Installation Instructions
Electronic pressure sensor
PX3111 
PX322x
PX323x
PX3244
PX3422
PX911x 
PX913x
704571/06 02/2011
2
1  Safety instructions
Please read the product description prior to installing the unit. Please check that
the product is suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
Please check in all applications that the product materials (see Technical data) are
compatible with the media to be measured.
For gaseous media the application is limited to max. 363 PSI.
High-pressure units (5000 PSI) are supplied with a pressure relief mechanism and
an integrated damping device to comply with the regulations for UL approval and
to avoid any risk of injury in case of bursting when bursting pressure is exceeded.
Any manipulation of the damping device is not permissible.
When the damping device is removed, there is no damping function any
more. ATTENTION: risk of injury!
For units with cULus approval this approval becomes invalid when the
damping device is removed.
Contents
1 Safety instructions ...............................................................................................2
2 Function and features ..........................................................................................4
3 Installation............................................................................................................5
4 Electrical connection ............................................................................................5
5 Scale drawing ......................................................................................................6
6 Technical data ......................................................................................................8
3
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
Ampere
AWG (mm2)
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having suit-
able ratings.