Installation Instructions
Electronic pressure sensor
PA6229
704900 / 00 08 / 2010
UK
2
1 Safety instructions
Please read the product description prior to installing the unit. Ensure that the
product is suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
Please check for all applications that the product materials (see Technical data)
are compatible with the media to be measured.
For the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
Ampere
AWG (mm2)
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having
suitable ratings.
Contents
1 Safety instructions ................................................................................................2
2 Function and features ...........................................................................................3
2.1 Applications ....................................................................................................3
3 Installation ............................................................................................................3
4 Electrical connection.............................................................................................4
5 Scale drawing .......................................................................................................4
6 Technical data .......................................................................................................5
3
UK
2 Function and features
The pressure sensor detects the system pressure and converts it into an inverted
analogue output signal.
20 mA (at the initial value of the measuring range) ... 4 mA (at the final value of
the measuring range).
2.1 Applications
Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
bar PSI bar PSI bar PSI
PA6229 -1...0 -14.5...0 10 145 30 450
MPa = bar ÷ 10 / kPa = bar × 100
Static and dynamic overpressures exceeding the indicated overload
pressure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the bur-
sting pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Insert the unit in a ¼“ NPT process connection.
Tighten firmly.