IFM AC2484 Bruksanvisning

Läs nedan 📖 manual på svenska för IFM AC2484 (4 sidor) i kategorin Inte kategoriserad. Denna guide var användbar för 3 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/4
Operating instructions
AS-i CompactModule M8
AC2482
AC2484
7390939/00 01/2013
UK
UK
UK
UK
UK
2
1 Preliminary note
An instruction is indicated by " ".
Example: Mount the unit as shown.
Important note
Non-compliance can result in malfunction or interference.
2 Functions and features
Maximum number of modules per master: 62
AS-Interface version 3.0, downward compatible
AC2482: 2 inputs / 2 outputs / AS-i profile S-B.A.E / extended addressing
mode: yes
AC2484: 4 inputs / AS-i profile S-0.A.E / extended addressing mode: yes
3 Installation
Disconnect the system from power before installation.
For installation choose a flat mounting surface.
The entire bottom of the module must lie flat on the mounting surface.
Fix the module onto the mounting surface using M4 screws and washers.
4 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment
must be adhered to.
Disconnect the installation from power and connect the unit.
To ensure the protection rating:
Connect the plugs of the sensors to the M8 sockets.
Tighten firmly, recommended tightening torque 0.3...0.5 Nm.
Cover the sockets that are not in use with the enclosed protective caps.
Tighten firmly, recommended tightening torque 0.3...0.5 Nm.
3
UK
4.1 Pin connection
Socket M12
1: AS-i +
3: AS-i -
Input M8
1: sensor supply +
3: sensor supply -
4: data input
Output M8
3: internal voltage E-
4: switching output
Parameter bit Designation Description
P1 Periphery fault 1 peripheral fault indication active
0 peripheral fault indication not active
5 Addressing
Addressing the unit via the M12 connector; the address is set to 0 at the
factory.
Addressing unit AC1154
Wiring of the addressing socket
5
1
3 4
2
1: SFC-i + / 2: TTL / 3: SFC-i -
4: TTL / 5: + 5 V
6 Operating and display elements
M12x1
M8x1
LEDs I-x
LEDs O-x
LED
PWR
LED
FAULT

Produktspecifikationer

Varumärke: IFM
Kategori: Inte kategoriserad
Modell: AC2484

Behöver du hjälp?

Om du behöver hjälp med IFM AC2484 ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad IFM Manualer

IFM

IFM OT5012 Bruksanvisning

27 Oktober 2024
IFM

IFM SUH201 Bruksanvisning

26 Oktober 2024
IFM

IFM PI1003 Bruksanvisning

26 Oktober 2024
IFM

IFM AC1254 Bruksanvisning

21 Oktober 2024
IFM

IFM EVW027 Bruksanvisning

21 Oktober 2024
IFM

IFM EVC132 Bruksanvisning

20 Oktober 2024
IFM

IFM PT2400 Bruksanvisning

20 Oktober 2024
IFM

IFM O2D532 Bruksanvisning

20 Oktober 2024
IFM

IFM PA3027 Bruksanvisning

20 Oktober 2024
IFM

IFM TW2001 Bruksanvisning

18 Oktober 2024

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer