionering Black And Decker
- Luftkonditionering Innoliving
- Luftkonditionering Tristar
- Luftkonditionering Domo
- Luftkonditionering Trisa
- Luftkonditionering Progress
- Luftkonditionering Hotpoint-Ariston
- Luftkonditionering Calor
- Luftkonditionering Rowenta
- Luftkonditionering Tomado
- Luftkonditionering Manta
- Luftkonditionering SereneLife
- Luftkonditionering OK
- Luftkonditionering Hisense
- Luftkonditionering Hyundai
- Luftkonditionering Vox
- Luftkonditionering Bestron
- Luftkonditionering Westinghouse
- Luftkonditionering ECG
- Luftkonditionering Melissa
- Luftkonditionering Emerio
- Luftkonditionering RCA
- Luftkonditionering Clatronic
- Luftkonditionering Taurus
- Luftkonditionering Itho
- Luftkonditionering Russell Hobbs
- Luftkonditionering Hotpoint
- Luftkonditionering Sencor
- Luftkonditionering Midea
- Luftkonditionering Lanaform
- Luftkonditionering Blaupunkt
- Luftkonditionering Mabe
- Luftkonditionering Concept
- Luftkonditionering Frigidaire
- Luftkonditionering Svan
- Luftkonditionering Logik
- Luftkonditionering Danby
- Luftkonditionering Anslut
- Luftkonditionering Balay
- Luftkonditionering Stirling
- Luftkonditionering Daikin
- Luftkonditionering Carson
- Luftkonditionering Frilec
- Luftkonditionering Teesa
- Luftkonditionering Mesko
- Luftkonditionering Profilo
- Luftkonditionering Tripp Lite
- Luftkonditionering Truma
- Luftkonditionering Finlux
- Luftkonditionering Heinner
- Luftkonditionering Termozeta
- Luftkonditionering Sanyo
- Luftkonditionering Eldom
- Luftkonditionering Jocca
- Luftkonditionering Einhell
- Luftkonditionering Kenmore
- Luftkonditionering Philco
- Luftkonditionering Theben
- Luftkonditionering TCL
- Luftkonditionering Nabo
- Luftkonditionering Guzzanti
- Luftkonditionering Defy
- Luftkonditionering Infiniton
- Luftkonditionering Mitsubishi
- Luftkonditionering Dometic
- Luftkonditionering Aspes
- Luftkonditionering Premium
- Luftkonditionering Dimplex
- Luftkonditionering DCG
- Luftkonditionering Emerson
- Luftkonditionering White Knight
- Luftkonditionering GlobalTronics
- Luftkonditionering Technisat
- Luftkonditionering Suntec
- Luftkonditionering Profile
- Luftkonditionering Orima
- Luftkonditionering Ferroli
- Luftkonditionering Inventor
- Luftkonditionering Haier
- Luftkonditionering Gree
- Luftkonditionering H.Koenig
- Luftkonditionering Evolar
- Luftkonditionering Ariston Thermo
- Luftkonditionering Kubo
- Luftkonditionering Exquisit
- Luftkonditionering Elba
- Luftkonditionering Proline
- Luftkonditionering Royal Sovereign
- Luftkonditionering Corberó
- Luftkonditionering Meaco
- Luftkonditionering Ansonic
- Luftkonditionering Ardes
- Luftkonditionering Be Quiet!
- Luftkonditionering Kelvinator
- Luftkonditionering Element
- Luftkonditionering Malmbergs
- Luftkonditionering Soler And Palau
- Luftkonditionering Everglades
- Luftkonditionering Heylo
- Luftkonditionering Bomann
- Luftkonditionering ElectriQ
- Luftkonditionering Insignia
- Luftkonditionering Listo
- Luftkonditionering Daitsu
- Luftkonditionering Sanus
- Luftkonditionering Ufesa
- Luftkonditionering Milectric
- Luftkonditionering Wilfa
- Luftkonditionering Carrier
- Luftkonditionering Olimpia Splendid
- Luftkonditionering Trotec
- Luftkonditionering Sigma
- Luftkonditionering Saunier Duval
- Luftkonditionering Camry
- Luftkonditionering Qlima
- Luftkonditionering Challenge
- Luftkonditionering Duux
- Luftkonditionering Alpatec
- Luftkonditionering Jocel
- Luftkonditionering Primo
- Luftkonditionering Comfee
- Luftkonditionering Meireles
- Luftkonditionering Godrej
- Luftkonditionering Sauber
- Luftkonditionering Maiko
- Luftkonditionering MPM
- Luftkonditionering Tectro
- Luftkonditionering Rotel
- Luftkonditionering Becken
- Luftkonditionering Esatto
- Luftkonditionering Bavaria
- Luftkonditionering Igenix
- Luftkonditionering Waeco
- Luftkonditionering Essentiel B
- Luftkonditionering Mestic
- Luftkonditionering Team
- Luftkonditionering Equation
- Luftkonditionering Vivax
- Luftkonditionering Edy
- Luftkonditionering HTW
- Luftkonditionering Prime3
- Luftkonditionering Edgestar
- Luftkonditionering Maxicool
- Luftkonditionering Fuave
- Luftkonditionering KDK
- Luftkonditionering G3 Ferrari
- Luftkonditionering CyberPower
- Luftkonditionering Dantherm
- Luftkonditionering Equator
- Luftkonditionering Thermex
- Luftkonditionering Bimar
- Luftkonditionering Kunft
- Luftkonditionering Day
- Luftkonditionering HQ
- Luftkonditionering Be Cool
- Luftkonditionering Master
- Luftkonditionering Koenig
- Luftkonditionering Fakir
- Luftkonditionering MundoClima
- Luftkonditionering Argoclima
- Luftkonditionering Baxi
- Luftkonditionering Easy Home
- Luftkonditionering Proklima
- Luftkonditionering Heller
- Luftkonditionering Sonnenkonig
- Luftkonditionering Lavorwash
- Luftkonditionering Climadiff
- Luftkonditionering Home Electric
- Luftkonditionering Eco-De
- Luftkonditionering REMKO
- Luftkonditionering Fairland
- Luftkonditionering Toyotomi
- Luftkonditionering DEXP
- Luftkonditionering Just Fire
- Luftkonditionering Broan
- Luftkonditionering Avidsen
- Luftkonditionering Teco
- Luftkonditionering Furrion
- Luftkonditionering Cecotec
- Luftkonditionering Livington
- Luftkonditionering Whynter
- Luftkonditionering Chigo
- Luftkonditionering RIDGID
- Luftkonditionering Hokkaido
- Luftkonditionering Kalorik
- Luftkonditionering Gutfels
- Luftkonditionering Telair
- Luftkonditionering Klarbach
- Luftkonditionering Mobile Airco
- Luftkonditionering Heiko
- Luftkonditionering Firstline
- Luftkonditionering Eden
- Luftkonditionering Qlima - Zibro
- Luftkonditionering Handson
- Luftkonditionering Galanz
- Luftkonditionering Bryant
- Luftkonditionering Duracraft
- Luftkonditionering Klima1stKlaas
- Luftkonditionering Emmeti
- Luftkonditionering Khind
- Luftkonditionering Evapolar
- Luftkonditionering Orava
- Luftkonditionering EcoFlow
- Luftkonditionering Elgin
- Luftkonditionering Tronix
- Luftkonditionering Liebert
- Luftkonditionering Oregon Scientific
- Luftkonditionering Frigor
- Luftkonditionering Fronius
- Luftkonditionering TechnoLife
- Luftkonditionering Shinco
- Luftkonditionering Innova
- Luftkonditionering Avalon Bay
- Luftkonditionering SMC
- Luftkonditionering Zymbo
- Luftkonditionering D-Let
- Luftkonditionering Domair
- Luftkonditionering NewAir
- Luftkonditionering Kogan
- Luftkonditionering Braemar
- Luftkonditionering ActronAir
- Luftkonditionering Klimaire
- Luftkonditionering Consul
- Luftkonditionering SEEGER
- Luftkonditionering Thermo Comfort
- Luftkonditionering LERAN
- Luftkonditionering General Electric
- Luftkonditionering SPT
- Luftkonditionering Mistral
- Luftkonditionering Mizushi
- Luftkonditionering Friedrich
- Luftkonditionering Simplicity
- Luftkonditionering Sinclair
- Luftkonditionering Starlyf
- Luftkonditionering Aerian
- Luftkonditionering Moa
- Luftkonditionering Fuji Electric
- Luftkonditionering Polocool
- Luftkonditionering Convair
- Luftkonditionering Kibernetik
- Luftkonditionering Fral
- Luftkonditionering Companion
- Luftkonditionering Prem-i-air
- Luftkonditionering Arcoaire
- Luftkonditionering Céliera
- Luftkonditionering Bodin
- Luftkonditionering Magnavox
- Luftkonditionering AFINTEK
- Luftkonditionering Brivis
- Luftkonditionering MRCOOL
- Luftkonditionering Volteno
- Luftkonditionering B-Air
- Luftkonditionering Rinnai
- Luftkonditionering Monzana
- Luftkonditionering Trilec
- Luftkonditionering Kaden
- Luftkonditionering Geist
- Luftkonditionering GoldAir
- Luftkonditionering Sôlt
- Luftkonditionering Avallon
- Luftkonditionering Ravanson
- Luftkonditionering Create
- Luftkonditionering Columbia Vac
- Luftkonditionering TURBRO
- Luftkonditionering House & Luft
- Luftkonditionering Daizuki
- Luftkonditionering Bonaire
- Luftkonditionering Woods
- Luftkonditionering Evapcool
- Luftkonditionering Protector
- Luftkonditionering Vostok
- Luftkonditionering American Comfort
- Luftkonditionering Ocean Breeze
- Luftkonditionering Quirky
- Luftkonditionering Krone
- Luftkonditionering KwiKool
- Luftkonditionering SMD
- Luftkonditionering Big Ass Fans
- Luftkonditionering Arctic King
- Luftkonditionering IFB
- Luftkonditionering Artrom
- Luftkonditionering Senville
- Luftkonditionering Climachill
- Luftkonditionering Commercial Cool
- Luftkonditionering Riffel
- Luftkonditionering Coolix
- Luftkonditionering Heat Controller
- Luftkonditionering Ausclimate
- Luftkonditionering Luma Comfort
- Luftkonditionering Norpole
- Luftkonditionering Kaco
- Luftkonditionering Omega Altise
- Luftkonditionering Middle Atlantic
- Luftkonditionering Goodwe
- Luftkonditionering Swegon
- Luftkonditionering InAlto
- Luftkonditionering JHS
- Luftkonditionering FREONIC
- Luftkonditionering ARCTIC WIND
- Luftkonditionering SHE
- Luftkonditionering Electroline
- Luftkonditionering BLUEPALM
- Luftkonditionering KuulAire
- Luftkonditionering Keystone
- Luftkonditionering Cool-Space
- Luftkonditionering BOSFOR
- Luftkonditionering Aconatic
- Luftkonditionering AireMax
- Luftkonditionering VänEE
- Luftkonditionering Mayer
- Luftkonditionering Perfect Aire
- Luftkonditionering Koldfront
- Luftkonditionering Yamazen
- Luftkonditionering Soler & Palau
- Luftkonditionering Universal Blue
- Luftkonditionering Symphony
- Luftkonditionering Corona
- Luftkonditionering Sheffield
Nyaste Luftkonditionering Manualer

18 Mars 2025

18 Mars 2025

18 Mars 2025

18 Mars 2025

18 Mars 2025

18 Mars 2025

12 Mars 2025

12 Mars 2025

12 Mars 2025

12 Mars 2025