Installation Instructions
Inductive Sensor
IDE
704286 / 00 09 / 2007
UK
UK
UK
UK
UK
2
Function and features
This sensor detects metals without contact and indicates their presence by
providing a switched signal. Sensing range adjustable from 20 to 60 mm; (values
based on standard measurement with mild steel; a shorter sensing range for other
metals). In the event of variations of the ambient temperature in the range from
-25°C to +80°C the set switch point may fluctuate by ± 10%.
Installation
Screw the to a firm sensor
base. If there is high mechanical stress,
ensure that it cannot work loose.
Non-flush installation.
Open space around the sensing face when mounted in metal:
3 x S
n
2 x a 2 x aa
Minimum distance when several sensors of the same type are mounted:
8 x S
n
aa
2 x a
3
UK
Electrical connection
Disconnect power before connecting the sensor. Open the sensor; connect
cable in accordance with the instructions on the type label.
Note: insert a miniature fuse according to the technical data sheet, if specified.
Recommendation: check the unit for reliable function after a short cirucit.
Adjustment
LED
NO NC
1. Place the target material in the safe sensing range
→ → LED is lit. LED goes off.
2. Decrease the sensing range until
LED goes off.
Decrease the sensing range until
LED is lit.
3. Increase the sensing range until
LED is lit.
Increase the sensing range until
LED goes off.
Sensing distance should not be increased beyond 60 mm.
Operation
Check the safe functioning of the sensor. The LED is lit when the output is swit-
ched. The operation of the sensor is maintenance-free.
For perfect functioning make sure that:
the sensing face and the open space are kept free of metal deposits and
foreign bodies, particularly for installation with the sensing face facing upwards.
EMC: The unit conforms to the requirements of EN 60947-5-2.
potentiometer
sensing range

Produktspecifikationer

Varumärke: IFM
Kategori: Inte kategoriserad
Modell: ID5047

Behöver du hjälp?

Om du behöver hjälp med IFM ID5047 ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad IFM Manualer

IFM

IFM OT5012 Bruksanvisning

27 Oktober 2024
IFM

IFM SUH201 Bruksanvisning

26 Oktober 2024
IFM

IFM PI1003 Bruksanvisning

26 Oktober 2024
IFM

IFM AC1254 Bruksanvisning

21 Oktober 2024
IFM

IFM EVW027 Bruksanvisning

21 Oktober 2024
IFM

IFM EVC132 Bruksanvisning

20 Oktober 2024
IFM

IFM PT2400 Bruksanvisning

20 Oktober 2024
IFM

IFM O2D532 Bruksanvisning

20 Oktober 2024
IFM

IFM PA3027 Bruksanvisning

20 Oktober 2024
IFM

IFM TW2001 Bruksanvisning

18 Oktober 2024

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer