Installation instructions
Compact speed monitor M30
AC/DC version
DI01xx
DI1xxA
11430370 / 00 03 / 2016
UK
2
1 Preliminary note
This document applies to devices of the type "compact speed monitor" (art. no.:
DI01xx and DI1xxA).
This document is intended for specialists. These specialists are people who are
qualified by their training and their experience to see risks and to avoid possible
hazards that may be caused during operation, installation or maintenance of the
device.
Read this document before use to familiarise yourself with operating conditions,
installation and operation. Keep this document during the entire duration of use of
the device.
WARNING
Adhere to the warning notes and safety instructions .(→ 2 Safety instructions)
Contents
1 Preliminary note 2 ...................................................................................................
1.1 Symbols and warning signs used .................................................................3
2 Safety instructions ...............................................................................................3
2.1 ATEX units (DI1xxA) 3 .....................................................................................
3 Functions and features 3 ........................................................................................
3.1 Switching function .........................................................................................3
3.2 Function diagram 4 ..........................................................................................
4 Installation............................................................................................................5
5 Electrical connection 5 ............................................................................................
6 Setting..................................................................................................................6
7 Operation .............................................................................................................6
8 Technical data 7 ......................................................................................................
3
UK
1.1 Symbols and warning signs used
Instructions
Cross-reference
Information
Supplementary note.
Important note
Non-compliance can result in malfunction or interference.
WARNING
Warning of serious personal injury.
Death or serious irreversible injuries may result.
2 Safety instructions
The sensor must be connected by a qualified electrician. Observe the national and
international regulations for the installation of electrical equipment.
2.1 ATEX units (DI1xxA)
Remarks for safe use in hazardous areas: operating instructions (Ex protection
related part) for speed monitors according to EU directive 2014/34/EC annex VIII
(ATEX) group II, equipment category 3D.
If no operating instructions (Ex protection related part) or EC declaration of
conformity is supplied with this product in the language of the EU user country,
these can be requested from your dealer (see delivery note) or manufacturer (see
cover sheet / back).
3 Functions and features
The compact inductive speed monitor detects without contact if a set rotational
speed is not reached and signals this by means of a switching signal.
3.1 Switching function
Transistor output LEDs
switched (conducting) On rotational speed > SP and during start-up delay
not switched (non
conducting)
Off rotational speed < SP
SP = set point