Installation Instructions
Electronic pressure sensor
PX32xx
PX34xx
704627 / 02 11 / 2010
UK
2
1 Safety instructions
Please read the product description prior to installing the unit. Ensure that the
product is suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
Please check for all applications that the product materials (see Technical data)
are compatible with the media to be measured.
For units with cULus approval and the scope of validity cULus: 6 Technical
data.
2 Function and features
The pressure sensor detects the system pressure and converts it into an analog
output signal (4...20 mA).
2.1 Applications
Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
PX3233 0...250 PSI 2 175 PSI 5 075 PSI
PX3234 0...200 PSI 1 087 PSI 2 175 PSI
PX3254 0...100 PSI 1 087 PSI 2 175 PSI
PX3438 0...100 inH2O 4 015 inH2O 12 043 inH2O
Static and dynamic overpressures exceeding the indicated overload pres-
sure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the burst-
ing pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Insert the unit in suitable process connection (see type label “Port Size”).
Tighten firmly. Tightening torque 25 Nm.
3
UK
4 Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power.
Connect the unit as follows:
L+
3
4
2
1
BU
BK
BN
WH L-
3
1
4
2
n.c.
n.c.
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black), n.c. = not connected.
5 Scale drawing
79,5
M12 x1
30
30
14
M5
-18 NPT
14
/
Dimensions are in millimeters
1: ventilation