Operating instructions
(Safety-related part ATEX)
Capacitive NAMUR sensors
KI-2015-N/NI*
706138 / 00 01 / 2012
UK
2
Remarks for safe use in hazardous areas
Functions and features
Use in hazardous areas according to the classification
II 1G
(group II, category 1G, apparatus for gas atmosphere)
The standards IEC 60079-0:2011, IEC 60079-11: 2011, IEC 60079-26: 2006 + Corr 2009
are applied.
Use in hazardous areas according to the classification
II 1D
(group II, category 1D, apparatus for dust atmosphere).
The standards IEC 60079-0:2011, IEC 60079-11:2011 are applied.
EC Type Test Certificate
DMT 01 ATEX E020
Marking
II 1G Ex ia IIB T6 Ga Ta: - 20°C to 60°C
II 1D Ex ia IIIC T90°C Da
Installation / Set-up
The units must only be installed, connected and set up by qualified staff. The qualified staff
must have knowledge of protection classes, regulations and provisions for apparatus in
hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable
for the application.
Connection only to intrinsically safe switching amplifiers which are approved with the EC
type test certificate and do not exceed the following maximum values:
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
Permissible operating temperature of the application (referred to the maximum power
which can be supplied):
-20 ... +60°C
Maximum effective internal inductance (Li) and capacitance (Ci):
Li = 1 H, Ci = 375 nFμ
The values apply to potted cables which are 2 m long.
The following values are added for the cable unit versions KI**** with potted cable > 2m:
0.5 H (Li) / 160 pF (Ci) per metre of potted cable.μ
3
UK
Installation remarks / Mounting
Adhere to the respective national regulations and provisions.
Avoid electrostatic charging on plastic units and cables.
Protect unit and cable against destruction.
The unit is not suitable for installation in walls which separate zone 0 from zone 1.
Maintenance / Repair
The unit must not be modified nor can it be repaired. In case of a fault please contact the
manufacturer.
If needed, you can obtain the data sheet, EC type test certificate or EC declaration of
conformity from the manufacturer.