Installation Instructions
Electronic pressure sensor
for industrial applications
PT354x/PT954x
704676 / 00 02 / 2010
UK
2
1 Safety instructions
Please read this document prior to installing the unit. Ensure that the product is •
suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal •
injury and/or damage to property may occur.
Please check for all applications that the product materials (see Technical data) •
are compatible with the media to be measured.
For the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated either
a) max 5 amps for voltages 0~20 Vrms (0~28.3 Vp) or
b) 100/Vp for voltages of 20~30 Vrms (28.3~42.4 Vp).
Contents
1 Safety instructions ................................................................................................2
2 Function and features ...........................................................................................3
2.1 Applications ....................................................................................................3
3 Installation ............................................................................................................3
4 Electrical connection.............................................................................................4
5 Scale drawing .......................................................................................................5
6 Technical data .......................................................................................................6
3
UK
2 Function and features
The pressure sensor detects the system pressure and converts it into an analog
output signal.
4 ... 20 mA (PT354x) / 0 ... 10 V (PT954x)
2.1 Applications
Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
bar PSI bar PSI bar PSI
PTx540 0...400 0...5 800 600 8 702 1 600 23 206
PTx541 0...250 0...3 625 400 5 800 1 000 14 504
PTx542 0...100 0...1 450 200 2 900 1 000 14 504
PTx543 0...25 0...362 60 870 600 8702
PTx544 0...10 0...145 25 362 300 4351
MPa = bar ÷ 10 / kPa = bar × 100
Static and dynamic overpressures exceeding the indicated overload pres-
sure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the burst-
ing pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Insert the unit in a G¼ process connection.
Tighten firmly. Tightening torque: max. 25 Nm.

Produktspecifikationer

Varumärke: IFM
Kategori: Inte kategoriserad
Modell: PT9541

Behöver du hjälp?

Om du behöver hjälp med IFM PT9541 ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad IFM Manualer

IFM

IFM OT5012 Bruksanvisning

27 Oktober 2024
IFM

IFM SUH201 Bruksanvisning

26 Oktober 2024
IFM

IFM PI1003 Bruksanvisning

26 Oktober 2024
IFM

IFM AC1254 Bruksanvisning

21 Oktober 2024
IFM

IFM EVW027 Bruksanvisning

21 Oktober 2024
IFM

IFM EVC132 Bruksanvisning

20 Oktober 2024
IFM

IFM PT2400 Bruksanvisning

20 Oktober 2024
IFM

IFM O2D532 Bruksanvisning

20 Oktober 2024
IFM

IFM PA3027 Bruksanvisning

20 Oktober 2024
IFM

IFM TW2001 Bruksanvisning

18 Oktober 2024

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer