Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
2
Contents
Safety precautions....................................................................................3
Preparing for installation..............................................................................6
Selecting installation location ........................................................................27
Space requirement for installation ....................................................................29
Accessories .........................................................................................31
Base construction and installation of the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installing the wind/snow prevention duct..............................................................36
Refrigerant pipe installation..........................................................................39
Electrical wiring work................................................................................70
Air tightness test and vacuum drying..................................................................89
Pipe insulation ......................................................................................91
Charging refrigerant.................................................................................94
Basic segment display ...............................................................................97
Setting outdoor unit option switch and key function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Setting the MCU and Pipe Addresses (for HR Only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Things to check after completing the installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Inspection and test operation........................................................................113
Automatic refrigerant amount detection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic
accessories (e.g. charger, headset, USB cable) should not be disposed of with other household waste at the
end of their working life. To prevent possible harm to the environment or human health from uncontrolled
waste disposal, please separate these items from other types of waste and recycle them responsibly to
promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local
˝ͱЭʪθ
͔
͝
ʪ
͝
ϩͱ˙ѣʀʪࡥ˙ͱθʒʪϩɇ̷
̈ϑͱ˙и˵ʪθʪɇ
͝
ʒ˵ͱиϩ˵ʪцʀɇ
͝
ϩɇ
̧ʪϩ˵ʪϑʪ
̈ϩʪ
͔
ϑ˙ͱθʪ
͝
Э
̈θͱ
͔
͝
ʪ
͝
ϩɇ̷̷цϑɇ˙ʪ
recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract.
This product and its electronic accessories should not be mixed with other commercial wastes for disposal.
ͱθ
̈͝
˙ͱθ
͔
ɇϩ
̈ͱ
͝
ͱ
͝
Ɗɇ
͔
ϑЇ
͝
˝ࣱϑʪ
͝
Э
̈θͱ
͔
͝
ʪ
͝
ϩɇ̷ ʀͱ
͔
͔
̈ϩ
͔
ʪ
͝
ϩϑɇ
͝
ʒΧθͱʒЇʀϩࣛϑΧʪʀ
̈ѣʀθʪ˝Ї̷ ɇϩͱθц
obligations, e.g. REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/
corporatecitizenship/data_corner.html
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
When using R-410A, moisture or foreign substances may affect the performance and reliability of the
product. Safety precautions must be obeyed when installing the refrigerant pipe.
The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material
and thickness according to the regulations.
࡛ ŵࣛߦߣߢ
̈ϑɇαЇɇϑ
̈ࣛɇіʪͱϩθͱΧʪͱ˙ϩиͱθʪ˙θ
̈˝ʪθɇ
͝
ϩϑɇ
͝
ʒ
̈ϩ˵ɇϑϩͱɵʪʀ˵ɇθ˝ʪʒ
̈͝
̷
̈αЇ
̈ʒΧ˵ɇϑʪи˵ʪ
͝
ѣ̷̷
̈͝
˝
the refrigerant. (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause
product malfunction.)
ǽͱЇ
͔
Їϑϩʀͱ
͝
͝
ʪʀϩϩ˵ʪ
̈͝
ʒͱͱθЇ
̈͝
ϩϑ˙ͱθŵࣛߦߣߢθʪ˙θ
̈˝ʪθɇ
͝
ϩ࢏ŵʪ˙ʪθϩͱΧθͱʒЇʀϩʀɇϩɇ̷ͱ˝ϩͱѣ
͝
ʒͱЇϩϩ˵ʪ
models names for connectable indoor units. (If you connect the indoor units that are not designed for
R-410A, it cannot operated normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the
product. Also, hand over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible
for any installation related claims from the user occurred by neglecting warnings and cautions stated in
this manual. (Installer will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be
θʪ̷ ͱʀɇϩʪʒ˙ͱθ
̈͝
ʪЭ
̈ϩɇɵ̷ ʪθʪɇϑͱ
͝
ϑࡥΧ̷ ʪɇϑʪʀͱ
͝
ϩɇʀϩƊɇ
͔
ϑЇ
͝
˝ࣱϑαЇɇ̷
̈ѣʪʒʒʪɇ̷ ʪθϑ˙ͱθϑцϑϩʪ
͔
ɇ
̈θʀͱ
͝
ʒ
̈ϩ
̈ͱ
͝
ʪθϑ࢏
WARNING ࡛Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION ࡛Hazards or unsafe practices that may result in minor personal injury (to installer/user)
or property damage.
SEVERE WARNING SIGNS
͝
ϑЇ̷ ϩαЇɇ̷
̈ѣʪʒ
̈͝
ϑϩɇ̷̷ ʪθͱθʒʪɇ̷ ʪθ˙ͱθ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
ॷ Ǯ˵ʪ
͝
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
̈ϑʒͱ
͝
ʪɵцЇ
͝
αЇɇ̷
̈ѣʪʒΧʪθϑͱ
͝
ࡥΧθͱɵ̷ ʪ
͔
ϑϑЇʀ˵ɇϑиɇϩʪθ̷ʪɇ
̧ɇ˝ʪࡥʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ͱθѣθʪ
͔
ɇц
occur.
Ã
͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
иͱθ
̧
͔
Їϑϩɵʪʒͱ
͝
ʪΧθͱΧʪθ̷цɇʀʀͱθʒ
̈͝
˝ϩͱϩ˵
̈ϑ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
͔
ɇ
͝
Їɇ̷ ࢏
ॷ Ǯ˵ʪ
͝
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
̈ϑ
͝
ͱϩʒͱ
͝
ʪΧθͱΧʪθ̷цࡥ
̈ϩ
͔
ɇцʀɇЇϑʪиɇϩʪθ̷ʪɇ̧ɇ˝ʪࡥʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ͱθѣθʪ࢏
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding
ɇ̷̷ ͱиɇɵ̷ ʪϑɇ˙ʪϩц̷
͔
̈
̈ϩϑ
̈͝
ʀɇϑʪͱ˙θʪ˙θ
̈˝ʪθɇ
͝
ϩ̷ʪɇ
̧ɇ˝ʪ࢏Aͱ
͝
ϑЇ̷ ϩϩ˵ʪʒʪɇ̷ ʪθ˙ͱθΧθʪʀɇЇϩ
̈ͱ
͝
ɇθц
͔
ʪɇϑЇθʪɵʪ˙ͱθʪ
ϩ˵ʪ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
࢏
When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may
ͱʀʀЇθɇ
͝
ʒ
̈ϩ
͔
ɇцʀɇЇϑʪ
̟
̈͝
Їθц
Ƹϑʪϩ˵ʪϑЇΧΧ̷
̈ʪʒɇʀʀʪϑϑͱθ
̈ʪϑࡥϑΧʪʀ
̈ѣʪʒʀͱ
͔
Χͱ
͝
ʪ
͝
ϩϑɇ
͝
ʒϩͱͱ̷ ϑ˙ͱθϩ˵ʪ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
Do not use the pipe and the installation product used for the R-22 refrigerant.
ॷ ɇ̷
̈ЇθʪϩͱЇϑʪϩ˵ʪϑΧʪʀ
̈ѣʪʒʀͱ
͔
Χͱ
͝
ʪ
͝
ϩϑʀɇ
͝
ʀɇЇϑʪΧθͱʒЇʀϩ˙ɇ̷̷ ʒͱи
͝
ࡥиɇϩʪθ̷ʪɇ
̧ɇ˝ʪࡥʪ̷ ʪʀϩθ
̈ʀɇ̷ ϑ˵ͱʀ
̧ࡥɇ
͝
ʒ
ѣθʪ࢏࣑Ɵ˵ʪΧ
̈Χʪɇ
͝
ʒѤɇθʪʀͱ
͔
Χͱ
͝
ʪ
͝
ϩϑЇϑʪʒ˙ͱθŵࣛߤߤθʪ˙θ
̈˝ʪθɇ
͝
ϩ
͔
Їϑϩ
͝
ͱϩɵʪЇϑʪʒ࣒
Ã
͝
ϑϩɇ̷̷ ϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩͱ
͝
ɇ˵ɇθʒɇ
͝
ʒʪЭʪ
͝
Χ̷ ɇʀʪϩ˵ɇϩʀɇ
͝
ϑЇΧΧͱθϩ
̈ϩϑиʪ
̈˝˵ϩ࢏
If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
4
Safety precautions
A˵ʪʀ
̧ϩ˵ʪ˙ͱ̷̷ ͱи
̈͝
˝ɵʪ˙ͱθʪ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
ɇ
͝
ʒϑʪθЭ
̈ʀʪиͱθ
̧࢏
9ʪ˙ͱθʪиʪ̷ ʒ
̈͝
˝ࡥθʪ
͔
ͱЭʪʒɇ
͝
˝ʪθͱЇϑɇ
͝
ʒ
̈͝
Ѥɇ
͔
͔
ɇɵ̷ ʪϩ˵
̈͝
˝ϑϩ˵ɇϩ
͔
ɇцʀɇЇϑʪɇ
͝
ʪуΧ̷ ͱϑ
̈ͱ
͝
ɇ
͝
ʒѣθʪɇθͱЇ
͝
ʒϩ˵ʪиͱθ
̧
Before welding, remove the refrigerant from inside the pipe or the product.
If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and
cause the pipe to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Uͱ
͝
ͱϩ
͔
ͱʒ
̈˙цϩ˵ʪΧθͱʒЇʀϩͱ
͝
цͱЇθͱи
͝
ॷ ťͱϩʪ
͝
ϩ
̈ɇ̷ θ
̈ϑ
̧ͱ˙ʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ࡥѣθʪࡥΧθͱʒЇʀϩ˙ɇ̷
̈Їθʪͱθ
̟
̈͝
Їθц
̈уϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩϑʪʀЇθʪ̷цͱ
͝
˙ͱЇ
͝
ʒɇϩ
̈ͱ
͝
ϩͱθʪϑ
̈ϑϩϑϩθͱ
͝
˝и
̈͝ʒͱθʪɇθϩ˵αЇɇ
̧ʪ࢏
ॷ Ã˙ϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩ
̈ϑ
͝
ͱϩΧθͱΧʪθ̷цѣуʪʒࡥ
̈ϩϩЇθ
͝
ϑͱЭʪθɇ
͝
ʒɇʀʀ
̈ʒʪ
͝
ϩϑ
͔
ɇцͱʀʀЇθ
k̷ ʪʀϩθ
̈ʀиͱθ
̧
͔
Їϑϩɵʪʒͱ
͝
ʪɵцαЇɇ̷ ̈ѣʪʒΧʪθϑͱ
͝
ϑࡥʀͱ
͔
Χ̷ ц
̈͝
˝ϩ˵ʪ
͝
ɇϩ
̈ͱ
͝
ɇ̷ и
̈θ
̈͝
˝θʪ˝Ї̷ ɇϩ
̈ͱ
͝
ϑɇ
͝
ʒ
̈͝
ϑϩɇ̷̷ ʪʒ
ɇʀʀͱθʒ
̈͝
˝ϩͱϩ˵ʪ
̈͝
ϑϩθЇʀϩ
̈ͱ
͝
ϑϩɇϩʪʒ
̈͝
ϩ˵ʪ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
͔
ɇ
͝
Їɇ̷ и
̈ϩ˵̷ʪɇϑʪʒʀ
̈θʀЇ
̈ϩ࢏
ॷ AɇΧɇʀ
̈ϩцϑ˵ͱθϩɇ˝ʪͱ
͝
ϩ˵ʪ̷ʪɇϑʪʒʀ
̈θʀЇ
̈ϩɇ
͝
ʒ
͔
̈ΧθͱΧʪθ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
͔
ɇцʀɇЇϑʪʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ͱθѣθʪ࢏
đɇ
̧ʪϑЇθʪϩͱΧʪθ˙ͱθ
͔
˝θͱЇ
͝
ʒ
̈͝
˝иͱθ
̧
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper
grounding could cause electric shock.
Ǯ
̈θ
̈͝
˝
͔
Їϑϩɵʪʀͱ
͝
͝
ʪʀϩʪʒи
̈ϩ˵ϩ˵ʪʒʪϑ
̈˝
͝
ɇϩʪʒи
̈θʪϑɇ
͝
ʒ
̈ϩ
͔
ЇϑϩɵʪѣуʪʒϑʪʀЇθʪ̷цϑͱϩ˵ɇϩ
̈ϩʒͱʪϑ
͝
ͱϩɇΧΧ̷ ц
ɇ
͝
цʪуϩʪθ
͝
ɇ̷ ˙ͱθʀʪϩͱϩ˵ʪʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
Χɇθϩͱ˙ϩ˵ʪϩʪθ
͔
̈͝
ɇ̷ ϑ࢏
ॷ Ã˙ʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
˙ͱθѣуɇϩ
̈ͱ
͝
̈ϑ
͝
ͱϩΧθͱΧʪθ̷цʒͱ
͝
ʪࡥ
̈ϩ
͔
ɇцʀɇЇϑʪ˵ʪɇϩ˝ʪ
͝
ʪθɇϩ
̈ͱ
͝
ͱθѣθʪ࢏
Ęʪɇϩ̷цɇθθɇ
͝
˝ʪϩ˵ʪи
̈θʪϑ
̈͝
ϩ˵ʪʪ̷ʪʀϩθ
̈ʀɇ̷ Χɇθϩϑϩͱ
͔
ɇ
̧ʪϑЇθʪϩ˵ɇϩʪ̷ ʪʀϩθ
̈ʀɇ̷ ʀͱЭʪθ
̈ϑʀ̷ ͱϑʪʒϑʪʀЇθʪ̷ ци
̈ϩ˵ͱЇϩɇ
͝
ц˝ɇΧϑ࢏
ॷ Ã˙ϩ˵ʪʀͱЭʪθ
̈ϑ
͝
ͱϩΧθͱΧʪθ̷цʀ̷ ͱϑʪʒࡥ˵ʪɇϩ
͔
ɇц˝ʪ
͝
ʪθɇϩʪͱ
͝
ϩ˵ʪʪ̷ ʪʀϩθ
̈ʀɇ̷ ϩʪθ
͔
̈͝
ɇ̷ ɇ
͝
ʒʀɇЇϑʪʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ͱθѣθʪ࢏
kуʀ̷Їϑ
̈Эʪʀ
̈θʀЇ
̈ϩɵθʪɇ
̧ʪθ࣑đAA9ࡥkø9࣒
͔
Їϑϩɵʪ
̈͝
ϑϩɇ̷̷ ʪʒϩͱϩ˵ʪΧͱиʪθϑЇΧΧ̷ ц
When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-off and
̈ϩ
͔
ɇцʀɇЇϑʪʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧ͱθѣθʪ࢏
ॷ Uͱ
͝
ͱϩЇϑʪʒɇ
͔
ɇ˝ʪʒΧɇθϩϑ࢏Ãϩ
͔
ɇцʀɇЇϑʪѣθʪͱθʪ̷ ʪʀϩθ
̈ʀϑ˵ͱʀ
̧
You must cut-off the power before you work on, or adjust any power supply part for product installation,
͔ɇ
̈͝
ϩʪ
͝
ɇ
͝
ʀʪࡥθʪΧɇ
̈θͱθɇ
͝
цͱϩ˵ʪθϑʪθЭ
̈ʀʪϑ࢏
There is risk of electric shock.
Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high
pressure DC voltage is charged to those parts.
When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before
replacing/repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
Ã˙ϩ˵ʪθʪ˙θ
̈˝ʪθɇ
͝
ϩ˝ɇϑ̷ʪɇ
̧ϑʒЇθ
̈͝
˝ϩ˵ʪ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
ࡥцͱЇϑ˵ͱЇ̷ ʒЭʪ
͝
ϩ̷
̈ɇϩʪϩ˵ʪθͱͱ
͔
ॷ Ǯ˵ʪ
͝
ϩ˵ʪθʪ˙θ
̈˝ʪθɇ
͝
ϩ˝ɇϑ˝ʪϩϑ
̈͝
ʀͱ
͝
ϩɇʀϩи
̈ϩ˵Ѥɇ
͔
͔
ɇɵ̷ ʪϑЇɵϑϩɇ
͝
ʀʪࡥ
̈ϩ
͔
ɇц˝ʪ
͝
ʪθɇϩʪϩͱу
̈ʀ˝ɇϑ࢏
ɇϑ̷ʪɇ
̧ɇ˝ʪ
͔
Їϑϩɵʪʀ˵ʪʀ
̧ʪʒɇ˙ϩʪθ
̈͝
ϑϩɇ̷̷ ɇϩ
̈ͱ
͝
̈ϑʀͱ
͔
Χ̷ ʪϩʪʒ࢏
ॷ Ǯ˵ʪ
͝
ϩ˵ʪθʪ˙θ
̈˝ʪθɇ
͝
ϩ˝ɇϑ˝ʪϩϑ
̈͝
ʀͱ
͝
ϩɇʀϩи
̈ϩ˵Ѥɇ
͔
͔
ɇɵ̷ ʪϑЇɵϑϩɇ
͝
ʀʪࡥ
̈ϩ
͔
ɇц˝ʪ
͝
ʪθɇϩʪϩͱу
̈ʀ˝ɇϑ࢏
ǽͱЇʀɇ
͝
˝ʪϩɇ˙θͱϑϩɵ
̈ϩʪ
̈˙цͱЇ˝ʪϩ
̈͝
ʀͱ
͝
ϩɇʀϩи
̈ϩ˵ϩ˵ʪ̷ʪɇ
̧ʪʒθʪ˙θ
̈˝ʪθɇ
͝
ϩ˝ɇϑ࢏
Supply power to the product during winter time since the product will operate in protection mode itself
и˵ʪ
͝
ϩ˵ʪϩʪ
͔
ΧʪθɇϩЇθʪʒʪʀθʪɇϑʪɵʪ̷ ͱиߢঌA࢏
If you cut-off the power, compressor protection mode cannot be operated and may cause damage to the product.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given supervision or
̈͝ϑϩθЇʀϩ
̈ͱ
͝
ʀͱ
͝
ʀʪθ
̈͝
͝
˝Їϑʪͱ˙ϩ˵ʪɇΧΧ̷
̈ɇ
͝
ʀʪɵцɇΧʪθϑͱ
͝
θʪϑΧͱ
͝
ϑ̈ɵ̷ ʪ˙ͱθϩ˵ʪ
̈θϑɇ˙ʪϩц࢏A˵̷
̈ʒθʪ
͝
ϑ˵ͱЇ̷ ʒɵʪ
ϑЇΧʪθЭ
̈ϑʪʒϩͱʪ
͝
ϑЇθʪϩ˵ɇϩϩ˵ʪцʒͱ
͝
ͱϩΧ̷ ɇци
̈ϩ˵ϩ˵ʪɇΧΧ̷
̈ɇ
͝
ʀʪ࢏
5
ENGLISH
For use in Europe : This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand the hazards
̈͝Эͱ̷Эʪʒ࢏A˵̷
̈ʒθʪ
͝
ϑ˵ɇ̷̷ 
͝
ͱϩΧ̷ ɇци
̈ϩ˵ϩ˵ʪɇΧΧ̷
̈ɇ
͝
ʀʪ࢏A̷ ʪɇ
̈͝
͝
˝ɇ
͝
ʒЇϑʪθ
͔
ɇ
̈͝
ϩʪ
͝
ɇ
͝
ʀʪϑ˵ɇ̷̷ 
͝
ͱϩɵʪ
͔
ɇʒʪɵц
ʀ˵̷
̈ʒθʪ
͝
и
̈ϩ˵ͱЇϩϑЇΧʪθЭ
̈ϑ
̈ͱ
͝
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so
ϩ˵ɇϩиɇϩʪθʒθɇ
̈͝
ϑͱЇϩϑ
͔
ͱͱϩ˵̷ ц࢏Ã˙
͝
ͱϩࡥΧ
̈Χʪ
͔
ɇц˙θʪʪіʪͱθɵЇθϑϩϑʒЇθ
̈͝
˝и
̈͝
ϩʪθϩ
͔
̈ʪɇ
͝
ʒʀɇЇϑʪʒɇ
͔
ɇ˝ʪϩͱϩ˵ʪ
ΧθͱʒЇʀϩͱθиɇϩʪθ̷ʪɇ
̧ɇ˝ʪ࢏
When the draining work is not done properly, water leak may occur and cause property damage.
Ã
͝
ϑϩɇ̷̷ ϩ˵ʪΧͱиʪθʀɇɵ̷ ʪɇ
͝
ʒʀͱ
͔
͔
Ї
̈͝
ʀɇϩ
̈ͱ
͝
ʀɇɵ̷ ʪͱ˙ϩ˵ʪ
̈͝
ʒͱͱθɇ͝ʒͱЇϩʒͱͱθЇ
̈͝
ϩɇϩ̷ʪɇϑϩߣ࢏͔ߧɇиɇц˙θͱ
͔
ϩ˵ʪ
ʪ̷ ʪʀϩθ
̈ʀɇΧΧ̷
̈ɇ
͝
ʀʪϑɇ
͝
ʒ
̈͝
ϑϩɇ̷̷ 
̈ϩɇϩ̷ʪɇϑϩ͔ߤɇиɇц˙θͱ
͔
ϩ˵ʪ̷
̈˝˵ϩ
̈͝
͝
˝ʀͱ
͝
ʒЇʀϩͱθ
Noise may be generated from the electronic devices, depending on the status of the electric wave.
Ã
͝
ϑϩɇ̷̷ ϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩи
̈ϩ˵
̈͝
ϩ˵ʪɇ
͝
˝̷ ʪϑϩɇϩʪʒ
̈͝
ϩ˵ʪϩɇɵ̷ ʪࡥɇʀʀͱθʒ
̈͝
˝ϩͱϩ˵ʪ˵ʪ
̈˝˵ϩͱ˙ϩ˵ʪɵЇ̷
̈ʒ
̈͝
˝࢏
Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very
high.
Make sure that the pipes does not get any weaker by welding it too much.
Make sure to install the product away from children’s’ reach. (Sharp parts of the heat exchanger is may
cause personal injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod Protective angle:
ߤߧઘड़ߧߧઘ
Height of the building Protection control
20m or less ߧߧઘ
40m or less ߥߧઘ
60m or less ߤߧઘ
Ã
͝
ϑϩɇ̷̷ ϩ˵ʪ
̈͝
ʒͱͱθЇ
̈͝
ϩ ̈˝˵ϩ
̈͝
˝ɇΧΧɇθɇϩЇϑϩ˵ɇϩЇϑʪϑɇиɇц˙θͱ
͔
̷ ɵɇ̷̷ ɇϑϩϑϩɇɵ̷
̈
̈
іʪθ
If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Uͱ
͝
ͱϩ
̈͝
ϑϩɇ̷̷ ϩ˵ʪΧθͱʒЇʀϩ
̈͝
˙ͱ̷̷ ͱи
̈͝
˝Χ̷ ɇʀʪϑ࢏
Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
The place where there is mineral oil or arsenic acid.
Those parts may get damaged due to burned resin and cause water leakage or product may fall.
ৄ Ɵ˵ʪʪ˙ѣʀ
̈ʪ
͝
ʀцͱ˙ϩ˵ʪ˵ʪɇϩʪуʀ˵ɇ
͝
˝ʪθ
͔
ɇцθʪʒЇʀʪͱθΧθͱʒЇʀϩ
͔
ɇцɵθʪɇ
̧
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.
The air conditioner may not operate normally due to problems in control system.
The place where there is a danger of combustible gas leakage or place where thinner or gasoline is
handled.
ৄ ࣑Ɵ˵ʪθʪ
̈ϑθ
̈ϑ
̧ͱ˙ѣθʪͱθʪуΧ̷ ͱϑ
̈ͱ
͝
࢏࣒
Ɵ˵ʪΧ̷ ɇʀʪи
̈ϩ˵ʀɇθɵͱ
͝
ѣɵʪθͱθѤɇ
͔
͔
ɇɵ̷ ʪʒЇϑϩ࢏
The place near seashore or hot spring where there is risk of outdoor unit corrosion.
6
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor
units. (Do not use T-joint)
You cannot operate normally if you do not complete the trial operation through outdoor unit key mode.
You must use KEY MODE to run trial operation.
DVM S air conditioner uses R-410A refrigerant.
Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
Make sure to note that outdoor unit combination is different from DVM PLUS III and IV.
The length of maximum piping, level difference, the quantity of connectable indoor units, the installation
at the outdoor joints and the outdoor unit combinations are different from the conventional models.
If the pipe length is over 2 m between outdoor units, make traps to prevent oil stagnation. Oil stagnation
may occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
Preparing for installation
ĮЇϩʒͱͱθЇ
̈͝
ϩʀ̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Small type DVM S Large A type DVM S Large B type
Appearance
Packaging material disposition
࡛Safely store or dispose the packaging materials.
Sharp metals such as nails or wooden material packaging that may break into pieces become a
cause for personal injury.
Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children.
Children may put them over their face, which is very dangerous since it may lead them to
suffocation.
CAUTION
7
ENGLISH
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and
heating capacity of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit
ʀɇΧɇʀ
̈ϩцߢ࢏ߧ
נ࣑ĮЇϩʒͱͱθЇ
̈͝
ϩʀɇΧɇʀ
̈ϩц࣒ख़Ɵͱϩɇ̷ ʀɇΧɇʀ
̈ϩцͱ˙ϩ˵ʪʀͱ
͝
͝
ʪʀϩʪʒ
̈͝
ʒͱͱθЇ
̈͝
ϩϑख़ߣ࢏ߥ
נ࣑ĮЇϩʒͱͱθЇ
̈͝
ϩ
capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor
unit is set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can
ɵʪɇϑϑ
̈˝
͝
ʪʒ˙θͱ
͔
ߢड़ߨߥ࢏Ã˙ϩ˵ʪ
̈͝
ʒͱͱθЇ
̈͝
ϩɇʒʒθʪϑϑиɇϑɇϑϑ
̈˝
͝
ʪʒ˙θͱ
͔
ߨߦड़߫ߩࡥkߤߢߣʪθθͱθи̷̷
̈ͱʀʀЇθ
đɇу
͔
̈Ї
͔
ߥߤǮɇ̷̷͔ࣛͱЇ
͝
ϩϩцΧʪ
̈͝
ʒͱͱθЇ
̈͝
ϩϑи
̈ϩ˵kkǤ࣑đ७७७७ĘůUk²७ࡥđ७७७âĘǤ७࣒ʀɇ
͝
ɵʪ
connected.
Do not install 1st-generation MCU and 2nd-generation MCU together.
ৄ ߣϑϩ
˝ʪ
͝
ʪθɇϩ
̈ͱ
͝
đAƸࡤđAƸࣛƊ७Ękk७ĘࡥđAƸࣛƊߤĘkçߣĘ
ৄ ͝ߤʒ
˝ʪ
͝
ʪθɇϩ
̈ͱ
͝
đAƸࡤđAƸࣛƊ७ĘkçߤĘࡥđAƸࣛƊߦĘkçߥĘࡥđAƸࣛƊߣĘkçߣĘ
࡛Use the following table to determine the size and number of outdoor units needed to achieve
ϩ˵ʪऌʀɇΧɇʀ
̈ϩцθʪαЇ
̈θʪ
͔
ʪ
͝
ϩϑ࢏
CAUTION
Standard type (Heat pump)
Model mane of combination
AM080JX
VAGH/EU
AM100JX
VAGH/EU
AM120JX
VAGH/EU
AM140KX
VAGH/ET
AM160KX
VAGH/ET
AM180KX
VAGH/ET
Number of individual outdoor units 1 1 1 1 1 1
Combined
outdoor unit
AM080JXVAGH/EU
1
AM100JXVAGH/EU
1
AM120JXVAGH/EU
1
AM140KXVAGH/ET
1
AM160KXVAGH/ET
1
AM180KXVAGH/ET
1
AM200KXVAGH/ET
AM220KXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
AM280KXVAGH/ET
AM300KXVAGH/ET
Rated capacity Cooling (kW) 22.4 28 33.6 40 45 50.4
Heating (kW) 25.2 31.5 37.8 45 50.4 56.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW) 11.2 14 16.8 20 22.5 25.2
Maximum (kW) 29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units 14 18 21 26 29 32
8
Preparing for installation
Model mane of combination
AM200KX
VAGH/ET
AM220KX
VAGH/ET
AM240KX
VAGH/ET
AM260KX
VAGH/ET
AM280KX
VAGH/ET
AM300KX
VAGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
AM120JXVAGH/EU
AM140KXVAGH/ET
AM160KXVAGH/ET
AM180KXVAGH/ET
AM200KXVAGH/ET
1
AM220KXVAGH/ET
1
AM240KXVAGH/ET
1
AM260KXVAGH/ET
1
AM280KXVAGH/ET
1
AM300KXVAGH/ET
1
Rated capacity Cooling (kW)
56 61.6 67.2 72.8 78.6 84
Heating (kW)
63 69.3 75.6 81.9 88.2 94.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
28 30.8 33.6 36.4 39.3 42
Maximum (kW)
72.8 80.1 87.4 94.6 102.2 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model mane of combination
AM320KX
VAGH/ET
AM340KX
VAGH/ET
AM360KX
VAGH/ET
AM380KX
VAGH/ET
AM400KX
VAGH/ET
AM420KX
VAGH/ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
1
AM120JXVAGH/EU
1
AM140KXVAGH/ET
1
AM160KXVAGH/ET
1
AM180KXVAGH/ET
1
AM200KXVAGH/ET
1
AM220KXVAGH/ET
1 1 1 1 1 1
AM240KXVAGH/ET
AM260KXVAGH/ET
AM280KXVAGH/ET
AM300KXVAGH/ET
Rated capacity Cooling (kW)
89.6 95.2 101.6 106.6 112 117.6
Heating (kW)
100.8 107.1 114.3 119.7 126 132.3
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
44.8 47.6 50.8 53.3 56 58.8
Maximum (kW)
116.5 123.8 132.1 138.6 145.6 152.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
9
ENGLISH
Model mane of combination
AM440KX
VAGH/ET
AM460KX
VAGH/ET
AM480KX
VAGH/ET
AM500KX
VAGH/ET
AM520KX
VAGH/ET
AM540KX
VAGH/ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
AM120JXVAGH/EU
AM140KXVAGH/ET
AM160KXVAGH/ET
1
AM180KXVAGH/ET
1
AM200KXVAGH/ET
1
AM220KXVAGH/ET
2 1
AM240KXVAGH/ET
1
AM260KXVAGH/ET
AM280KXVAGH/ET
AM300KXVAGH/ET
1 1 1 1 1
Rated capacity Cooling (kW)
123.2 129 134.4 140 145.6 151.2
Heating (kW)
138.6 144.9 151.2 157.5 163.8 170.1
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
61.6 64.5 67.2 70 72.8 75.6
Maximum (kW)
160.2 167.7 174.7 182.0 189.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM560KX
VAGH/ET
AM580KX
VAGH/ET
AM600KX
VAGH/ET
AM620KX
VAGH/ET
AM640KX
VAGH/ET
AM660KX
VAGH/ET
Number of individual outdoor units
2 2 2 3 3 3
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
1
AM120JXVAGH/EU
1
AM140KXVAGH/ET
1
AM160KXVAGH/ET
AM180KXVAGH/ET
AM200KXVAGH/ET
AM220KXVAGH/ET
111
AM240KXVAGH/ET
AM260KXVAGH/ET
1
AM280KXVAGH/ET
1
AM300KXVAGH/ET
1 1 2 1 1 1
Rated capacity Cooling (kW)
156.8 162.6 168 173.6 179.2 185.6
Heating (kW)
176.4 182.7 189 195.3 201.6 208.8
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.3 84 86.8 89.6 92.8
Maximum (kW)
203.8 211.4 218.4 225.7 233.0 241.3
Maximum number of connectable
indoor units
64 64 64 64 64 64
10
Preparing for installation
Model mane of combination
AM680KX
VAGH1ET
AM700KX
VAGH/ET
AM720KX
VAGH/ET
AM740KX
VAGH/ET
AM760KX
VAGH/ET
AM780KX
VAGH/ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
AM120JXVAGH/EU
AM140KXVAGH/ET
AM160KXVAGH/ET
1
AM180KXVAGH/ET
1
AM200KXVAGH/ET
1
AM220KXVAGH/ET
1 1 1 2 1 1
AM240KXVAGH/ET
1
AM260KXVAGH/ET
1
AM280KXVAGH/ET
AM300KXVAGH/ET
1 1 1 1 1 1
Rated capacity Cooling (kW)
190.6 196 201.6 207.2 212.8 218.4
Heating (kW)
214.2 220.5 226.8 233.1 239.4 245.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
95.3 98 100.8 103.6 106.4 109.2
Maximum (kW)
247.8 254.8 262.1 269.4 276.6 283.9
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM800KX
VAGH/ET
AM820KX
VAGH/ET
AM840KX
VAGH/ET
AM860KX
VAGH/ET
AM880KX
VAGH/ET
AM900KX
VAGH/ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVAGH/EU
AM100JXVAGH/EU
AM120JXVAGH/EU
AM140KXVAGH/ET
AM160KXVAGH/ET
AM180KXVAGH/ET
AM200KXVAGH/ET
AM220KXVAGH/ET
1 1
AM240KXVAGH/ET
1
AM260KXVAGH/ET
1
AM280KXVAGH/ET
1 1
AM300KXVAGH/ET
1 2 2 2 2 3
Rated capacity Cooling (kW)
224.2 229.6 235.2 240.8 246.6 252
Heating (kW)
252 258.3 264.6 270.9 277.2 283.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
112.1 114.8 117.6 120.4 123.3 126
Maximum (kW)
291.5 298.5 305.8 313.0 320.6 327.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
11
ENGLISH
Premium compact type (Heat pump)
Model mane of combination
AM080JX
VHGH/EU
AM100JX
VHGH/EU
AM120JX
VHGH/EU
AM140JX
VHGH/ET
AM160JX
VHGH/ET
AM180JX
VHGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGH/EU 1
AM100JXVHGH/EU 1
AM120JXVHGH/EU 1
AM140JXVHGH/ET 1
AM160JXVHGH/ET 1
AM180JXVHGH/ET 1
AM200JXVHGH/ET
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
AM280KXVGGH/ET
AM300KXVAGH/ET
Rated capacity Cooling (kW)
22.4 28 33.6 40 45 50.4
Heating (kW)
25.2 31.5 37.8 45 50.4 56.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
11.2 14 16.8 20 22.5 25.2
Maximum (kW)
29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
Model mane of combination
AM200JX
VHGH/ET
AM220JX
VHGH/ET
AM240KX
VGGH/ET
AM260KX
VGGH/ET
AM280KX
VGGH/ET
AM300KX
VAGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET
AM160JXVHGH/ET
AM180JXVHGH/ET
AM200JXVHGH/ET 1
AM220JXVHGH/ET 1
AM240KXVGGH/ET 1
AM260KXVGGH/ET 1
AM280KXVGGH/ET 1
AM300KXVAGH/ET 1
Rated capacity Cooling (kW)
56 61.6 67.2 72.8 78.6 84
Heating (kW)
63 69.3 75.6 81.9 88.2 94.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
28 30.8 33.6 36.4 39.3 42
Maximum (kW)
72.8 80.1 87.4 94.6 102.2 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
12
Preparing for installation
Model mane of combination
AM320KX
VGGH1ET
AM340KX
VGGH1ET
AM360KX
VGGH1ET
AM380KX
VGGH1ET
AM400KX
VGGH1ET
AM420KX
VGGH1ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU 1 1
AM140JXVHGH/ET 1
AM160JXVHGH/ET 1
AM180JXVHGH/ET 1
AM200JXVHGH/ET 1 1
AM220JXVHGH/ET 1 1 1 1 1
AM240KXVGGH/ET
AM260KXVGGH/ET
AM280KXVGGH/ET
AM300KXVAGH/ET
Rated capacity Cooling (kW)
89.6 95.2 101.6 106.6 112 117.6
Heating (kW)
100.8 107.1 114.3 119.7 126 132.3
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
44.8 47.6 50.8 53.3 56 58.8
Maximum (kW)
116.5 123.8 132.1 138.6 145.6 152.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
Model mane of combination
AM440KX
VGGH1ET
AM460KX
VGGH1ET
AM480KX
VGGH1ET
AM500KX
VGGH1ET
AM520KX
VGGH1ET
AM540KX
VGGH1ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET 1
AM160JXVHGH/ET 1
AM180JXVHGH/ET 1
AM200JXVHGH/ET 1
AM220JXVHGH/ET 1
AM240KXVGGH/ET 1
AM260KXVGGH/ET
AM280KXVGGH/ET
AM300KXVAGH/ET 1 1 1 1 1 1
Rated capacity Cooling (kW)
124 129 134.4 140 145.6 151.2
Heating (kW)
139.5 144.9 151.2 157.5 163.8 170.1
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
62 64.5 67.2 70 72.8 75.6
Maximum (kW)
161.2 167.7 174.7 182.0 189.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
13
ENGLISH
Model mane of combination
AM560KX
VGGH1ET
AM580KX
VGGH1ET
AM600KX
VGGH1ET
AM620KX
VGGH1ET
AM640KX
VGGH1ET
AM660KX
VGGH1ET
Number of individual outdoor units
2 2 2 3 3 3
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU 1 1
AM140JXVHGH/ET 1
AM160JXVHGH/ET
AM180JXVHGH/ET
AM200JXVHGH/ET 1
AM220JXVHGH/ET 1 1
AM240KXVGGH/ET
AM260KXVGGH/ET 1
AM280KXVGGH/ET 1
AM300KXVAGH/ET 1 1 2 1 1 1
Rated capacity Cooling (kW)
156.8 162.6 168 173.6 179.2 185.6
Heating (kW)
176.4 182.7 189 195.3 201.6 208.8
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.3 84 86.8 89.6 92.8
Maximum (kW)
203.8 211.4 218.4 225.7 233.0 241.3
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM680KX
VGGH1ET
AM700KX
VGGH1ET
AM720KX
VGGH1ET
AM740KX
VGGH1ET
AM760KX
VGGH1ET
AM780KX
VGGH1ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET
AM160JXVHGH/ET 1
AM180JXVHGH/ET 1
AM200JXVHGH/ET 1
AM220JXVHGH/ET 1 1 1 2 1 1
AM240KXVGGH/ET 1
AM260KXVGGH/ET 1
AM280KXVGGH/ET
AM300KXVAGH/ET 1 1 1 1 1 1
Rated capacity Cooling (kW)
190.6 196 201.6 207.2 212.8 218.4
Heating (kW)
214.2 220.5 226.8 233.1 239.4 245.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
95.3 98 100.8 103.6 106.4 109.2
Maximum (kW)
247.8 254.8 262.1 269.4 276.6 283.9
Maximum number of connectable
indoor units
64 64 64 64 64 64
14
Preparing for installation
Model mane of combination
AM800KX
VGGH1ET
AM820KX
VGGH1ET
AM840KX
VGGH1ET
AM860KX
VGGH1ET
AM880KX
VGGH1ET
AM900KX
VGGH1ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET
AM160JXVHGH/ET
AM180JXVHGH/ET
AM200JXVHGH/ET
AM220JXVHGH/ET 1 1
AM240KXVGGH/ET 1
AM260KXVGGH/ET 1
AM280KXVGGH/ET 1 1
AM300KXVAGH/ET 1 2 2 2 2 3
Rated capacity Cooling (kW)
224.2 229.6 235.2 240.8 246.6 252
Heating (kW)
252 258.3 264.6 270.9 277.2 283.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
112.1 114.8 117.6 120.4 123.3 126
Maximum (kW)
291.5 298.5 305.8 313.0 320.6 327.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
ťθʪ
͔
̈Ї
͔
ʪ
͝
ʪθ˝цʪ˙ѣʀ
̈ʪ
͝
ʀцϩцΧʪ
²ʪɇϩΧЇ
͔
Χ
Model mane of combination
AM080JX
VHGH/EU
AM100JX
VHGH/EU
AM120JX
VHGH/EU
AM140JX
VHGH/ET
AM160JX
VHGH/ET
AM180JX
VHGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGH/EU 1
AM100JXVHGH/EU 1
AM120JXVHGH/EU 1
AM140JXVHGH/ET 1
AM160JXVHGH/ET 1
AM180JXVHGH/ET 1
AM200JXVHGH/ET
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Rated capacity Cooling (kW)
22.4 28 33.6 40 45 50.4
Heating (kW)
25.2 31.5 37.8 45 50.4 56.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
11.2 14 16.8 20 22.5 25.2
Maximum (kW)
29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
15
ENGLISH
Model mane of combination
AM200JX
VHGH/ET
AM220KX
VGGH2ET
AM240KX
VGGH2ET
AM260KX
VGGH2ET
AM280KX
VGGH2ET
AM300KX
VGGH2ET
Number of individual outdoor units
1 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGH/EU 1 1
AM100JXVHGH/EU 1
AM120JXVHGH/EU 1 2 1
AM140JXVHGH/ET
AM160JXVHGH/ET
AM180JXVHGH/ET 1 1
AM200JXVHGH/ET 1 1
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Rated capacity Cooling (kW)
56 61.6 67.2 72.8 78.4 84
Heating (kW)
63 69.3 75.6 81.9 88.2 94.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
28 30.8 33.6 36.4 39.2 42
Maximum (kW)
72.8 80.1 87.4 94.6 101.9 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model mane of combination
AM320KX
VGGH2ET
AM340KX
VGGH2ET
AM360KX
VGGH2ET
AM380KX
VGGH2ET
AM400KX
VGGH2ET
AM420KX
VGGH2ET
Number of individual outdoor units
2 3 2 2 3 3
Combined
outdoor unit
AM080JXVHGH/EU 2 1 1
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET 1 1 1
AM160JXVHGH/ET
AM180JXVHGH/ET 1 1 2 1 1
AM200JXVHGH/ET 1 1
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Rated capacity Cooling (kW)
90.4 95.2 100.8 106.4 112.8 118.4
Heating (kW)
101.7 107.1 113.4 119.7 126.9 133.2
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
45.2 47.6 50.4 53.2 56.4 59.2
Maximum (kW)
117.5 123.8 131.0 138.3 146.6 153.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
16
Preparing for installation
Model mane of combination
AM440KX
VGGH2ET
AM460KX
VGGH2ET
AM480KX
VGGH2ET
AM500KX
VGGH2ET
AM520KX
VGGH2ET
AM540KX
VGGH2ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGH/EU 111 11
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET 1
AM160JXVHGH/ET
AM180JXVHGH/ET 2 1 2 1
AM200JXVHGH/ET 1 2 1
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET 1 1
Rated capacity Cooling (kW)
123.2 128.8 134.4 140.8 145.6 151.2
Heating (kW)
138.6 144.9 151.2 158.4 163.8 170.1
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
61.6 64.4 67.2 70.4 72.8 75.6
Maximum (kW)
160.2 167.4 174.7 183.0 189.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM560KX
VGGH2ET
AM580KX
VGGH2ET
AM600KX
VGGH2ET
AM620KX
VGGH2ET
AM640KX
VGGH2ET
AM660KX
VGGH2ET
Number of individual outdoor units
3 3 3 4 4 4
Combined
outdoor unit
AM080JXVHGH/EU 1 1 1
AM100JXVHGH/EU
AM120JXVHGH/EU 1 1
AM140JXVHGH/ET
AM160JXVHGH/ET
AM180JXVHGH/ET 1 2 3 2 3
AM200JXVHGH/ET 1
AM220JXVHGH/ET
AM240KXVGGH/ET 1 1
AM260KXVGGH/ET 1 1
Rated capacity Cooling (kW)
156.8 162.4 168 173.6 179.2 184.8
Heating (kW)
176.4 182.7 189 195.3 201.6 207.9
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.2 84 86.8 89.6 92.4
Maximum (kW)
203.8 211.1 218.4 225.7 233.0 240.2
Maximum number of connectable
indoor units
64 64 64 64 64 64
17
ENGLISH
Model mane of combination
AM680KX
VGGH2ET
AM700KX
VGGH2ET
AM720KX
VGGH2ET
AM740KX
VGGH2ET
AM760KX
VGGH2ET
AM780KX
VGGH2ET
Number of individual outdoor units
4 4 4 4 4 4
Combined
outdoor unit
AM080JXVHGH/EU 1
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET 1
AM160JXVHGH/ET
AM180JXVHGH/ET 3 2 4 3 2 1
AM200JXVHGH/ET 1 2 3
AM220JXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET 1
Rated capacity Cooling (kW)
191.2 196 201.6 207.2 212.8 218.4
Heating (kW)
215.1 220.5 226.8 233.1 239.4 245.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
95.6 98 100.8 103.6 106.4 109.2
Maximum (kW)
248.6 254.8 262.1 269.4 276.6 283.9
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM800KX
VGGH2ET
AM820KX
VGGH2ET
AM840KX
VGGH2ET
AM860KX
VGGH2ET
AM880KX
VGGH2ET
AM900KX
VGGH2ET
Number of individual outdoor units
4 4 4 4 4 4
Combined
outdoor unit
AM080JXVHGH/EU
AM100JXVHGH/EU
AM120JXVHGH/EU
AM140JXVHGH/ET
AM160JXVHGH/ET
AM180JXVHGH/ET 3 2 1 1 1 1
AM200JXVHGH/ET 1 2 1 1 1
AM220JXVHGH/ET 1
AM240KXVGGH/ET 1
AM260KXVGGH/ET 1 1 1 1 1 2
Rated capacity Cooling (kW)
224 229.6 235.2 240.8 246.4 252
Heating (kW)
252 258.3 264.6 270.9 277.2 283.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
112 114.8 117.6 120.4 123.2 126
Maximum (kW)
291.2 298.5 305.8 313.0 320.3 327.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
18
Preparing for installation
Essential type (Heat pump)
Model mane of combination
AM100MX
VDGH/ET
AM120MX
VDGH/ET
AM140MX
VDGH/ET
AM160MX
VDGH/ET
AM180MX
VDGH/ET
AM200MX
VDGH/ET
Number of individual outdoor units
1 1 1 1 1 2
Combined
outdoor unit
AM100MXVDGH/ET 1 2
AM120MXVDGH/ET 1
AM140MXVDGH/ET 1
AM160MXVDGH/ET 1
AM180MXVDGH/ET 1
Rated capacity Cooling (kW)
28.0 33.6 40.0 45.0 50.4 56.0
Heating (kW)
31.5 37.8 45.0 50.4 56.7 63.0
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
14.0 16.8 20.0 22.5 25.2 28.0
Maximum (kW)
36.4 43.7 52.0 58.5 65.5 72.8
Maximum number of connectable
indoor units
18 21 26 29 32 36
Model mane of combination
AM220MX
VDGH/ET
AM240MX
VDGH/ET
AM260MX
VDGH/ET
AM280MX
VDGH/ET
AM300MX
VDGH/ET
AM320MX
VDGH/ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM100MXVDGH/ET 1
AM120MXVDGH/ET 1 2 1 1
AM140MXVDGH/ET 1 2 1
AM160MXVDGH/ET
AM180MXVDGH/ET 1 1
Rated capacity Cooling (kW)
61.6 67.2 73.6 80.0 84.0 90.4
Heating (kW)
69.3 75.6 82.8 90.0 94.5 101.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
30.8 33.6 36.8 40.0 42.0 45.2
Maximum (kW)
80.1 87.4 95.7 104.0 109.2 117.5
Maximum number of connectable
indoor units
40 43 47 51 54 58
Model mane of combination
AM340MX
VDGH/ET
AM360MX
VDGH/ET
AM380MX
VDGH/ET
AM400MX
VDGH/ET
Number of individual outdoor units
2 2 3 3
Combined
outdoor unit
AM100MXVDGH/ET
AM120MXVDGH/ET 2 1
AM140MXVDGH/ET 1 2
AM160MXVDGH/ET 1
AM180MXVDGH/ET 1 2
Rated capacity Cooling (kW)
95.4 100.8 107.2 113.6
Heating (kW)
107.1 113.4 120.6 127.8
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
47.7 50.4 53.6 56.8
Maximum (kW)
124.0 131.0 139.4 147.7
Maximum number of connectable
indoor units
61 64 64 64
20
Preparing for installation
Model mane of combination
AM320MX
VGNR1ET
AM340MX
VGNR1ET
AM360MX
VGNR1ET
AM380MX
VGNR1ET
AM400MX
VGNR1ET
AM420MX
VGNR1ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGR/EU
AM100JXVHGR/EU
AM120JXVHGR/EU 1 1
AM140JXVHGR/ET 1
AM160JXVHGR/ET 1
AM180JXVHGR/ET 1
AM200JXVHGR/ET 1 1
AM220JXVHGR/ET 11111
AM240MXVGNR/ET
AM260MXVGNR/ET
AM280MXVGNR/ET
AM300MXVANR/ET
Rated capacity Cooling (kW)
89.6 95.2 101.6 106.6 112 117.6
Heating (kW)
100.8 107.1 114.3 119.7 126 132.3
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
44.8 47.6 50.8 53.3 56 58.8
Maximum (kW)
116.5 123.8 132.1 138.6 145.6 152.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
Model mane of combination
AM440MX
VGNR1ET
AM460MX
VGNR1ET
AM480MX
VGNR1ET
AM500MX
VGNR1ET
AM520MX
VGNR1ET
AM540MX
VGNR1ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGR/EU
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET 1
AM160JXVHGR/ET 1
AM180JXVHGR/ET 1
AM200JXVHGR/ET 1
AM220JXVHGR/ET 1
AM240MXVGNR/ET 1
AM260MXVGNR/ET
AM280MXVGNR/ET
AM300MXVANR/ET 111111
Rated capacity Cooling (kW)
124 129 134.4 140 145.6 151.2
Heating (kW)
139.5 144.9 151.2 157.5 163.8 170.1
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
62 64.5 67.2 70 72.8 75.6
Maximum (kW)
161.2 167.7 174.7 182.0 189.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
22
Preparing for installation
Model mane of combination
AM800MX
VGNR1ET
AM820MX
VGNR1ET
AM840MX
VGNR1ET
AM860MX
VGNR1ET
AM880MX
VGNR1ET
AM900MX
VGNR1ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGR/EU
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET
AM160JXVHGR/ET
AM180JXVHGR/ET
AM200JXVHGR/ET
AM220JXVHGR/ET 1 1
AM240MXVGNR/ET 1
AM260MXVGNR/ET 1
AM280MXVGNR/ET 1 1
AM300MXVANR/ET 1 2 2 2 2 3
Rated capacity Cooling (kW)
224.2 229.6 235.2 240.8 246.6 252
Heating (kW)
252 258.3 264.6 270.9 277.2 283.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
112.1 114.8 117.6 120.4 123.3 126
Maximum (kW)
291.5 298.5 305.8 313.0 320.6 327.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
ťθЇʪ͝ʪθ˝цʪ˙ѣʀ̈ʪ͝ʀцϩцΧʪ²ʪɇϩθʪʀͱЭʪθц
Model mane of combination
AM080JX
VHGR/EU
AM100JX
VHGR/EU
AM120JX
VHGR/EU
AM140JX
VHGR/ET
AM160JX
VHGR/ET
AM180JX
VHGR/ET
Number of individual outdoor units
111111
Combined
outdoor unit
AM080JXVHGR/EU 1
AM100JXVHGR/EU 1
AM120JXVHGR/EU 1
AM140JXVHGR/ET 1
AM160JXVHGR/ET 1
AM180JXVHGR/ET 1
AM200JXVHGR/ET
AM220JXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET
Rated capacity Cooling (kW)
22.4 28 33.6 40 45 50.4
Heating (kW)
25.2 31.5 37.8 45 50.4 56.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
11.2 14 16.8 20 22.5 25.2
Maximum (kW)
29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
23
ENGLISH
Model mane of combination
AM200JX
VHGR/ET
AM220MX
VGNR2ET
AM240MX
VGNR2ET
AM260MX
VGNR2ET
AM280MX
VGNR2ET
AM300MX
VGNR2ET
Number of individual outdoor units
1 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGR/EU 1 1
AM100JXVHGR/EU 1
AM120JXVHGR/EU 1 2 1
AM140JXVHGR/ET
AM160JXVHGR/ET
AM180JXVHGR/ET 1 1
AM200JXVHGR/ET 1 1
AM220JXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET
Rated capacity Cooling (kW)
56 61.6 67.2 72.8 78.4 84
Heating (kW)
63 69.3 75.6 81.9 88.2 94.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
28 30.8 33.6 36.4 39.2 42
Maximum (kW)
72.8 80.1 87.4 94.6 101.9 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model mane of combination
AM320MX
VGNR2ET
AM340MX
VGNR2ET
AM360MX
VGNR2ET
AM380MX
VGNR2ET
AM400MX
VGNR2ET
AM420MX
VGNR2ET
Number of individual outdoor units
232233
Combined
outdoor unit
AM080JXVHGR/EU 2 1 1
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET 1 1 1
AM160JXVHGR/ET
AM180JXVHGR/ET 1 1 2 1 1
AM200JXVHGR/ET 1 1
AM220JXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET
Rated capacity Cooling (kW)
90.4 95.2 100.8 106.4 112.8 118.4
Heating (kW)
101.7 107.1 113.4 119.7 126.9 133.2
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
45.2 47.6 50.4 53.2 56.4 59.2
Maximum (kW)
117.5 123.8 131.0 138.3 146.6 153.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
24
Preparing for installation
Model mane of combination
AM440MX
VGNR2ET
AM460MX
VGNR2ET
AM480MX
VGNR2ET
AM500MX
VGNR2ET
AM520MX
VGNR2ET
AM540MX
VGNR2ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGR/EU 111 11
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET 1
AM160JXVHGR/ET
AM180JXVHGR/ET 2 1 2 1
AM200JXVHGR/ET 1 2 1
AM220JXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET 1 1
Rated capacity Cooling (kW)
123.2 128.8 134.4 140.8 145.6 151.2
Heating (kW)
138.6 144.9 151.2 158.4 163.8 170.1
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
61.6 64.4 67.2 70.4 72.8 75.6
Maximum (kW)
160.2 167.4 174.7 183.0 189.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM560MX
VGNR2ET
AM580MX
VGNR2ET
AM600MX
VGNR2ET
AM620MX
VGNR2ET
AM640MX
VGNR2ET
AM660MX
VGNR2ET
Number of individual outdoor units
3 3 3 4 4 4
Combined
outdoor unit
AM080JXVHGR/EU 1 1 1
AM100JXVHGR/EU
AM120JXVHGR/EU 1 1
AM140JXVHGR/ET
AM160JXVHGR/ET
AM180JXVHGR/ET 1 2 3 2 3
AM200JXVHGR/ET 1
AM220JXVHGR/ET
AM240MXVGNR/ET 1 1
AM260MXVGNR/ET 1 1
Rated capacity Cooling (kW)
156.8 162.4 168 173.6 179.2 184.8
Heating (kW)
176.4 182.7 189 195.3 201.6 207.9
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.2 84 86.8 89.6 92.4
Maximum (kW)
203.8 211.1 218.4 225.7 233.0 240.2
Maximum number of connectable
indoor units
64 64 64 64 64 64
25
ENGLISH
Model mane of combination
AM680MX
VGNR2ET
AM700MX
VGNR2ET
AM720MX
VGNR2ET
AM740MX
VGNR2ET
AM760MX
VGNR2ET
AM780MX
VGNR2ET
Number of individual outdoor units
4 4 4 4 4 4
Combined
outdoor unit
AM080JXVHGR/EU 1
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET 1
AM160JXVHGR/ET
AM180JXVHGR/ET 3 2 4 3 2 1
AM200JXVHGR/ET 1 2 3
AM220JXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET 1
Rated capacity Cooling (kW)
191.2 196 201.6 207.2 212.8 218.4
Heating (kW)
215.1 220.5 226.8 233.1 239.4 245.7
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
95.6 98 100.8 103.6 106.4 109.2
Maximum (kW)
248.6 254.8 262.1 269.4 276.6 283.9
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model mane of combination
AM800MX
VGNR2ET
AM820MX
VGNR2ET
AM840MX
VGNR2ET
AM860MX
VGNR2ET
AM880MX
VGNR2ET
AM900MX
VGNR2ET
Number of individual outdoor units
4 4 4 4 4 4
Combined
outdoor unit
AM080JXVHGR/EU
AM100JXVHGR/EU
AM120JXVHGR/EU
AM140JXVHGR/ET
AM160JXVHGR/ET
AM180JXVHGR/ET 3 2 1 1 1 1
AM200JXVHGR/ET 1 2 1 1 1
AM220JXVHGR/ET 1
AM240MXVGNR/ET 1
AM260MXVGNR/ET 111112
Rated capacity Cooling (kW)
224 229.6 235.2 240.8 246.4 252
Heating (kW)
252 258.3 264.6 270.9 277.2 283.5
Total capacity of
the connected
indoor units
(Cooling)
Minimum (kW)
112 114.8 117.6 120.4 123.2 126
Maximum (kW)
291.2 298.5 305.8 313.0 320.3 327.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
26
Preparing for installation
Moving the outdoor unit
Select the moving path in advance.
Be sure that moving path can support weight of the outdoor unit.
Uͱͱϩϑ̷ɇ͝ϩϩ˵ʪΧθͱʒЇʀϩͱθʪϩ˵ɇ͝и˵ʪ͝ʀɇθθц̈͝˝ϩUͱͱϩɇцϩ˵ʪΧθͱʒЇʀϩʒͱи͝ϑ̈ʒʪиɇцϑ
Surface of the heat exchanger is sharp. Be careful not to get injured while moving the product.
You must use certain part of the product when moving the product.
CAUTION
When moving with a crane
ɇϑϩʪ͝ϩ˵ʪӥθʪθͱΧʪɇϑϑ˵ͱи͝ϩ˵ʪѣ˝Їθʪ
To protect damage or scratches, insert a piece of cloth between
the outdoor unit and the wire rope.
Wire rope
Holes for wire
rope to go through
When moving with a forklift
Carefully insert the forklift forks into the forklift holes at the
bottom of the outdoor unit.
Be careful with the forklift from damaging the product.
Forklift
Forklift holes
Holes for forklift
forks to go
through
When moving the product without wooden pallet and the crane is not available for use
Connect a wire rope to the outdoor unit as you would move it
with a crane.
Hang the wire rope to the forklift fork to move the outdoor unit.
Wire rope
Forklift
27
ENGLISH
Selecting installation location
Decide the installation location, with the consideration of the following conditions, under users approval.
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in
residential areas, keep the operation hours in mind.)
Place where structure can bear the weight and vibration of the outdoor unit.
ť̷ɇʀʪӥϩ˵ѤɇϩϑЇθ˙ɇʀʪи˵ʪθʪθɇ̈͝иɇϩʪθʒͱʪϑͱϩϑʪϩϩ̷ʪͱθʪɇ̧
Place where it is not exposed to strong wind.
Ǯʪ̷̷Эʪ͝ϩ̷̈ɇϩʪʒΧ̷ɇʀʪӥϩ˵ϑЇ˙ѣʀ̈ʪ͝ϩϑʪθӬʀʪΧ̷ɇʀʪ˙ͱθθʪΧɇ̈θϑɇ͝ʒɇ̈͝ϩʪ͝ɇ͝ʀʪÜϑʀ˵ɇθ˝ʪʒЇʀϩʀɇ͝ɵʪ
purchased separately)
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable
distance.
ť̷ɇʀʪи˵ʪθʪϩɇ̷̷ͱиϑʪɇϑциɇϩʪθΧθͱͱѣ͝˝ɇ͝ʒʒθɇ̈̈͝͝˝иͱθ̧˙ͱθϩ˵ʪʀͱ͝ʒʪ͝ϑɇϩ̈ͱ͝иɇϩʪθ˝ʪ͝ʪθɇϩʪʒ˙θϩ˵ʪ
outdoor unit during heating operation.
ť̷ɇʀʪи˵ʪθʪϩ˵ʪθʪϑͱθ̈ϑ̧ͱ˙Ѥɇɵ̷ʪ˝ɇϑʪɇ̧ɇ˝ʪ
ť̷ɇʀʪи˵ʪθʪϩ˵ʪθʪϑͱʒ̈θʪʀϩѤЇʪ͝ʀʪͱ˙ϑ͝ͱиͱθθɇ̈͝
28
Selecting installation location
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore.
1. Do not install the product in a place where it is directly exposed to sea water and sea breeze.
 Make sure to install the product behind a structure (such as building) that can block see breeze.
 Even when it is inevitable to install the product in seashore, make sure that product is not directly
exposed to sea breeze by installing a protection wall.
2. Aͱ͝ϑ̈ʒʪθϩ˵ɇϩϩ˵ʪϑɇ̷̈̈͝ϩцΧɇθϩ̈ʀ̷ʪϑʀ̷̈͝˝̈͝˝ϩͱϩ˵ʪʪуϩʪθ͝ɇ̷Χɇ͝ʪ̷ϑϑ˵ͱЇ̷ʒɵʪϑЇ˙ѣʀ̈ʪ͝ϩ̷циɇϑ˵ʪʒͱЇϩ
3. 9ʪʀɇЇϑʪϩ˵ʪθʪϑ̈ʒЇɇ̷иɇϩʪθɇϩϩ˵ʪɵͱϩϩͱ˙ϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩϑ̈˝̈͝ѣʀɇ͝ϩ̷цΧθͱϩʪϑʀͱθθͱϑ̈ͱ͝
make sure that the slope does not disturb drainage.
 çʪʪΧϩ˵ʪѤͱͱθʪЭʪ̷ϑͱϩ˵ɇϩθɇ̈͝ʒͱʪϑͱϩɇʀʀЇЇ̷ɇϩʪ
 Be careful not to block the drain hole due to foreign substance
4. When product is installed in seashore, periodically clean it with water to remove attached salinity.
5. Make sure to install the product in a place that provides smooth water drainage. Especially, ensure that the
base part has good drainage.
6. If the product is damaged during the installation or maintenance, make sure to repair it.
7. Check the condition of the product periodically.
 Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied
by SAMSUNG (Code : MOK-220SA) or commercial water repellent grease and wax, etc., based on the
product condition.
 When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate
measures like covering the product.
8. If the product installed within 500m of seashore, special anti-corrosion treatment is required.
ť̷ʪɇϑʪʀͱ͝ϩɇʀϩцͱЇθͱʀɇ̷ƊđƊƸĘθʪΧθʪϑʪ͝ϩɇϩ̈Эʪ˙ͱθ˙Їθϩ˵ʪθʒʪϩɇ̷̈ϑ
Sea
Sea
Sea breeze
Sea breeze
Outdoor
unit
Outdoor
unit
Outdoor
unit
Protection wall should be constructed with a solid
material that can block the sea breeze and the height and
width of the wall should be 1.5 times larger than the size
of the outdoor unit. (You must secure more than 700mm
of space between the protection wall and the outdoor unit
for air circulation.)
Sea
Sea breeze
Outdoor
unit
Outdoor unit
Protection wall
29
ENGLISH
Space requirement for installation
System air conditioner may cause static noise when listening to AM stations. Therefore, select
an installation location for indoor unit where electrical wiring can be done while keeping certain
distance from a radio, computer and stereo equipment.
 Especially, keep the unit at least 3m away from the electrical equipment in an area with weak
electromagnetic waves and put the main power cable and communication cables in a separately
installed protection tube.
 Make sure that there is no equipment that generates electromagnetic waves. If not
electromagnetic waves may cause problem to the control systems which may lead to air
conditioner malfunction. (Example: Remote control sensor of the indoor unit may not receive
the signal very well, due to ballast stabilizer of the lighting equipment.)
In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns
of direct snowfall on the outdoor unit. Also, build higher base support so that accumulated snow
does not block the air inlet or the heat exchanger.
ŵθʪ˙θ̈˝ʪθɇ͝ϩϑɇϑɇ˙ʪͱ͝ϩͱӱʀɇ͝ʒͱ͝Ѥɇɵ̷ʪθʪ˙θ̈˝ʪθɇ͝ϩ²ͱиʪЭʪθ˙ϩ˵ʪΧ̷ɇʀʪͱ̷ʒϑ
any concerns for exceeding dangerous level of refrigerant concentration in case of refrigerant
leakage, extra ventilation system is required.
When you install the outdoor unit in high places such as roof, install fence or guardrail around it.
When there is no fence or guardrail, service person could fall.
Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and
sulfurous gas are produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex,
cattle shed, sulfuric hot spring, nuclear power plant, ship etc.) When installing the product in
those places, contact an installation specialty store as the copper pipe and brazing part will need
additional corrosion proof or anti-rust additive to prevent corrosion.
đɇ̧ʪϑЇθʪϩͱʪʪΧɇ͝цѤɇɵ̷ʪɇϩʪθ̈ɇ̷ϑϑЇʀ˵ɇϑиͱͱʒʪ͝ɇϩʪθ̈ɇ̷ϑͱ̷̈ʪϩʀɇθͱЇ͝ʒϩ˵ʪ
ͱЇϩʒͱͱθЇ̈͝ϩǮ˵ʪ͝ϩ˵ʪθʪϑѣθʪϩ˵ͱϑʪѤɇɵ̷ʪɇϩʪθ̈ɇ̷ӥ̷̷ʪɇϑ̷̈цʀɇϩʀ˵ϩ˵ʪѣθʪɇ͝ʒɇцΧɇϑϑ
it on to the product.
Depending on the condition of power supply, unstable power or voltage any cause malfunction of
the parts or control system. (At the ship or places using power supply from electric generator...etc)
Make sure to install MCU when using HR products.
When you select the location to install MCU, the location is far away from indoor rooms because
the refrigerant running of MCU may create noise.
CAUTION
Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of
Aøɇθ˝ʪθϑΧɇʀʪϑθʪαЇ̈θʪʒ˙ϩ˵ʪͱЇϩʒͱͱθϩΧʪθɇϩЇθʪϑ˝ʪθϩ˵ɇ͝Aͱθ˙ϩ˵ʪΧ̷ɇʀʪϑʪɇϩ
easily by quantity of solar radiation.
When you secure installation space, consider path for people and the direction of the wind.
Secure installation space as shown in the below illustration, considering ventilation and the service space.
If the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product.
If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space
̈˙ϩ˵ʪθʪϑɇ͝циɇ̷̷ϑɇθͱЇ͝ʒϩ˵ʪΧθͱʒЇʀϩϩ˵ɇϩɇцʒ̈ϑϩЇθɵϩ˵ʪɇ̈θѤͱиÃ˙ʪ͝ͱЇ˝˵Эʪ͝ϩ̷̈ɇϩ̈ͱ͝ϑΧɇʀʪϑͱϩ
secured, product may malfunction.
You may install the outdoor units with 20mm of space between the product, but products performance
may decrease depending on the installation environment.
30
Space requirement for installation
Single installation
(Unit : mm)
Height of the wall is
unlimited
Over 100 (S2)Over 500 (S1)
Over 100 Over 100
Front
side Over 100
Over 300
<Case 1> <Case 2>
Front side
Module installation (Unit : mm)
<Case 3>
Over 500Over 500 Over 600
Over 100 Over 100 Over 100
Over 100
Over 100 Over 100 Over 100 Over 100
Front side
Front side
<Case 1> <Case 2>
Over 200
Over 100
Over 300
(S2)
Over 500
(S1)
Over 100
Over 100
Over 100
Over 300
Over
400
Over
400
Height of
the wall is
unlimited
Front
side
Front side
For <Case 1> or <Case 3>
Height of the wall on the front side should not
be higher than 1500mm.
Height of the wall on the air inlet side should not
be higher than 500mm.
Height of the wall on the side is not limited.
If the height of the wall exceeds by certain value
(h1, h2), additional clearance [(h1)/2, (h2)/2 : Half
of the exceeded distance] should be added to
the service space (S1, S2).
1500 h1
500 h2
Front side
Air inlet side
(Unit : mm)
S1+h1/2 S2+h2/2
31
ENGLISH
Accessories
Accessories
ǽͱЇЇϑϩʪʪΧ˙ͱ̷̷ͱӥ͝˝ɇʀʀʪϑϑͱθ̈ʪϑЇ͝ϩ̷̈ϩ˵ʪϑϩɇ̷̷ɇϩ̈ͱ͝ϑѣ̈͝ϑ˵ʪʒ
²ɇ͝ʒͱЭʪθϩ˵ʪϑϩɇ̷̷ɇϩ̈ͱ͝ɇ͝Їɇ̷ϩͱϩ˵ʪʀЇϑϩʪθɇ˙ϩʪθѣ̈͝ϑ˵̈͝˝ϩ˵ʪϑϩɇ̷̷ɇϩ̈ͱ͝
Installation manual (1)
Optional accessories
Following optional accessories are needed for connecting pipes between the indoor and outdoor units.
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ ƊΧʪʀ̈ѣʀɇϩ̈ͱ͝Model Name
ǽâͱ̈͝ϩ
đǹâǽ߫đ 15.0 kW and below
đǹâǽđߣǮߢǮ
đǹâǽđߣǮߢǮ
đǹâǽđߣǮߥǮ
đǹâǽ߫đ ߦǮ߫ߦǮ
đǹâǽ߫đ߫ߧǮߤǮ
đǹâǽđ Over 135.2 kW
ǽâͱ̈͝ϩĮ̷͝ц²ŵ
đǹâǽđ 22.4 kW and below
đǹâǽđߧǮߥǮ
đǹâǽđ ߦǮߤǮ
đǹâǽđ Over 135.2 kW
Distribution header
đǹâ²đ 45.0 kW and below (for 4 rooms)
đǹâ²đ 70.3 kW and below (for 8 rooms)
đǹâ²߫đ ߦǮߤǮ˙ͱθθͱϑ
ǽâͱ̈͝ϩ
- Outdoor unit
đǹâƟ߫đ 135.2 kW and below
đǹâƟđ Over 135.2 kW
ǽâͱ̈͝ϩĮ̷͝ц²ŵ
- Outdoor unit
đǹâƟđ 135.2 kW and below
đǹâƟđ Over 135.2 kW
If you use an indoor unit with no internal EEV(Electric Expansion Valve), you will need an EEV kit.
Only use the genuine accessories listed in above table and do not use imitated accessories.
32
Base construction and installation of the outdoor unit
Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove
ϩ˵ʪиͱͱʒʪ͝Χɇ̷̷ʪϩϩ˵ʪθʪϑθ̈ϑ̧ͱ˙ѣθʪʒЇθ̈͝˝иʪ̷ʒ̈͝˝ϩ˵ʪΧ̈ΧʪϑÃ˙ϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩϑϑϩɇ̷̷ʪʒ
with wooden pallet on, and it was used for long period time, wooden palette may break and cause
electrical hazard or high pressure may damage the pipes.
WARNING
уɇ͝ͱЇϩʒͱͱθЇ̈͝ϩѣθцͱ͝ϩ˵ʪɵɇϑʪ˝θͱЇ͝ʒӥϩ˵ɇ͝ʀ˵ͱθɵͱ̷ϩϑ
Manufacturer is not responsible for the damage occurred by not following the installation standards.
1. Make sure that the height of the base ground is 200mm or higher to protect the outdoor unit from rain
water or other external conditions. Also, install a draining pit around the base ground and connect the
drain pipe to the drainage.
2. Considering the vibration and weight of the outdoor unit, strength of the base ground must be strong to
ΧθʪЭʪ͝ϩͱ̈ϑʪɇ͝ʒϩ˵ʪϩͱΧϑЇθ˙ɇʀʪͱ˙ϩϑ˵ͱЇ̷ʒɵʪѤɇϩ
3. Base ground should be 1.5 times larger than the bottom of the outdoor unit.
4. ĮЇϩʒͱͱθЇ̈͝ϩЇϑϩɵʪѣуʪʒѣθцϑͱϩ˵ɇϩϩʀɇ͝ӥϩ˵ϑϩɇ͝ʒϩ˵ʪӥ͝ʒϑΧʪʪʒͱ˙ϑÃ˙цͱЇʀɇ͝͝ͱϩѣуϩ˵ʪ
ͱЇϩʒͱͱθЇ̈͝ϩͱ͝ϩ˵ʪɵɇϑʪ˝θͱЇ͝ʒѣуϩɵцϑ̈ʒʪͱθЇϑʪʪуϩθɇϑϩθЇʀϩЇθʪ
5. Ã͝ʪɇϩ̈͝˝ͱΧʪθɇϩ̈ͱ͝ʒʪ˙θͱϑϩиɇϩʪθɇц˙ͱθϑͱцͱЇЇϑϩθʪɇ̷̷цʀɇθʪɇɵͱЇϩϩ˵ʪʒθɇ̈͝ɇ˝ʪɇ͝ʒиɇϩʪθΧθͱͱѣ͝˝
ϩ˵ʪѤͱͱθƟͱΧθʪЭʪ͝ϩʒʪ˙θͱϑϩиɇϩʪθ˙θϑϩɇ˝͝ɇϩ̈͝˝ͱθ˙θʪʪї͝˝ʀͱ͝ϑϩθЇʀϩɇʒθɇ̈͝ɇ˝ʪӥϩ˵ͱЭʪθϑ̷ͱΧʪ
Ãʀʪɇц˙ͱθͱ͝ϩ˵ʪѤͱͱθӥ͝ϩʪθϑʪɇϑͱ͝
6. It is necessary to add wire mesh or steel bar during concrete construction for the base ground to prevent
damages or cracks.
7. When installing multiple outdoor units at the same place, construct an H beam or an anti-vibration frame
on the base ground to install the outdoor unit.
8. After installing an H beam or an anti-vibration frame, apply corrosion protection and other necessary
coating.
9. When concrete construction for outdoor unit installation is completed, install an anti-vibration pad
(t=20mm or more) or an anti-vibration frame to prevent vibration of the outdoor unit from transferring to
the base ground.
10. ť̷ɇʀʪϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩͱ͝ɇ͝²ɵʪͱθɇ͝ɇ͝ϩ̈Ӭɵθɇϩ̈ͱ͝˙θʪɇ͝ʒѣуϩӥϩ˵ϩ˵ʪɵͱ̷ϩЇϩɇ͝ʒиɇϑ˵ʪθ
(The bearing force has to be over 3.5kN)
Base ground construction
<When installing on the ground>
Draining pit Over 200 mm
<When installing on the roof>
Bottom surface of the base
ground must be horizontally
leveled Over 200 mm
Over 200 mm
33
ENGLISH
Outdoor unit installation
Over 200 mm
Over 50 mm
Base ground
H beam or anti-
vibration frame
Over 200 mm
Outdoor unit base mount and anchor bolt position
(Unit : mm)
A
B
54
761
803
54
Outdoor unit - Anti-vibration
frame (4-Ø 12)
Anti-vibration - Base ground
(4-Ø 18)
(Unit : mm)
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ DVM S Small Type DVM S Large A Type DVM S Large B type
A 880 1,295 1,295
B 740 1,150 1,150
Refer to the blueprints in technical data book to make a holes for connecting the anti-vibration pad.
34
Base construction and installation of the outdoor unit
Examples of draining work
 Aͱ͝ϑϩθЇʀϩϩ˵ʪʒθɇ̈͝ɇ˝ʪʒ̈ϩʀ˵ӥϩ˵θʪ̈͝˙ͱθʀʪʒʀͱ͝ʀθʪϩʪϑɇ͝ʒɇ̧ʪϑЇθʪϩ˵ɇϩиɇϩʪθΧθͱͱѣ͝˝иͱθ̧ϑʒͱ͝ʪ
For smooth draining of defrost water, make sure to apply 1/50 slope.
Construct a drainage around the outdoor unit to prevent the defrost water (from the outdoor unit) from
ϑϩɇ˝͝ɇϩ̈͝˝ͱЭʪθѤͱӥ͝˝ͱθ˙θʪʪї͝˝ʪɇθϩ˵ʪϑϩɇ̷̷ɇϩ̈ͱ͝ϑΧɇʀʪ
When the outdoor unit is installed on the roof, check the strength and waterproof status of the roof.
(Unit : mm)
960
760100
80
80
80
100
XX’
Direction of the
drainage (Slope 1/50)
<Drainage work for single installation>
B
A
50
100
150 100
<X-X’ SECTION>
80
80
80
80
80
80
80
80
200
B B
200
Direction of the drainage
(Slope 1/50)
<Drainage work for module installation>
(Unit : mm)
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝DVM S Small Type DVM S Large A Type DVM S Large B type
A940 1,350 1,350
B740 1,150 1,150
35
ENGLISH
Cautions regarding on connecting the anchor bolt
Tighten the rubber washer to prevent the bolt connection part of the outdoor unit from corroding.
Rubber washer
ʀ˵ͱθϑΧʪʀ̈ѣʀɇϩ̈ͱ͝
Size Diameter of
drill bit (a)
Anchor
length (b)
Sleeve
length (c)
Insert
depth
Fastening
torque
B
C
D
N
Ø 10 14 mm 75 mm 40 mm 50 mm 30 N·m
Use the anchor bolts and nuts that is zinc plated or made of STS material.
Regular anchor bolts or nuts may get damaged by corrosion.
Cautions regarding on connecting the pipe
If you install the outdoor unit on the rooftop, check the strength and make sure to waterproof the
rooftop.
Construct draining pit around the base construction and pay attention to the drainage around the
outdoor unit. (Condensation or defrost water may form during outdoor unit operation.)
If there's any possibility of small animals from entering the pipe outlet, block the outlet as shown
in the illustration.
Liquid side pipe
Gas side pipe
Block the part. (When withdrawing the pipe
from the front side)
Cautions regarding on anti-vibration frame installation
During installation, make sure there is no gap between the base ground and the supporting
structures such as anti-vibration frame or H beam.
Base ground must be constructed strongly to support the bottom part of the anti-vibration
mount.
˙ϩʪθϑϩɇ̷̷̈͝˝ϩ˵ʪɇ͝ϩ̈Ӭɵθɇϩ̈ͱ͝˙θʪЇ͝ϩ̈˝˵ϩʪ͝ϩ˵ʪѣӱ͝˝Χɇθϩͱ͝ϩ˵ʪϩͱΧɇ͝ʒɵͱϩϩΧɇθϩͱ˙
the frame.
CAUTION
37
ENGLISH
Installing the wind/snow prevention duct
Cautions regarding on installing the frame and selecting the base ground
Height (h) of the frame and the base ground should be higher than the "heaviest expected
snowfall".
Area of the frame and the base ground should not be larger than the are of the outdoor unit. Snow
may accumulate if the area of the frame or the base ground is larger.
CAUTION
Should adopt bar type louver. Don’t use a type of rain resistance louver.
[Bar type louver] [Rain resistance louver]
øͱЇЭʪθϑΧʪʀ̈ѣʀɇϩ̈ͱ͝ϑ
 ˝̷ʪʀθ̈ϩʪθ̈ɇʪϑϑϩ˵ɇ͝
 Opening ratio criteria : greater than 80%
WARNING
38
Installing the wind/snow prevention duct
Installing the outdoor unit in windy region
In windy regions such as near sea shores, protection wall or wind protection duct must be installed for
normal operation of the outdoor unit. (Refer to the illustration of the snow prevention duct, for installing
the wind protection duct.)
Install the wind prevention duct with the consideration of major wind direction. If the direction of the
discharge part is same as major direction of the wind, it could cause products performance decrease.
CAUTION
Cautions regarding on installing the frame and selecting the base ground
Ɵ˵ʪɵɇϑʪ˝θͱЇ͝ʒЇϑϩɵʪϑͱ̷̈ʒɇ͝ʒϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩЇϑϩɵʪѣуʪʒӥϩ˵ɇ͝ʀ˵ͱθɵͱ̷ϩϑ
Make sure to install outdoor unit in a place strong enough to withstand its weight. If the place
cannot withstand the weight of the outdoor unit, outdoor unit may fall and cause personal injury.
When installing on a rooftop subject to strong wind, countermeasures must be taken to prevent
the unit from falling down.
Use a frame that is resistant to corrosion.
DVM S Large B Type
DVM S Small Type
(Unit : mm)
DVM S Large A Type
782
560 880 560 871
765
2300
668
532
2271
1134
965
180
1632
1150
980
180
2000
127 593
1318
1210
612 108
550
1197
2415
560 5601295
593127
1318
1210
612108
2300
1632
1150
980
180
871
765
668
532
2271
1134
965
180
550
406
2415
550
180
1080
640
1252
1315
552
1192
560 560 8711295
1255
1732
1080
1255 2371
2400
668
532
180
550 550765
39
ENGLISH
Refrigerant pipe installation
When installing, make sure there is no leakage. When collecting the refrigerant, stop the
ʀΧθʪϑϑͱθѣθϑϩɵʪ˙ͱθʪθͱӬ͝˝ϩ˵ʪʀͱ͝͝ʪʀϩ̈ͱ͝Χ̈ΧʪÃ˙ϩ˵ʪθʪ˙θ̈˝ʪθɇ͝ϩΧ̈ΧʪϑͱϩΧθͱΧʪθ̷ц
connected and the compressor works with the service valve open, the pipe inhales the air and it
makes the pressure inside of the refrigerant cycle abnormally high which may lead to explosion
and injury.
WARNING
Refrigerant pipe work
The length of refrigerant pipe should be as short as possible and the height difference between an indoor
and outdoor unit should be minimized.
Piping work must be done within allowable piping length, height difference, and the allowable length after
branching.
Ɵ˵ʪΧθʪϑϑЇθʪͱ˙ϩ˵ʪŵϑ˝Ƹϑʪͱ̷͝цʀʪθϩ̈ѣʪʒθʪ˙θ̈˝ʪθɇ͝ϩΧ̈Χʪɇ͝ʒ˙ͱ̷̷ͱиϩ˵ʪϑϩɇ̷̷ɇϩ̈ͱ͝ʪϩ˵ͱʒ
After installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed.
When you need to charge the additional refrigerant, make sure to use R-410A refrigerant.
Use clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture
inside pipe.
Ƹϑʪϩͱͱ̷ϑɇ͝ʒɇʀʀʪϑϑͱθ̈ʪϑϩ˵ɇϩѣϩͱ͝ŵͱ̷͝ц
Tool Installation process/purpose Compatibility with conventional tool
Pipe cutter
Refrigerant pipe
installation
Pipe cutting Compatible
Flaring tool ť̈ΧʪѤɇθ̈͝˝
Refrigerant
machine oil
Apply
refrigerant oil
ͱ͝ѤɇθʪʒΧɇθϩ
Exclusive ether oil, ester oil, alkali benzene oil or synthetic
oil
Torque wrench Aͱ͝͝ʪʀϩѤɇθʪ
nut with pipe
Compatible
Pipe bender Pipe bending
Nitrogen gas Air tightness
test
Prevent
oxidation within
the pipe
Welder Pipe welding
Manifold gage Air tightness
ϩʪϑϩɇʒʒ̈ϩ̈ͱ͝ɇ̷
refrigerant
charging
Vacuuming,
charging
refrigerant
and checking
operation
Need exclusive one to prevent mixture of R-22 refrigerant
oil use and also the measurement is not available due to
high pressure
Refrigerant
charging hose
Need exclusive one since there is risk of refrigerant leakage
ͱθѤͱиͱ˙ΧЇθ̈ϩ̈ʪϑ
Vacuum pump Pipe drying
Compatible (Use products which contain the check valve to
ΧθʪЭʪ͝ϩϩ˵ʪͱ̷̈˙θѤͱӥ͝˝ɵɇʀ̧иɇθʒϩͱϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩ
Use the one that can be vacuumed up to -100.7kpa(5Torr).
Scale for
refrigerant
charging
Refrigerant charging Compatible
Gas leak
detector Gas leak test Need exclusive one
(Ones used for R-134a is compatible)
Flare nut đЇϑϩЇϑʪϩ˵ʪѤɇθʪЇϩʪαЇ̈ΧΧʪʒӥϩ˵ϩ˵ʪΧθͱʒЇʀϩŵʪ˙θ̈˝ʪθɇ͝ϩʪɇ̧ɇ˝ʪɇцͱʀʀЇθи˵ʪ͝ϩ˵ʪ
ʀͱ͝Эʪ͝ϩ̈ͱ͝ɇ̷ѤɇθʪЇϩ˙ͱθŵϑЇϑʪʒ
40
Refrigerant pipe installation
Selecting refrigerant pipe
First branch joint
Increase the main
pipe size
Install the refrigerant pipe according to main pipe size of each outdoor unit capacity.
When the pipe length (including elbow) between an outdoor unit and the farthest indoor unit exceeds 90m,
you must increase the size of the pipe (main pipe) by one grade which connects between the outdoor unit
ϩͱϩ˵ʪѣθϑϩɵθɇ͝ʀ˵ͱ̈͝ϩ
For H/R model, When the pipe length (including elbow) between an outdoor unit and the farthest indoor
unit exceeds 90m, you must increase the size of the liquid pipe by one grade among the pipes(main pipe)
и˵̈ʀ˵ʀͱ͝͝ʪʀϩϑɵʪϩиʪʪ͝ϩ˵ʪͱЇϩʒͱͱθЇ̈͝ϩϩͱϩ˵ʪѣθϑϩɵθɇ͝ʀ˵ͱ̈͝ϩ
41
ENGLISH
H/P
Ǯ ߢǮ
(D)
(E)(C)
(A)
(B)
(3)(2)(1)
ǮkуߤǮ
Capacity (kW) ĘͱPipe size (mm)
Liquid pipe Gas pipe
Ǯ(1) Ø 12.70 Ø 28.58
Ǯ(2) Ø 19.05 Ø 34.92
ߤǮ(3) Ø 19.05 Ø 41.28
Size of the pipe connected to the outdoor unit (A)
Select the size of the main pipe according to the below table.
Outdoor unit capacity (kW)
(Cooling)
*Maximum pipe length within 90m *Maximum pipe length over 90m
Liquid pipe (mm) gas pipe (mm) Liquid pipe (mm) gas pipe (mm)
22.4 kW Ø 9.52 Ø 19.05 Ø 12.70 Ø 22.22
ߧǮߣǮØ 22.22 Ø 25.40
note1)
ߤǮǮ
Ø 12.70
Ø 28.58
Ø 15.88 Ø 28.58
ǮߢǮ
ߣǮߢǮ
Ø 31.75
note2)
ߣǮߦǮ
Ø 15.88 Ø 19.05
ߧǮߢǮ
ߣǮߥǮ
ߦǮߥǮØ 34.92 Ø 38.10
note3)
ߦǮ߫ߦǮ
Ø 19.05 Ø 22.22߫ߧǮߤǮØ 41.28 Ø 41.28
ߥǮߢǮØ 53.98
ߣǮߢǮØ 22.22 Ø 53.98 Ø 25.40
note1)
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe
installed on the site, a socket is provided by default together with the outdoor unit.
42
Refrigerant pipe installation
Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to
the outdoor unit (A), apply the pipe size (A).
Indoor unit capacity (kW) Branch pipe length within 45m Branch pipe length between 45~90m
Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm)
ߢǮɇ͝ʒɵʪ̷ͱи
Ø 9.52
Ø 15.88
Ø 12.70
Ø 19.05
ߣǮߦǮØ 19.05 Ø 22.22
ߧǮߣǮØ 22.22 Ø 25.40
note1)
ߤǮߢǮØ 12.70 Ø 28.58 Ø 15.88 Ø 28.58
ߣǮߢǮØ 31.75
note2)
ߣǮߥǮØ 15.88 Ø 19.05
ߦǮߥǮØ 34.92 Ø 38.10
note3)
ߦǮ߫ߦǮ
Ø 19.05 Ø 22.22߫ߧǮߤǮØ 41.28 Ø 41.28
ߥǮ߫◌ߢǮØ 53.98
ĮЭʪθߢǮØ 22.22 Ø 53.98 Ø 25.40
note1)
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
Indoor unit capacity (kW) ť̈Χʪϑ̈іʪĮU
Liquid pipe Gas pipe
ߢǮɇ͝ʒɵʪ̷ͱи Ø 6.35 Ø 12.70
ߣǮߢǮØ 9.52 Ø 15.88
ߣǮߢǮØ 9.52 Ø 19.05
ĮЭʪθߢǮØ 9.52 Ø 22.22
43
ENGLISH
Ǯ ߢǮ
(D)
(E)(C)
(A)
(B)
(3)(2)(1)
ǮBranch joint
Branch joint between outdoor units (C)
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ ƊΧʪʀ̈ѣʀɇϩ̈ͱ͝ǮModel name
Y-joint for outdoor unit (C) đǹâƟ߫đߤǮɇ͝ʒɵʪ̷ͱи
đǹâƟđ Over 135.2 kW
First branch joint (D)
Make a selection according to outdoor unit capacity.
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ Outdoor unit capacity
(kW)
Model name of the
branch joint
Y-joint (D)
ߢǮɇ͝ʒɵʪ̷ͱи đǹâǽđ
ߣǮߢǮđǹâǽđ
ߣǮߤǮđǹâǽđ
ߥǮ߫ߧߤǮđǹâǽ߫đ
߫ߧߥǮߤǮđǹâǽ߫đ
Over 135.2 kW đǹâǽđ
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
However, if the size of the pipe between branch joints (E) is bigger than the size of the pipe connected to
the outdoor unit (D), apply the pipe size (D).
1) Y-joint
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ ƊΧʪʀ̈ѣʀɇϩ̈ͱ͝ǮModel name
Y-joint (E)
đǹâǽ߫đ ߢǮɇ͝ʒɵʪ̷ͱи
đǹâǽđ ߣǮߢǮ
đǹâǽđ ߣǮߢǮ
đǹâǽđ ߣǮߥǮ
đǹâǽ߫đ ߦǮ߫ߦǮ
đǹâǽ߫đ ߫ߧǮߤǮ
đǹâǽđ ĮЭʪθߤǮ
2) Distribution header
A̷ɇϑϑ̈ѣʀɇϩ̈ͱ͝ ƊΧʪʀ̈ѣʀɇϩ̈ͱ͝ǮModel name
Distribution header (E)
đǹâ²đ ߢǮɇ͝ʒɵʪ̷ͱи˙ͱθߦθͱϑ
đǹâ²đ ߥǮɇ͝ʒɵʪ̷ͱи˙ͱθθͱϑ
đǹâ²߫đ ߦǮߤǮ
44
Refrigerant pipe installation
H/R
(A)
(B)
Ǯ ߢǮ
(D)
(E)
(F)
(C)
(3)
(2)
(1)
Ǯ
kуߤǮ
Capacity (kW) Ęͱ
Pipe size (mm)
Liquid pipe Low pressure
gas pipe
High pressure
gas pipe
Ǯ(1) Ø 12.70 Ø 28.58 Ø 19.05
Ǯ(2) Ø 19.05 Ø 34.92 Ø 28.58
ߤǮ(3) Ø 19.05 Ø 41.28 Ø 34.92
Size of the pipe connected to the outdoor unit (A)
Select the size of the pipe according to the below table.
Outdoor unit capacity
(kW)
(Cooling)
*Maximum pipe length within 90m *Maximum pipe length over 90m
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
Liquid pipe
(mm)
Low pressure
gas pipe (mm)
High pressure
gas pipe (mm)
22.4 kW Ø 9.52 Ø 19.05 Ø 15.88 Ø 12.70 Ø 19.05 Ø 15.88
ߧǮߣǮØ 22.22 Ø 19.05 Ø 22.22 Ø 19.05
ߤǮǮ
Ø 12.70
Ø 28.58
Ø 15.88
Ø 28.58
ǮߢǮ
Ø 22.22 Ø 22.22ߣǮߦߧߢǮ
ߣǮߦǮ
Ø 15.88 Ø 19.05
ߧǮߢǮ
Ø 28.58 Ø 28.58
ߣǮߥǮ
ߦǮߥǮØ 34.92 Ø 34.92
ߦǮ߫ߦǮ
Ø 19.05 Ø 22.22߫ߧǮߤǮØ 41.28 Ø 34.92 Ø 41.28 Ø 34.92
ߥǮ߫◌ߢǮ
ߣǮߢǮØ 22.22 Ø 53.98 Ø 53.98 Ø 25.40
note1)
Ø 53.98 Ø 53.98
*Maximum pipe length : The pipe length between an outdoor unit and the farthest indoor unit.
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
For HR model, only increase the size of the liquid pipe If pipe length exceeds 90m
For the case that the diameter of the default pipe of an outdoor unit does not match that of the pipe
installed on the site, a socket is provided by default together with the outdoor unit.
48
Refrigerant pipe installation
Refrigerant pipe installation
Basic amount of refrigerant within the outdoor unit (kg)
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU AM140JXVHGH/ET AM160JXVHGH/ET AM180JXVHGH/ET
Basic amount
6.5 6.5 6.5 9.4 9.4 8.4
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM200JXVHGH/ET AM220JXVHGH/ET AM240KXVGGH/ET AM260KXVGGH/ET AM280KXVGGH/ET
Basic amount
11.0 11.0 14.0 14.0 14.0
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM080JXVAGH/EU AM100JXVAGH/EU AM120JXVAGH/EU AM140KXVAGH/ET AM160KXVAGH/ET AM180KXVAGH/ET
Basic amount
5.5 5.5 6.5 7.7 8.4 8.4
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM200KXVAGH/ET AM220KXVAGH/ET AM240KXVAGH/ET AM260KXVAGH/ET AM280KXVAGH/ET AM300KXVAGH/ET
Basic amount
8.4 8.4 14.0 14.0 14.0 14.0
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM100MXVDGH/ET AM120MXVDGH/ET AM140MXVDGH/ET AM160MXVDGH/ET AM180MXVDGH/ET
Basic amount
5.5 6.5 7.7 8.4 8.4
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM080JXVHGR/EU AM100JXVHGR/EU AM120JXVHGR/EU AM140JXVHGR/ET AM160JXVHGR/ET AM180JXVHGR/ET
Basic amount
6.5 6.5 6.5 9.4 9.4 8.4
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝
AM200JXVHGR/ET AM220JXVHGR/ET AM240MXVGNR/ET AM260MXVGNR/ET AM280MXVGNR/ET AM300MXVANR/ET
Basic amount
11.0 11.0 14.0 14.0 14.0 14.0
Amount of additional refrigerant depending on the pipe size ( )
Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe ŝߨ࢏ߥߧ ŝ߫࢏ߧߤ ŝߣߤ࢏ߩߢ ŝߣߧ࢏ߪߪ ŝ߫ߣ࢏ߢߧ ŝߤߤ࢏ߤߤ ŝߤߧ࢏ߦߢ ŝߤߪ࢏ߧߪ
Additional amount (kg/m) 0.02 0.06 0.125 0.18 0.27 0.35 0.53 0.65
For the indoor unit already connected to EEV kit, the additional refrigerant charging is 0.01kg per meter
regardless of the pipe size.
Amount of additional refrigerant for each indoor unit ( )
(Unit : kg)
Capacity (kW)
Model
ߣߧ ߣߩ ߤ࢏ߤ ߤߪ ߥߤ ߥ࢏ߨ 4ߦ࢏ߧ ߧ࢏ߨ 6ߩߣ ߪ࢏ߤ 9߫ߥ 11 ߣߣ࢏ߤ ߣߤ࢏ߪ 14 16 18 22 ߤߤ࢏ߦ 25 28 32 50 500
CMH
1000
CMH
Interior 1way cassette
(AM***HN1DEH/**)
(AM***NN1PEH/**)
0.15 0.15
Slim 1way cassette
đࡒࡒ࣑âࢩĘ࣒ĘߣUk²ࢩࡒࡒ0.25 0.25 0.25 0.32 0.32
2way cassette
(AM****N2DEH/**)
0.31 0.47
4way cassette S
(600x600)
(AM****NNDEH/**)
0.29 0.29 0.29 0.29 0.37 0.37 0.37
4way cassette S
(AM***F(N)N4DEH/**)
0.45 0.45 0.45 0.45 0.57 0.69 0.69
4way cassette S
(AM****N4FEH/**)
0.69 0.69 0.69 1.00 1.00 1.00 1.00 1.00 1.00
360 cassette
(AM***KN4DEH/**)
0.45 0.45 0.45 0.45 0.69 0.69 0.69
Duct S
(AM****NMPKH/**)
0.22 0.22 0.22 0.22 0.31 0.38 0.38 0.38
Duct S
(AM****NMPKH9**)
0.31 0.31 0.38 0.38 0.38
Duct S
(AM***HNHPKH/**)
0.38 0.38 0.38
Home Duct
(AM***KNLDEH/**)
0.13 0.13 0.13 0.17
Home Duct
(AM***MNLDEH/**)
0.24 0.24 0.31
49
ENGLISH
Capacity (kW)
Model
ߣߧ ߣߩ ߤ࢏ߤ ߤ࢏ߪ ߥ࢏ߤ ߥ࢏ߨ 4ߦ࢏ߧ ߧߨ 6ߩߣ ߪ࢏ߤ 9߫ߥ 11 ߣߣ࢏ߤ ߣߤ࢏ߪ 14 16 18 22 ߤߤ࢏ߦ 25 28 32 50 500
CMH
1000
CMH
Slim duct
(AM***FNLDEH/**)
0.17 0.17 0.17 0.26 0.35 0.35 0.45 0.42 0.42 0.62 0.62
Slim duct
(with drain pump)
(AM***KNLDEH/**)
0.35 0.35 0.45 0.42 0.42 0.62 0.62
Slim duct
(AM***FNLF(P)EH/**)
0.62 0.45 0.45 0.62 0.62 0.62
Slim duct
(AM***NNLFEH/**)
0.62 0.62
MSP duct
(AM****NMDEH***)
0.24 0.24 0.24 0.28 0.28 0.28 0.32 0.54 0.68 0.68 0.91
HSP duct
(AM****NHDEH/**)
0.68 0.68 0.68 1.18 1.18
HSP duct
(AM****NHF(P)EH/**)
1.18 1.18 1.18 1.18 1.18 1.18 1.18
Big duct
đࡒâĘ²࣑ťç²ࢩ
1.15 1.15
OAP duct
(AM****NEPEH/**)
0.68 1.18 1.18
Concealed Floor Standing
(AM****NFDEH/**)
0.22 0.32 0.32
Floor Standing
(AM****NPDKH/**)
0.69 1.85
Ceiling
(AM****NCDEH/**)
(AM****NCDKH/**)
0.39 0.39 0.56 0.95
Console
࣑đࡒࡒࡒࡒĘâUk²ࢩࡒࡒ
0.16 0.27 0.27 0.27 0.27
Wall mounted (Neo forte)
(AM***F(H)NTDEH/**)
0.24 0.24 0.24 0.24 0.36 0.36
Wall mounted
(Neo forte with EEV)
đࡒ
²ĘůUk²ࢩࡒ
0.34 0.34 0.34 0.34 0.51 0.51 0.51
Wall mounted
(AR5000)
(AM****NADKH/**)
0.16 0.16 0.19 0.25 0.25 0.52 0.52 0.52
Wall mounted
(AR5000 with EEV)
(AM****NVDE(K)H/**)
0.22 0.22 0.25 0.34 0.34 0.71 0.71 0.71
Wall mounted
(Boracay)
(AM***KNTDEH/**)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
Wall mounted
(Boracay with EEV)
࣑đࡒࡒࡒçĘůUk²ࢩࡒࡒ
0.24 0.24 0.32 0.32 0.49 0.49 0.49
Wall mounted (MAX4
with EEV)
࣑đࡒࡒࡒđĘůUk²ࢩࡒࡒ࣒
0.68
ERV plus
(AM****NKDEH/**)
0.11 0.36
Hydro Unit HE
(AM****NBDEH/**)
0.60 0.70 1.20
Hydro Unit HT
(AM****NBF*B/**)
0.60
Note1)
MCU (MCU-S*NE**N)
0.50
If AHU kit is included among the indoor units, you must add 0.063kg of refrigerant for every 1kW of the
AHU capacity increase.
Note1) In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please
don’t put the additional refrigerant.
51
ENGLISH
Example of refrigerant calculation for HR models
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Size of liquid pipe Length (m)
Unit amount
of refrigerant
(kg/m)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
× × )ॣ࣑
Liquid pipe ( )
Ø 6.35 15 0.02 0.3
11.965
Ø 9.52 112 0.06 6.72
Ø 12.70 25 0.125 3.125
Ø 15.88 10 0.18 1.8
Ø 6.35
࣑kkǤç
̈ϩड़
̈͝
ʒͱͱθЇ
̈͝
ϩ࣒
2 0.01 0.02
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Model name of
indoor unit
Number of units
Unit amount of
refrigerant (kg/EA)
Amount of
additional
refrigerant (kg)
Total amount
of additional
refrigerant (kg)
× × )ॣ࣑
Indoor unit ( )
4way cassette
࣑đߢߩߣĘߦUk²७࣒ 5 0.45 2.25
4.66
4way cassette
࣑đߣߣߤĘߦUk²७࣒ 2 0.57 1.14
Neo forte
࣑đߢߤߪĘƟUk²७࣒ 1 0.27 0.27
MCU 2 0.5 1
Total amount of refrigerant ( + ) = 11.965+4.66 = 16.625 (kg)
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter (mm) Minimum thickness (mm) Temper grade
Ø 6.35 0.70
Annealed
Ø 9.52 0.70
Ø 12.70 0.80
Ø 15.88 1.00
Ø 19.05 0.90
Drawn
Ø 22.22 0.90
Ø 25.40 1.00
Ø 28.58 1.10
Ø 31.75 1.10
Ø 34.92 1.20
Ø 38.10 1.35
Ø 41.28 1.43
Ø 44.45 1.60
Ø 50.80 2.00
Ø 53.98 2.10
52
Refrigerant pipe installation
࡛For pipes larger than Ø 19.05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be
used. If a annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure
resistance and cause personal injury.
CAUTION
Keeping refrigerant pipe
To prevent foreign materials or water from entering the pipe, storing method and sealing method (especially
during installation)is very important. Apply correct sealing method depending on the environment.
Exposure place Exposure time Sealing type
Outdoor Longer than one month Pipe pinch
Shorter than one month Taping
Indoor - Taping
Refrigerant pipe welding and safety information
Important information for refrigerant pipe work
࡛Make sure there is no moisture inside the pipe.
࡛Make sure there are no foreign substances and impurities in the pipe.
࡛Make sure there is no leakage.
࡛Make sure to follow the instruction when welding or storing the pipe.
CAUTION
Ę
̈ϩθͱ˝ʪ
͝
ѤЇϑ˵
̈͝
˝иʪ̷ʒ
̈͝
˝
ॷ Ǯ˵ʪ
͝
иʪ̷ ʒ
̈͝
˝ϩ˵ʪθʪ˙θ
̈˝ʪθɇ
͝
ϩΧ
̈ΧʪϑࡥѤЇϑ˵ϩ˵ʪ
͔
и
̈ϩ˵
̈͝
ϩθͱ˝ʪ
͝
˝ɇϑɇϑϑ˵ͱи
͝
̈͝
ϩ˵ʪΧ
̈ʀϩЇθʪ࢏
ॷ Ã˙цͱЇʒͱ
͝
ͱϩΧʪθ˙ͱθ
͔
̈͝
ϩθͱ˝ʪ
͝
ѤЇϑ˵
̈͝
˝и˵ʪ
͝
иʪ̷ ʒ
̈͝
˝ϩ˵ʪΧ
̈Χʪϑࡥͱу
̈ʒʪ
͔
ɇц˙ͱθ
͔
̈͝
ϑ
̈ʒʪϩ˵ʪΧ
̈Χʪ࢏Ãϩʀɇ
͝
cause the damage of the important parts such as compressor and valves etc.
ॷ ʒ
̟Їϑϩϩ˵ʪѤͱиθɇϩʪͱ˙ϩ˵ʪ
̈͝
ϩθͱ˝ʪ
͝
ѤЇϑ˵
̈͝
˝и
̈ϩ˵ɇΧθʪϑϑЇθʪθʪ˝Ї̷ ɇϩͱθϩͱ
͔
ɇ
̈͝
ϩɇ
̈͝
ߢ࢏ߢ͔ߧ 3/h or less.
Welding part
Nitrogen gas
Ø 6.35 copper pipe
Stop valve
Taping
High pressure hose
Pressure regulator
Nitrogen gas
Flowmeter
Direction of the pipe when welding
Direction of the pipe should be headed downward or in a sideways when welding.
Avoid welding the pipe with pipe direction heading upward.
࡛When you test gas leakage after welding the pipes, use a designated solution for gas leakage
detection. If you use the detection solution that includes sulfuric ingredient, it may cause corrosion
to the pipes.
CAUTION
53
ENGLISH
AЇϩϩ
̈͝
˝ͱθѤɇθ
̈͝
˝ϩ˵ʪΧ
̈Χʪϑ
1. Make sure that you prepared the required tools.
ॷ ť
̈ΧʪʀЇϩϩʪθࡥUʪɵЇθθ
̈͝
˝ϩͱͱ̷ ࡥѤɇθ
̈͝
˝ϩͱͱ̷ ɇ
͝
ʒΧ
̈Χʪ˵ͱ̷ ʒʪθࡥʪϩʀ࢏
2. Ã˙цͱЇиɇ
͝
ϩϩͱϑ˵ͱθϩʪ
͝
ϩ˵ʪΧ
̈ΧʪࡥʀЇϩ
̈ϩи
̈ϩ˵ɇΧ
̈ΧʪʀЇϩϩʪθʪ
͝
ϑЇθ
̈͝
˝ϩ˵ɇϩϩ˵ʪʀЇϩʪʒ˝ʪθʪ
͔
ɇ
̈͝
ϑɇϩ߫ߢঌи
̈ϩ˵ϩ˵ʪ
side of the pipe.
Refer to below illustrations for correct and incorrect examples of cut edges.
߫ߢঌ Oblique Rough Burr
3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a Deburring tool.
4. AɇθθцͱЇϩѤɇθ
̈͝
˝иͱθ
̧Їϑ
̈͝
˝Ѥɇθ
̈͝
˝ϩͱͱ̷ ɇϑϑ˵ͱи
͝
ɵʪ̷ ͱи
A
Flaring bar
Pipe
Yoke
Flaring bar
Pipe
Flare nut
Clutch type Wing nut type
[Flaring tools]
Pipe diameter
[D (mm)]
UʪΧϩ˵ͱ˙Ѥɇθ
̈͝
˝Χɇθϩࣈ
͔
͔
Ƹϑ
̈͝
˝Ѥɇθ
̈͝
˝ϩͱͱ̷ ˙ͱθ
R-410A
Ƹϑ
̈͝
˝ʀͱ
͝
Эʪ
͝
ϩ
̈ͱ
͝
ɇ̷ Ѥɇθ
̈͝
˝ϩͱͱ̷
Clutch type Wing nut type
Ø 6.35 ߢड़ߢ࢏ߧ ߣ࢏ߢड़ߣ࢏ߧ ߣ࢏ߧड़ߤ࢏ߢ
Ø 9.52 ߢड़ߢ࢏ߧ ߣ࢏ߢड़ߣ࢏ߧ ߣ࢏ߧड़ߤ࢏ߢ
Ø 12.70 ߢड़ߢ࢏ߧ ߣ࢏ߢड़ߣ࢏ߧ ߣ࢏ߧड़ߤ࢏ߢ
Ø 15.88 ߢड़ߢ࢏ߧ ߣ࢏ߢड़ߣ࢏ߧ ߣ࢏ߧड़ߤ࢏ߢ
5. A˵ʪʀ
̧ϩ˵ɇϩцͱЇѤɇθʪʒϩ˵ʪΧ
̈Χʪʀͱθθʪʀϩ̷ц࢏
ŵʪ˙ʪθϩͱɵʪ̷ ͱи̷̷
̈Їϑϩθɇϩ
̈ͱ
͝
ϑ˙ͱθʀͱθθʪʀϩɇ
͝
ʒ
̈͝
ʀͱθθʪʀϩʪуɇ
͔
Χ̷ ʪϑͱ˙ѤɇθʪʒΧ
̈Χʪ࢏
Uneven ThicknessCrackedDamaged SurfaceInclinedCorrect
࡛If foreign matters or burrs are not removed after cutting pipe, refrigerant gas may leak.
࡛If foreign matters enter inside the pipe, important interior parts of the unit may get damaged
ͱθΧθͱʒЇʀϩʪ˙ѣʀ
̈ʪ
͝
ʀци̷̷
̈ɵʪθʪʒЇʀʪʒ࢏Ɗͱࡥϩ˵ʪʒ
̈θʪʀϩ
̈ͱ
͝
ͱ˙Χ
̈Χʪϑ˵ͱЇ̷ ʒɵʪʒͱи
͝
иɇθʒʒЇθ
̈͝
˝Χ
̈Χʪ
ʀЇϩϩ
̈͝
˝ͱθѤɇθ
̈͝
˝࢏
CAUTION
54
Refrigerant pipe installation
͝
͝
ʪʀϩ
̈͝
˝ϩ˵ʪѤɇθʪʒΧ
̈Χʪϑ
ॷ A˵ʪʀ
̧
̈˙ϩ˵ʪѤɇθ
̈͝
˝
̈ϑΧθͱΧʪθ̷цʒͱ
͝
ʪɇʀʀͱθʒ
̈͝
˝ϩͱϩ˵ʪϑϩɇ
͝
ʒɇθʒϑ
̈іʪ࢏
ॷ ̷
̈˝
͝
ϩ˵ʪʀʪ
͝
ϩʪθͱ˙ϩ˵ʪΧ
̈Χ
̈͝
˝ɇ
͝
ʒϩ
̈˝˵ϩʪ
͝
ϩ˵ʪѤɇθʪ
͝
Їϩи
̈ϩ˵цͱЇθ˵ɇ
͝
ʒϑ࢏Ɵ˵ʪ
͝
ࡥϩ
̈˝˵ϩʪ
͝
ϩ˵ʪѤɇθʪ
͝
Їϩи
̈ϩ˵
torque wrench in a direction of the arrow indicated in below illustration.
ॷ đɇ
̧ʪϑЇθʪϩͱЇϑʪʪϑϩʪθͱ̷
̈ϩͱʀͱɇϩϩ˵ʪѤɇθʪʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
ϑʪʀϩ
̈ͱ
͝
Flare connection
section
Flare nut
Pipe
Monkey wrench
Torque wrench
Outer diameter (D, mm) Connection torque (N·m) Flare dimension (L, mm) Flare shape (mm)
Ø 6.35 ߣߦड़ߣߪ ߪ࢏ߩड़߫ߣ
߫ߢঌग़ߤঌ
ߦߧঌग़ߤঌ
ŵߢ࢏ߦड़ߢ࢏ߪ
LD
Ø 9.52 ߥߦड़ߦߤ ߣߤ࢏ߪड़ߣߥ࢏ߤ
Ø 12.70 ߫ߦड़ߨߣ ߣߨ࢏ߤड़ߣߨ࢏ߨ
Ø 15.88 ߨߪड़ߪߤ ߫ߣ࢏ߥड़߫ߣ࢏ߩ
Ø 19.05 ߣߢߢड़ߣߤߢ ߤߥ࢏ߨड़ߤߦ࢏ߢ
࡛Blowing Nitrogen gas should be done when welding the pipe.
࡛đɇ
̧ʪϑЇθʪϩͱЇϑʪϩ˵ʪΧθͱЭ
̈ʒʪʒѤɇθʪ
͝
Їϩ࢏
࡛Make sure that there are no cracks or twisted part when you need to bend the pipe.
࡛Uͱ
͝
ͱϩ˙ɇϑϩʪ
͝
ϩ˵ʪѤɇθʪ
͝
Їϩи
̈ϩ˵ʪуʀʪϑϑ
̈Эʪϑϩθʪ
͝
˝ϩ˵࢏
࡛ŵࣛߦߣߢ
̈ϑɇ˵
̈˝˵ΧθʪϑϑЇθʪθʪ˙θ
̈˝ʪθɇ
͝
ϩɇ
͝
ʒϩ˵ʪθʪ
̈ϑɇθ
̈ϑ
̧ͱ˙θʪ˙θ
̈˝ʪθɇ
͝
ϩ̷ʪɇ
̧ɇ˝ʪ
̈˙ϩ˵ʪѤɇθʪ
ʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
̈ϑ
͝
ͱϩʀͱɇϩʪʒи
̈ϩ˵ʪϑϩʪθͱ̷
̈࢏Ɵ˵ʪθʪ˙ͱθʪࡥɇΧΧ̷ цʪϑϩʪθͱ̷
̈ϩͱʀͱɇϩϩ˵ʪѤɇθʪʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
ɇθʪɇ࢏
CAUTION
Pipe installation for an outdoor unit
1. Direction of the pipe
Refrigerant pipe can be withdrawn from the front, left and right
side. Take necessary method to install the pipes according to the
condition of the installation site.
Front side connection
Right side
connection
Left side
connection
55
ENGLISH
Caution for using knock-out hole
Knock-out
hole
࡛Make sure to prevent any damages on the exterior of the outdoor unit.
࡛Remove all burrs around the knock-out hole and apply varnish on the cross section and edges of
the knock-out hole to prevent rust.
࡛Use a cable protection tube and bushing to prevent a cable from being damaged when passing
through a knock-out hole.
CAUTION
2. Connecting refrigerant pipe for outdoor unit
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Front side connection Right/left (and bottom) side connection
Working
process
࡛First, remove the piping cover from the
outdoor unit.
࡛Separate the knock-out hole that you are
going to use. If you separate the knock-
out hole that is going to be unused, small
animals such as squirrels and rats may get
into the unit through the hole.
࡛
̈уϩ˵ʪɵͱϩϩͱ
͔
ϑ
̈ʒʪͱ˙ϩ˵ʪΧ
̈Χ
̈͝
˝ʀͱЭʪθѣθϑϩ
ɇ
͝
ʒϩ˵ʪ
͝
ѣуϩ˵ʪϩͱΧΧɇθϩͱ˙
̈ϩ࢏
࡛Separate the knock-out hole at the bottom
side of the unit and install the pipe.
࡛After installing and insulating the pipe,
close up the remaining holes. If not, small
animals such as rats and squirrels may get
inside the unit.
H/P
Liquid side
pipe
Gas side
pipe
Gas side
pipe Liquid side
pipe
H/R
High
pressure gas
pipe
Liquid side
pipe
Low pressure
gas pipe
Liquid side
pipe
Low pressure
gas pipe
High
pressure gas
pipe
56
Refrigerant pipe installation
CAUTION
< H/P >
Temperature
sensor
Wet towel
Service port
Service valve
Temperature
sensor
Wet towel
Service port
Service valve
< H/R >
Caution for welding the pipe to an outdoor unit
࡛Ǯ˵ʪ
͝
иʪ̷ ʒ
̈͝
˝ϩ˵ʪΧ
̈Χʪࡥϩ˵ʪЇ
̈͝
ϩ
͔
ɇц˝ʪϩʒɇ
͔
ɇ˝ʪʒɵцϩ˵ʪ˵ʪɇϩɇ
͝
ʒѤɇ
͔
ʪ˙θͱ
͔
иʪ̷ʒ
̈͝
˝࢏Ƹϑʪɇ
Ѥɇ
͔
ʪΧθͱͱѣ
͝
˝ʀ̷ ͱϩ˵ϩͱΧθͱϩʪʀϩϩ˵ʪЇ
̈͝
ϩ˙θͱ
͔
ɇиʪ̷ ʒ
̈͝
˝ѣθʪͱθѤɇ
͔
ʪ࢏Ɗʪ
͝
ϑͱθ˙ͱθʒʪϩʪʀϩ
̈͝
˝ͱЇϩϑ
̈ʒʪ
temperature is located on the left side of the welding part so be extra careful not to damage the
sensor when welding.
࡛Ɵ˵ʪĮࣛθ
̈͝
˝ɇ
͝
ʒƟʪѤͱ
͝
Χɇʀ
̧
̈͝
˝
̈͝
ϑ
̈ʒʪϑʪθЭ
̈ʀʪЭɇ̷ Эʪ
͔
ɇц˝ʪϩʒɇ
͔
ɇ˝ʪʒɵцϩ˵ʪ˵ʪɇϩ˙θͱ
͔
иʪ̷ʒ
̈͝
˝࢏
Wrap the bottom side of the service valve with a wet cloth and weld it as shown in the illustration.
Also, water dripping from the wet cloth may interrupt the welding. Make sure the water does not
drip from the wet cloth.
࡛Make sure that connected pipes does not interrupt each other or make contact with the product.
(Vibration may cause damage to the pipes.)
࡛When removing the sealed pipe on the bottom side of the service valve, cut it with a pipe cutter
ѣθϑϩɇ
͝
ʒϩ˵ʪ
͝
ϑϩɇθϩϩ˵ʪиʪ̷ ʒ
̈͝
˝࢏Ǯ˵ʪ
͝
ϩ˵ʪϑʪɇ̷ ʪʒΧ
̈Χʪ
̈ϑиʪ̷ ʒʪʒи
̈ϩ˵ͱЇϩʀЇϩϩ
̈͝
˝ࡥцͱЇ
͔
ɇц˝ʪϩ
injured by the refrigerant within the pipe.
3. Pipe installation between the outdoor units
You will need branch joints, which is an optional accessory, for connecting in between outdoor units in
order to combine outdoor units in module.
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor
Ї
̈͝
ϩϑ࢏࣑Uͱ
͝
ͱϩЇϑʪƟ̟ࣛͱ
̈͝
ϩ࣒
When you install the outdoor units in module, there is no restriction of installation order among outdoor
units.
Height of the connection pipe should be same or lower than the ones connected to the outdoor units.
ॷ A˵ʪʀ
̧ϩ˵ʪʀ˵ɇ
͝
˝ʪϑ
̈͝
ʀͱ
͔
Χɇθ
̈ϑͱ
͝
и
̈ϩ˵ϩ˵ʪUǤđࡥࠫɇ
͝
ʒࠬ
Caution Correct installation Incorrect installation
Refrigerant pipes
should be connected
at the same or lower
level than the ones
connected to the
outdoor unit.
57
ENGLISH
Caution Correct installation Incorrect installation
Refrigerant pipes must
be connected by the
side of the product. Straight section
should be 300mm
or more
Branch joint between
outdoor units must be
installed horizontally.
Install a vertical trap in
following cases as shown
̈͝ϩ˵ʪѣ˝Їθʪࡤ
Case1. Pipe length
between outdoor unit
branches exceeds 2m.
Case2. Pipe length
between outdoor unit and
its branch exceeds 2m.
1 m or less
1 m or less
ߤߢߢड़
ߥߢߢऌ͔͔
ߤߢߢड़
ߥߢߢऌ͔͔
Over 2 m
Over 2 m
Over 2 m
Over 2 m
Examples of refrigerant pipe installation
H/P
1. Using Y-joint
58
Refrigerant pipe installation
2. Using distribution header
H/R
Using Y-joint
MCU
MCU
MCU
MCU
MCU
MCU
Note 1)
Note 1) Direct-connected indoor unit without MCU (for HR only)
This indoor unit can only be used for cooling operation. (Heating operation is not possible.)
Connect indoor unit to liquid and low pressure gas pipe.
Change the installation option for direct-connected indoor unit without MCU. (refer to the indoor unit
installation manual)
59
ENGLISH
Allowable length of the refrigerant pipe and the installation examples
H/P
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Single Installation Module installation
Installing only with
Y-joint
Branch joint
Outdoor unit
Indoor unit
Branch joint
Outdoor unit
Indoor unit
Installing with
Y-joint and
distribution header
Branch joint
Distribution header
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Distribution header
Branch joint
Installing only with
distribution header
Outdoor unit
Indoor unit
Distribution header
Outdoor unit
Indoor unit
Distribution header
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Example Remarks
Maximum
allowable
length of
pipe
ĮЇϩʒͱͱθЇ
̈͝
ϩड़
Indoor unit
Actual
length
(Equivalent
length)
200m and
below
(220m and
below)
Installing only
with Y-joint
ɇॐɵॐʀॐʒॐʪॐ˙ॐ˝ॐΧख़
200m(220m)
Equivalent
length
Y-joint: 0.5 m,
Distribution
header: 1 m
Installing with
Y-joint and
distribution
header
ɇॐɵॐ˵ख़ߤߢ͔ߢ࣑ߤߤ͔ߢ࣒ࡥ
ɇॐ̈ॐ̧ख़ߤߢ͔ߢ࣑ߤߤ͔ߢ࣒
Installing only
with distribution
header
ɇॐ̈ख़ߤߢ͔ߢ࣑ߤߤ͔ߢ࣒
Total
length of
pipe (m)
1,000 m or
less
Installing only
with Y-joint
a+b+c+d+e+f+g+h+i+
̟ॐ̧ॐ̷ॐ͔ॐ͝ॐΧख़ߣߢߢ͔ߢ -
Installing with
Y-joint and
distribution
header
a+b+c+d+e+f+g+h+i+j+k
ख़ߣߢߢ͔ߢ -
Installing only
with distribution
header
a+b+c+d+e+f+g+h+i
ख़ߣߢߢ͔ߢ -
Outdoor unit
ड़ĮЇϩʒͱͱθ
unit (Module
installation)
Pipe length
10 m or less
уख़ߣߢ
͔
ࡥцख़ߣ͔ߢࡥіख़ߣߢ
͔
Equivalent
length
13 m or less
уख़ߣߥ
͔
ࡥцख़ߣ͔ߥࡥіख़ߣߥ
͔
Maximum
allowable
height
difference
of pipe
ĮЇϩʒͱͱθЇ
̈͝
ϩड़
Indoor unit 110/110m
Note 2)
²ߣख़ߣߣߢࢩߣߣ͔ߢ
Ã
͝
ʒͱͱθЇ
̈͝
ϩड़
Indoor unit
50m or less ²ߤख़ߧ͔ߢ
9Їϩࡥи˵ʪ
͝
đ७७७७ĘůUk²७ࢩđ७७७âĘǤ७
̈ϑ
̈͝
ϑϩɇ̷̷ ʪʒࡥ²ߤ
̈ϑߣߧ
͔
ͱθ̷ʪϑϑ
60
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Example Remarks
Maximum
allowable
length after
branch joint
First branch
̟ͱ
̈͝
ϩड़ɇθϩ˵ʪϑϩ
Indoor unit
Pipe length
45 m or less
Installing only with Y-joint
ɵॐʀॐʒॐʪॐ˙ॐ˝ॐΧख़ߦߧ
͔
-
Installing with Y-joint and
distribution header
̈ॐ̧ख़ߦߧ
͔
Installing only with
distribu-tion header
̈ख़ߦߧ
͔
ߦߧ
͔
ड़߫ߢऌ͔
Note 1)
ŵʪαЇ
̈θʪʒʀͱ
͝
ʒ
̈ϩ
̈ͱ
͝
ϑ
͔
Їϑϩɵʪϑɇϩ
̈ϑѣʪʒ -
EEV kit Model name Remarks
kkǤ
̧
̈ϩड़
Indoor unit
Actual pipe
length
2 m MEV-E24SA 1 indoor
Apply to products without EEV
(Wall mount & ceiling)
MEV-E32SA
20 m or less
MXD-E24K132A
2 indoorMXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
Please refer to the EEV Kit manual.
Note 1) Required condition
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Condition Example
̈θϑϩɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩड़
Farthest Indoor unit
ߦ͔ߧख़ɵॐʀॐʒॐʪॐ˙ॐ˝ॐΧख़͔߫ߢࡤɵθɇ
͝
ʀ˵Χ
̈Χʪϑ
(b, c, d, e, f, g) size must be increased by 1
grade
Total length of
extended pipe
If the size of pipe (main pipe), between the
ѣθϑϩɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩɇ
͝
ʒϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩࡥ
̈ϑ
͝
ͱϩ
increased by 1 grade, a+(b+c+d+e+f+g)×2
ॐ˵ॐ̈ॐ̟ॐ̧ॐ̷ॐ͔ॐ͝ॐΧख़ߣߢߢߢ
͔
If the size of pipe (main pipe), between the
ѣθϑϩɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩɇ
͝
ʒϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩࡥ
̈ϑ
increased by 1 grade, (a+b+c+d+e+f+g)×2
ॐ˵ॐ̈ॐ̟ॐ̧ॐ̷ॐ͔ॐ͝ॐΧख़ߣߢߢߢ
͔
kɇʀ˵ǽ̟ࣛͱ
̈͝
ϩड़
Each indoor unit ˵ࡥ
̈ࡥ
̟ࡥࡰΧख़ߦߧ
͔
Difference between the distance of the outdoor unit to the farthest indoor
Ї
̈͝
ϩɇ
͝
ʒ
͝
ʪɇθʪϑϩ
̈͝
ʒͱͱθЇ
̈͝
ϩख़ߦ͔ߧࡥ࣑ɇॐɵॐʀॐʒॐʪॐ˙ॐ˝ॐΧ࣑࣒ࣛɇॐ˵࣒ख़ߦ͔ߧ
Note 2) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If
the height difference is over 40m, contact your local dealer for more information.)
but when the indoor unit is located at lower level than outdoor unit, allowable height difference is
110m (If the height difference is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Refrigerant pipe installation
61
ENGLISH
H/R
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Installation with Y-joint
Installing with
MCU only
Installing with
MCU and Y-joint
Direct-connected indoor unit without MCU (Cooling only)
(Connecting Only Low Pressure Gas Pipe / Liquid Pipe note3)
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Example Remarks
Maximum
allowable
pipe length
ĮЇϩʒͱͱθЇ
̈͝
ϩड़
Indoor unit
Actual pipe
length
(Equivalent
length)
200 m or less
(220 m or
less)
Installing only
with MCU ɇॐ˝ॐ̟ख़ߤߢߢ
͔
࣑ߤߤߢ
͔
Equivalent length
࡛ ǽ̟ࣛͱ
̈͝
ϩࡤߢ࢏ߧऌ͔
࡛ Distribution
˵ʪɇʒʪθࡤߣऌ͔
࡛ MCU: 1 m
Installing
with MCU and
Y-joint
ɇॐɵॐ˵ॐ̧ख़ߤߢߢ
͔
࣑ߤߤߢ
͔
Total length
of pipe
1000 m or less
Installing only
with MCU
ɇॐɵॐʀॐʒॐʪॐ˙ॐ˝ॐ˵ॐ̈ॐ̟ख़ߣߢߢߢ
͔
Installing
with MCU and
Y-joint
ɇॐɵॐʀॐ࢏࢏࢏ॐθख़ߣߢߢߢ
͔
Outdoor unit
ड़ĮЇϩʒͱͱθ
unit (Module
installation)
Pipe length ߣߢऌ͔ͱθ̷ʪϑϑ уख़ߣߢ
͔
ࡥцख़ߣ͔ߢࡥіख़ߣߢ
͔
Equivalent
length ߣߥऌ͔ͱθ̷ʪϑϑ уख़ߣߥ
͔
ࡥцख़ߣ͔ߥࡥіख़ߣߥ
͔
đAƸड़Ã
͝
ʒͱͱθ
unit Pipe length 45 m or less
Installing only
with MCU
ɵॐʀख़ߦߧ
͔
ࡥɵॐʒख़ߦߧ
͔
ࡥɵॐʪ
ख़ߦߧ
͔
ࡥ˙ख़ߦߧ
͔
ࡥ˝ॐ˵ख़ߦߧ
͔
ࡥ
˝ॐ̈ख़ߦߧ
͔
ࡥ˝ॐ̟ख़ߦߧ
͔
Installing
with MCU and
Y-joint
c+d, c+e, c+f, g, h+i, h+j, h+k,
͝
ࡥͱࡥΧࡥαࡥθख़ߦߧ
͔
62
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Example Remarks
Maximum
allowable
height
difference
ĮЇϩʒͱͱθЇ
̈͝
ϩड़
Indoor unit
Pipe length
110 m / 110 m
Note 1)
²ߣख़ߣߣߢ
͔
ࢩߣߣߢ
͔
Ã
͝
ʒͱͱθЇ
̈͝
ϩड़
Indoor unit
40 m or less ²ߤख़ߦߢ
͔
9Їϩࡥи˵ʪ
͝
đ७७७७ĘůUk²७ࢩđ७७७âĘǤ७
̈ϑ
installed, H2 is 15 m or less.
Ã
͝
ʒͱͱθЇ
̈͝
ϩड़
Indoor unit
(in one MCU)
15 m or less ²ߥख़ߣߧ
͔
đAƸड़đAƸ 30 m or less ²ߦख़ߥߢ
͔
Maximum
allowable
length after
branch joint
First branch
̟ͱ
̈͝
ϩड़ɇθϩ˵ʪϑϩ
Indoor unit
Pipe length
ߦߧऌ͔ͱθ̷ʪϑϑ
Installing only
with MCU ˝ॐ̟ख़ߦߧ
͔
Installing
with MCU and
Y-joint
ɵॐ˵ॐ̧ख़ߦߧ
͔
̷ॐ͔ॐαख़ߦߧ
͔
̷ॐθख़ߦߧ
͔
ߦߧड़߫ߢ
͔
Note 2)
ŵʪαЇ
̈θʪʒʀͱ
͝
ʒ
̈ϩ
̈ͱ
͝
ϑ
͔
Їϑϩɵʪϑɇϩ
̈ϑѣʪʒ
EEV Kit Model name Remarkers
kkǤ
̧
̈ϩड़
Indoor unit
Actual pipe
length
2 m MEV-E24SA 1 indoor
Apply to products without EEV
(Wall mount & ceiling)
MEV-E32SA
20 m or
less
MXD-E24K132A
2 indoorMXD-E24K200A
MXD-E32K200A
MXD-E24K232A
3 indoor
MXD-E24K300A
MXD-E32K222A
MXD-E32K300A
Please refer to the EEV Kit manual.
Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 110m, (If
the height difference is over 40m, contact your local dealer for more information.) but when the indoor
unit is located at lower level than outdoor unit, allowable height difference is 110m (If the height
difference is over 50m, need to decide whether to install PDM kit or not.)
Model name of the PDM kit : MXD-A38K2A, MXD-A12K2A, MXD-A58K2A
Refrigerant pipe installation
63
ENGLISH
Note 2) Required condition
A̷ ɇϑϑ
̈ѣʀɇϩ
̈ͱ
͝Condition Example
First branch
̟ͱ
̈͝
ϩड़ɇθϩ˵ʪϑϩ
Indoor unit
ߦߧ
͔
ख़ɵॐ˵ॐ̧ࡥ̷ॐ͔ॐαࡥ̷ॐθख़߫ߢ
͔
ࡤƊ
̈іʪͱ˙ϩ˵ʪ
branch liquid and low pressure gas pipes
(b, l, m) must be increased by 1 grade.
Total length of
extended pipe
If the size of pipe (main pipe), between
ϩ˵ʪѣθϑϩɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩɇ
͝
ʒϩ˵ʪͱЇϩʒͱͱθЇ
̈͝
ϩࡥ
is not increased by 1 grade, a+(b+l+m)
уߤॐʀॐʒॐʪॐ˙ॐ˝ॐ˵ॐ̈ॐ̟ॐ̧ॐ͝ॐͱॐΧॐαॐθख़ߣߢߢߢ
͔
If the size of pipe (main pipe), between
ϩ˵ʪѣθϑϩɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩɇ
͝
ʒϩ˵ʪͱЇϩʒͱͱθ
unit, is increased by 1 grade, (a+b+l+m)
уߤॐʀॐʒॐʪॐ˙ॐ˝ॐ˵ॐ̈ॐ̟ॐ̧ॐ͝ॐͱॐΧॐαॐθख़ߣߢߢߢ
͔
đAƸड़kɇʀ˵
indoor unit
ʀॐʒࡥʀॐʪࡥʀॐ˙ࡥ˝ࡥ˵ॐ̈ࡥ˵ॐ̟ࡥ˵ॐ̧ࡥ
͝
ࡥͱΧࡥαࡥθख़ߦߧ
͔
Difference between the distance of the outdoor unit to the
˙ɇθϩ˵ʪϑϩ
̈͝
ʒͱͱθЇ
̈͝
ϩɇ
͝
ʒ
͝
ʪɇθʪϑϩ
̈͝
ʒͱͱθЇ
̈͝
ϩख़ߦߧ࣑ɇॐɵॐ˵ॐ̧࣒ࣛ
࣑ɇॐɵॐʀॐʒ࣒ख़ߦߧ
Note 3) For indoor units to which no MCU is connected, be sure to set their options to “Cooling only indoor unit,
and then connect them to a low pressure gas pipe and a liquid pipe. Be sure to combine the cooling
only indoor units so that their total capacity becomes 50% or less of the total capacity of all indoor
units.
Note 4) In case of connecting more than one indoor unit in one MCU Port, the below indoor units
ʀɇ
͝
͝
ͱϩɵʪʀͱ
͔
ɵ
̈͝
ʪʒ࢏kŵǤΧ̷ Їϑ࣑đ७७७ĘçUk७७࣒ࡥĮťʒЇʀϩ࣑đ७७७âĘkťk७७࣒ࡥ²цʒθͱƸ
̈͝
ϩ
²k࣑đ७७७Ę9U७७࣒ࡥ²цʒθͱƸ
̈͝
ϩ²Ɵ࣑đ७७७Ę9७७࣒ࡥ²Ƹ
̧
̈ϩ࣑đǹUࣛç७७७ĘࡥđAđࣛU७७७Ę࣒
Note 5)
In case of connecting two MCU ports with Y-joint, the indoor units cannot be combined to more than one.
64
Refrigerant pipe installation
Installing the branch joints
Branch joints must be installed ‘horizontally’ or ‘vertically’.
Horizontal installation
Vertical installation
࡛ͱθड़âϩцΧʪɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩϑࡤAͱ
͝
͝
ʪʀϩϩ˵ʪɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩϩͱϩ˵ʪʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
Χ
̈Χʪи
̈ϩ˵ϩ˵ʪΧθͱЭ
̈ʒʪʒ
reducer.
࡛ͱθçड़ȐϩцΧʪɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩϑࡤAЇϩϩ˵ʪʀͱ
͝
͝
ʪʀϩ
̈ͱ
͝
Χɇθϩͱ˙ϩ˵ʪɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩͱθϩ˵ʪΧθͱЭ
̈ʒʪʒϑͱʀ
̧ʪϩࡥ
according to the diameter of the connection pipe, before connecting them.
ĮЭʪθߣߢड़ߣ͔͔ߧ
NOTE
࡛Ã
͝
ϑϩɇ̷̷ ϩ˵ʪɵθɇ
͝
ʀ˵
̟ͱ
̈͝
ϩи
̈ϩ˵
̈͝
ग़ߣߧঌͱ˙ϩ˵ʪ˵ͱθ
̈іͱ
͝
ͱθЭʪθϩ
̈ʀɇ̷ ̷̈͝ʪ࢏
࡛Make sure that the pipe is not bent at where it is connected to the branch joint.
࡛Keep a minimum straight line distance of 500mm or more before connecting branch joint.
Ã
͝
ϑϩɇ̷̷ и
̈ϩ˵
̈͝
ग़ߣߧঌͱ˙ϩ˵ʪ˵ͱθ
̈іͱ
͝
ͱθЭʪθϩ
̈ʀɇ̷ ̷
̈͝
ʪ࢏
Minimum straight
line (over 500mm)
Connect to
indoor unit
Pipe
Before branching
After branching
After branching
Gas side/Liquid side branch joint
Pipe connection
Socket
Connect to other branch joint or indoor unit
Socket
CAUTION
65
ENGLISH
Installing the distribution header
1. Ɗʪ̷ʪʀϩϩ˵ʪθʪʒЇʀʪθϩ˵ɇϩѣϩϑϩ˵ʪʒ̈ʪϩʪθͱ˙ϩ˵ʪΧ̈Χʪ
<Gas side>
Socket
Pipe *
To indoor unit
Pipe*
Socket
To outdoor unit
<Liquid side>
Socket
Pipe*
To indoor unit
Pipe*
Socket
To outdoor unit
Provided item
Pipe : Separately purchased item
2. If the number of connected indoor unit is fewer than ports on the distribution header, block the unused
ports with caps.
<Liquid side>
Case of blocking the unused
distribution header ports
Connect
in order
Welding part
Provided
item
<Gas side>
Case of blocking the unused
distribution header ports
Connect
in order
ͱθâϩцΧʪʒ̈ϑϩθ̈ɵЇϩ̈ͱ͝ʪɇʒʪθ
Connect the distribution header to the connection pipe with the provided reducer.
ͱθçȐϩцΧʪʒ̈ϑϩθ̈ɵЇϩ̈ͱ͝ʪɇʒʪθϑ
Cut the provided socket, according to the diameter of the connection pipe, before connecting it.
ĮЭʪθ
NOTE
Connect the indoor units in order, while respecting the direction of the arrow shown in the
illustration.
When indoor units are connected to same distribution head, indoor unit must be connected in order
of their capacity, from largest to smallest.
CAUTION
66
Refrigerant pipe installation
3. Install the distribution header horizontally.
Install the distribution header horizontally so that its ports does not face down.
9ʪ̷ͱи
Horizon line
Socket Distribution header
Pipe
(Separately purchased item)
9ʪ̷ͱи
Horizon line
Horizon line
< Liquid side >
9ʪ̷ͱи
Horizon line
9ʪ̷ͱи
Horizon line
< Gas side >
67
ENGLISH
Installing the branch joint between outdoor units
Installation of outdoor joints
Do not install the outdoor
joint in this direction.
Liquid pipe
High pressure
gas pipe
Gas pipe
High pressure gas pipe only applies to the H/R product.
<Liquid side>
Use the attached reducer according to the selected pipe
size.
Pipe
Reducer
Reducer
Pipe
To other outdoor unit
To other outdoor joint or Y-joint of the main pipe
To other outdoor joint or outdoor unit
<Gas side>
Use the attached reducer according to the selected pipe
size.
Pipe
Reducer
Reducer
Pipe
To other outdoor unit
To other outdoor joint or Y-joint of the main pipe
To other outdoor joint or outdoor unit
68
Refrigerant pipe installation
Use the attached reducer according to the selected
pipe size.
Pipe
Reducer
Reducer
Pipe
To other outdoor unit
To other outdoor joint or Y-joint of the main pipe
<High pressure gas side>
To other outdoor joint or outdoor unit
Connect the Outdoor joint to the pipe by cutting the outlet of the Outdoor joint or provided reducer
properly.

or more
NOTE
Installing the MCU
đAƸϑΧʪʀ̈ѣʀɇϩ̈ͱ͝
Model MCU-S6NEK2N MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N
Exterior of MCU
Number of
connectable indoor
units at one port
Up to 8 units Up to 8 units Up to 8 units Up to 8 units
The maximum
capacity of the
connectable indoor
units at one port
16 kW 16 kW 16 kW 16 kW
The maximum
capacity of the
connectable indoor
units
61.6 kW 61.6 kW 32.0 kW 16 kW
Internal EEV Not included
Ã͝ʒͱͱθЇ̈͝ϩϑӥϩ˵ͱЇϩϩʪθ͝ɇ̷kkǤđĘƟUkđĘUkʀɇ͝ͱϩɵʪʀͱ͝͝ʪʀϩʪʒ
directly to the MCU.
ť̷ʪɇϑʪʀͱ͝͝ʪʀϩϩ˵ʪϑʪʒͱͱθЇ̈͝ϩϑЇϑ̈͝˝kkǤϩđkǤkƊđǹUkç
CAUTION
69
ENGLISH
Installing the indoor units
Model MCU-S6NEK2N MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N
Example installing
(Each port
connection)
Example installing
(MCU series
connection)
MCU MCU
MCU series connection
Installing indoor
units
Under 16.0 kW indoor unit : Don’t use Y-connector
ߢǮߢǮʒͱͱθЇ̈͝ϩƸϑʪǽʀͱ͝͝ʪʀϩͱθɇϩϩ˵ʪɇϑø̈αЇ̈ʒʪ
Ã˙цͱЇиɇ͝ϩϩͱʀͱ͝ϩ̈͝ЇͱЇϑʀͱͱ̷̈͝˝ͱΧʪθɇϩ̈ͱ͝Ї͝ʒʪθߧϑʪϩͱЇϩʒͱͱθ
‘Expand operational temperature range for cooling operation (HR only)’,
ɇ͝ʒЇϑʪǽʀͱ͝͝ʪʀϩͱθͱ͝ߧߢǮʒͱͱθЇ̈͝ϩ
In case of using Y-connector, it is only connectable for port combination at below
Connectable port combination for Y-connector : A + B port, C + D port, E + F port
Non-connectable port combination for Y-connector : B + C port, D + E port, non-
continuous port
Set Dip Switch option for using Y-connector
1
ON
2 3 4 1
ON
2 3 4 1
ON
2 3 4 1
ON
234
S/W Option S/W Option S/W Option S/W Option
Default Combination of A+B port Combination of C+D port
Combination of E+F port
In case of MCU connection in series, the maximum capacity of indoor
units in MCU series connection is 61.6 kW
This unit is only
connectable for
one port under
16 Kw
This unit is
impossible to
connect MCU to
MCU in series.