Tripp Lite PDU3V602D354B Bruksanvisning
Tripp Lite
Elskena
PDU3V602D354B
Läs nedan 📖 manual på svenska för Tripp Lite PDU3V602D354B (68 sidor) i kategorin Elskena. Denna guide var användbar för 11 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare
Sida 1/68

1. Important Safety 2
Instructions
2. Installation 3
2.1 Mounting the ATS 3
2.2 Mounting the Power Strip 4
2.3 Connecting the Power Strip 4
to the ATS
2.4 Connecting the ATS 5
2.5 Networking the ATS 5
3. Features 6
4. Digital Display 8
5. Using the Digital Display 11
5.1 Navigating Display Menus 11
and Submenus
5.2 Navigating Config Menus 18
and Submenus
6 20. Configuration and Operation
6.1 Automatic Transfer Switch 20
7. Service 22
8. Warranty and Product 22
Registration
Español 24
Français 47
Owner’s Manual
PDU360AT6G60
(Series Number: AG-013D)
3-Phase 1U Monitored Rack PDU
with Automatic Transfer Switch (ATS)
PDU3V602D354, PDU3V602D354A,
PDU3V602D354B
(Series Number: AG-013E)
3-Phase Vertical Power Strip
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2016 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
16-01-031-933588.indb 1 3/22/2016 4:14:15 PM

2
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be
followed during the installation, operation and storage of this product.
Failure to heed these instructions and warnings may affect the
product warranty.
• The Power Strip provides the convenience of multiple outlets, but DOES NOT provide surge or
line noise protection for connected equipment.
• Use only with Tripp Lite PDU3V60XXXXX Series with overcurrent protection. Overcurrent
protection per PDU consists of six double-pole 20A, 240V AC breakers (2 per phase).
• Do not exceed the following equipment ratings:
• For Outputs 1 and 2, the maximum full balanced load is 13.9A per bank when powered by a
3-phase ATS (Automatic Transfer Switch) with a rated input of 48A.
• The Automatic Transfer Switch and Power Strip are designed for indoor use only, in a controlled
environment, away from excess moisture, temperature extremes, conductive contaminants, dust
or direct sunlight.
• Keep indoor ambient temperature between 32°F and 113°F (0°C and 45°C).
• The Automatic Transfer Switch and Power Strip must be installed by a qualified technician only.
• Do not attempt to mount the Automatic Transfer Switch or Power Strip to an insecure or
unstable surface.
• Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
• Connect the Automatic Transfer Switch to an outlet that is in accordance with your local building
codes and that is adequately protected against excess currents, short circuits and earth faults.
• The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
• Do not connect the Automatic Transfer Switch to an ungrounded outlet or to extension cords or
adapters that eliminate the connection to ground.
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• Individual equipment connected to the Power Strip should not draw more current than the
individual outlet’s rating.
• The total load connected to the Power Strip must not exceed the maximum load rating for the
Automatic Transfer Switch.
• Do not attempt to modify the Automatic Transfer Switch’s or Power Strip’s input plugs or power
cables.
• Do not drill into or attempt to open any part of the Automatic Transfer Switch or Power Strip
housing. There are no user-serviceable parts inside.
• Do not attempt to use the Automatic Transfer Switch or Power Strip if any part of it becomes damaged.
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
1. Important Safety Instructions
16-01-031-933588.indb 2 3/22/2016 4:14:15 PM

3
2.1 Mounting the Automatic Transfer Switch (ATS)
Mount your equipment in a 4-post rack or rack enclosure. The user must determine the fitness of
hardware and procedures before mounting. If hardware and procedures are not suitable for your
application, contact the manufacturer of your rack or rack enclosure. The procedures described in this
manual are for common rack and rack enclosure types and may not be appropriate for all applications.
Note: Each snap-in slide rail assembly consists of a sliding rack enclosure mounting bracket and an inner
channel rail. For ease of installation, the inner channel rails come pre-attached to the ATS unit.
2. Installation
1 Align the rear bracket's tabs with the rack
enclosure's square mounting holes 1A
and push the metal hooks through the
mounting holes 1B. Push the rear bracket
toward the enclosure support post in
order for the blue tabs to snap into the
mount 1A. Align the front bracket's tabs
with the rack enclosure's front square
mounting holes and push the metal
hooks through the mounting holes.
Finally, push the front bracket toward the
enclosure support post in order for the
blue tabs to snap into the mount 1B.
2 Repeat step one for the second mounting
bracket on the opposite side of the rack
enclosure.
3 Once both mounting brackets are fixed
onto the rack enclosure, secure the rear
brackets using the included M5X10L
screws.
4 Align the inner channel rails attached to
the ATS with the mounting brackets. Then
slide the unit into the rail assembly. Using
a screwdriver, secure the ATS’s panel-
mounted screws to the rack enclosure.
1A
1B
3
4
16-01-031-933588.indb 3 3/22/2016 4:14:16 PM

4
2.2 Mounting the Power Strip
Note: Power strips require a 4-inch installation width
within the rack. Mounting buttons come pre-installed
on the Power Strip for toolless mounting. A second
set of button mounting holes on the Power Strip
allow alternate positioning in the rack.
Position the Power Strip as desired within the
rack enclosure, align the buttons with the rack
mounting slots and slide the Power Strip
downward into position.
Your model may differ slightly from image.
2. Installation
2.3 Connecting the Power Strip to the ATS
The power strip has two 8-conductor plugs.
Each cord is labeled Output 1 and Output 2.
The cord labeled Output 1 must be connected
to the ATS Output 1 receptacle; the cord
labeled Output 2 must be connected to the ATS
Output 2 receptacle.
The power strip also has a 6-conductor circuit
detection cable that requires connection from
the power strip to the ATS unit.
Your model may differ slightly from image.
16-01-031-933588.indb 4 3/22/2016 4:14:17 PM

5
2. Installation
2.4 Connecting the ATS
2.4.1 Connect ATS Input Plugs
Note: The ATS comes equipped with two 3-Phase AC
power inputs: Source A and Source B. Source A is
the default preferred (primary) source. See 5.2
Navigating Config Menus and Submenus section
for instructions on changing the preferred source. The
connection instructions below assume Source A is the
preferred source.
Connect the Source A input plug A to a
preferred 3-Phase AC power source. Under
normal operating conditions, the ATS will
distribute AC power from the Source A input
source. Connect the Source B input plug B to
an alternative source of grounded AC power.
Do not plug the Source B input into the same
power source as the Source A input. The ATS
will distribute AC power from the Source B
input only if the Source A input becomes
unavailable or unstable.
2.4.2 Connect Equipment
to Power Strip
Do not exceed the load rating of the power
strip. The total electrical current used by each
phase of the power strip will be displayed in
amperes on the digital meter.
2.5 Networking the ATS
The ATS provides remote monitoring and more via Web browser, telnet and SNMP-based Network
Management Systems.
Your ATS can receive its IP address assignment via DHCP server (dynamic) or static (manual)
addressing methods. If you are uncertain which method to use, contact your network administrator
for assistance before continuing the configuration process.
For more information about configuration and operation of the ATS via the PowerAlert
® Web
browser interface, refer to the SNMPWEBCARD User's Guide by going to
www.tripplite.com/support/snmpwebcard.
Note: The MAC address (12-digit string in this format: 000667xxxxxx) is printed on a label and attached to the ATS
enclosure. For static IP address assignment, use the DB9 configuration cable (73102) included with the ATS.
A
B
16-01-031-933588.indb 5 3/22/2016 4:14:17 PM

6
3. Features
ATS Automatic Transfer Switch
(PDU360AT6G60)
Power Strip* (PDU3V602D354, PDU3V602D354A, PDU3V602D354B)
1 Power Strip Outlets: These single-phase IEC C13 and C19 outlets receive power from the
interlaced 3-phase power input connections of Source A or Source B of the ATS. These
outlets are not controllable.
2 Power Strip Input Power Cords: The 7-conductor plugs
contain an 8-position connector that attaches directly to the
ATS.
3 ATS Source A and Source B Input: The cords are permanently
attached to the ATS and have IEC 309 60A Blue (3P + E)
plugs.
4 Digital Display: Shows source status, measured values, display
modes and other information. See the Digital Display section
for detailed explanations of the indicators and displays.
5 SNMP Reset Button: Press the reset button for 3 seconds to
reboot the ATS network card. Rebooting the network card will
not erase network settings or interrupt AC power. The reset
button is recessed. Use a paper clip or other suitable object to
press it.
386 7
5
11 11 12
10
102
4
9 9
IEC 309 60A Blue (3P + E)
* PDU3V602D354B model shown. Appearance may vary by model.
1
16-01-031-933588.indb 6 3/22/2016 4:14:19 PM

7
3. Features
6 Network Interface: Use the RJ-45 jack to connect the ATS to the network
with a standard Ethernet patch cable. The Status LED A and Link LED B
indicate operating conditions as shown in the table below. These ports are
not compatible with PoE (Power Over Ethernet) applications.
Network Operating Conditions
A Status LED Color B Link LED Color
Off OffCard Not Initialized No Network Connection
Steady Green Card Initialized and Operational Flashing Amber 100 Mbps Network Connection
Flashing Amber Error - Card Not Initialized Flashing Green 10 Mbps Network Connection
7 Configuration Port: Use this port to provide direct terminal connection to a computer with a
terminal emulation program. A serial cable is included with the ATS. If you need to order a
replacement cable, contact Tripp Lite Customer Support at www.tripplite.com/support.
8 ENVIROSENSE Port: Use this port to connect a Tripp Lite ENVIROSENSE environmental
sensor to provide remote temperature/humidity monitoring and a dry contact interface to
control and monitor alarm, security and telecom devices. Visit www.tripplite.com for ordering
information.
Note: Do not connect a keyboard or mouse to this port.
9 Circuit Breakers: Each single phase output load (six output load banks) has its own double-
pole magnetic breaker. If the connected equipment load exceeds the maximum load rating for
that phase, the circuit breaker will trip. Disconnect excess equipment before resetting the
breaker(s).
10 Chassis Ground Screw: Use this to connect equipment that requires a chassis ground.
11 ATS Mating Receptacles: These receptacles only accept the 8-position connector on the
power strip input power cords.
Note: The receptacle labeled Output 1 on the ATS must be matched with Output 1 cord from the power
strip and the receptacle labeled Output 2 on the ATS must be match with Output 2 cord from the power
strip.
12 Breaker Detect: The power strip’s six position cable connects to the ATS and allows the ATS
to sense the ON/OFF state of the power strip circuit breakers.
A B
16-01-031-933588.indb 7 3/22/2016 4:14:19 PM

