Operating instructions
Ultrasonic diffuse-reflection sensor
with IO-Link
UGT203
UGT206
UGT509
UGT512
80275568 / 00 05 / 2018
UK
2
1 Safety instructions
Read this document before setting up the product and keep it during the entire
service life.
The product must be suitable for the corresponding applications and
environmental conditions without any restrictions.
Only use the product for its intended purpose .(→ 2 Functions and features)
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
The manufacturer assumes no liability or warranty for any consequences
caused by tampering with the product or incorrect use by the operator.
Installation, electrical connection, set-up, operation and maintenance of the
product must be carried out by qualified personnel authorised by the machine
operator.
Protect units and cables against damage.
2 Functions and features
Ultrasonic sensor for monitoring levels and detecting objects.
3 Installation
3
4
1
2
Secure the unit to a bracket.
1/2: status LEDs 1/2 (yellow),
setting aid and output indication
3: echo LED (green), is on when object or
background is detected
4: teach button
Sound-absorbing surfaces have a negative effect on a reliable function.
Technical data sheet): Consider the dead zone (
No object detection in the dead zone.
3
UK
For units with metal housing (according to UL 508):
Observe a minimum distance of 12.7 mm between the sensor and non-
insulated live parts.
For further information please refer to www.ifm.com
→ General information about installation and operation.
4 Electrical connection
Disconnect power.
Connect unit (depending on the type selected):
BK: black
BN: brown
BU: blue
WH: white
BN
WH
BK
BU
4
1
3
2OUT2
L+
L
OUT1
• OUT1: switching output / IO-Link
• OUT2: switching output
colours to DIN EN 60947-5-2
5 Settings
The unit and the parameters are set via the IO-Link interface (→ 5.1) or the
teach button (→ 5.2).
5.1 IO-Link
This unit has an IO-Link communication interface which enables direct access to
process and diagnostic data. In addition it is possible to set the parameters of the
unit while it is in operation. Operation of the unit via an IO-Link interface requires
an IO-Link master.
With a PC, suitable IO-Link software and an IO-Link adapter cable communication
is possible when the system is not in operation.
The IODDs necessary for the configuration of the unit, detailed information about
process data structure, diagnostic information, parameter addresses and the
necessary information about the required IO-Link hardware and software can be
found at www.ifm.com.

Produktspecifikationer

Varumärke: IFM
Kategori: Inte kategoriserad
Modell: UGT512

Behöver du hjälp?

Om du behöver hjälp med IFM UGT512 ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad IFM Manualer

IFM

IFM OT5012 Bruksanvisning

27 Oktober 2024
IFM

IFM SUH201 Bruksanvisning

26 Oktober 2024
IFM

IFM PI1003 Bruksanvisning

26 Oktober 2024
IFM

IFM AC1254 Bruksanvisning

21 Oktober 2024
IFM

IFM EVW027 Bruksanvisning

21 Oktober 2024
IFM

IFM EVC132 Bruksanvisning

20 Oktober 2024
IFM

IFM PT2400 Bruksanvisning

20 Oktober 2024
IFM

IFM O2D532 Bruksanvisning

20 Oktober 2024
IFM

IFM PA3027 Bruksanvisning

20 Oktober 2024
IFM

IFM TW2001 Bruksanvisning

18 Oktober 2024

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer