Installation Instructions
Temperature transmitter
TA3333
TA3337
704559 / 01 12 / 2012
UK
2
1 Functions and features
The temperature transmitter detects the current system temperature and converts
it into an analog output signal (4 ... 20 mA).
Measuring range:
TA3333 -17,8...148,9 °C / 0...300 °F
TA3337 0...100 °C / 32...212 °F
Measuring element: Pt1000 to DIN EN 60751, class A
Temperature resistance
110 115 120 125 130 135 140 145 150
[°C]
40
80
120
160
200
240
[min]
0
¥
155
Maximum operation time depending on the medium temperature
3
UK
2 Installation
Before mounting and removing the unit: ensure that no medium can leak
at the process connection.
Insert the unit in a ¼“ NPT process
connection.
Minimum installation depth: 15 mm
(0.6 inch).
Tighten firmly. Tightening torque:
max. 25 Nm (18 ft-lbs).
3 Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power.
Connecting the unit as follows:
L+
3
4
2
1
L-
3
1
4
2
n.c.
n.c.
n.c. = not connected