8
4. Digital Display
1 Source Status LEDs: Lit LED patterns indicate which source is preferred, which sources(s) is
(are) available for use, and which source is currently being used. See Source Status LED
Indicators section for an explanation of the LED patterns.
2 Breaker Trip LED: Lit when a breaker has tripped.
3 3-Digit Display: Shows measured or calculated values such as Amperage, Kilowatts, Voltage,
Power Unbalance Percentage, Frequency, Power Factor and Temperature.
4 Enter Button: When a menu is selected using the Mode Button, the Enter Button scrolls
through the submenus within each category. Submenus are shown by the Indicator LEDs.
Note: Pushing the Enter and Mode button simultaneously for 2 seconds displays the IP address.
5 Indicator LEDs: Lit LED indicates which value is being displayed on the 3-digit screen.
Amps (A): The input current on the selected Source Input (A# or b#) or Output Load Circuit
(C#) is displayed in amps.
Wattage (kW): The Output Power for the selected Output Load Circuit (C#) or Total Output
Power (OP) is displayed in kW.
Voltage (V): The Source A or B Input Phase-to-Phase voltage (A# or b#) or Output Load
Circuit voltage (C#) is displayed in volts.
Frequency (Hz): Source Input A or B frequency is displayed in Hz.
Power Factor (PF): Output Load power factor is displayed as a decimal (from 0 to 1.00).
1 742
3 5 6
16-01-031-933588.indb 8 3/22/2016 4:14:19 PM

10
4. Digital Display
Source Status LED Indicators
LED pattern Description
• Source A preferred
• Both sources of good quality and available
• Output is connected to Source A
• Source B preferred
• Both sources of good quality and available
• Output is connected to Source B
• Source A preferred
• Source A is of poor quality or unavailable
• Output is connected to Source B
• Source B preferred
• Source B is of poor quality or unavailable
• Output is connected to Source A
• Source A preferred
• Sources are of mixed levels of stability
• Output phases are powered by different sources
Note: “Available” LED will flash if phases of the source are of mixed levels of stability.
Lit LED
Unlit LED
Flashing LED
Note: This event is
a rare occurrence.
16-01-031-933588.indb 10 3/22/2016 4:14:20 PM

12
5. Using the Digital Display
Volts (L2-L3)
Volts (L3-L1)
Hz (L2-L3)
Hz (L3-L1)
Source A
Phase Current (L2)
Source A
Phase Current (L3)
i 3.2.
i 3.2.
2.0.8
2.0.8
6.0
6.0
A2
A3
A2
A3
A2
A3
16-01-031-933588.indb 12 3/22/2016 4:14:21 PM

13
5. Using the Digital Display
Volts (L1-L2)
Volts (L2-L3)
Hz (L1-L2)
Hz (L2-L3)
Source B
Phase Current (L1)
Source B
Phase Current (L2)
i 3.2.
i 3.2.
2.0.8
2.0.8
6.0
6.0
16-01-031-933588.indb 13 3/22/2016 4:14:21 PM

15
5. Using the Digital Display
Voltage (L1-L2)
Voltage (L2-L3)
Power Factor (L1-L2)
Power Factor (L2-L3)
Circuit Current (L1-L2) (Page 14)
Output Load Circuit
Circuit Current (L2-L3)
Kilowatts (L2-L3)
2 0 8
2 0 8
i.0 0
i.0 0
C i
C 2
C i
C 2
i 3.2
2.7 5
C 2
C 2
16-01-031-933588.indb 15 3/22/2016 4:14:22 PM

16
5. Using the Digital Display
Voltage (L3-L1)
Power Factor (L3-L1)
Output Load Circuit
Circuit Current (L3-L1)
Total Output Power
Kilowatts
Temperature
tC = Celsius; tF = Fahrenheit
Kilowatts (L3-L1)
Source A Phase Current (L1) (Page 11)
Note: Total of six loads C1-C6
2 0 8
i.0 0
8.2 5
2 5
C 3
C 3
OP
i 3.2
2.7 5
C 3
C 3
16-01-031-933588.indb 16 3/22/2016 4:14:23 PM

17
5. Using the Digital Display
Fault Code Menu
The Fault Code Menu is only available when a breaker is tripped, causing the Breaker Trip LED to
illuminate. The display will jump to the Fault Code menu and auto scroll through the tripped
breakers (only tripped breakers will be shown in the scroll sequence). Manual scrolling option is still
available, but Auto Scroll feature will remain active within the fault code menu while a fault exists.
If Auto Scroll is disabled, the display will still jump to the Fault Menu but you must manually scroll
through each tripped breaker individually. The number in the 3-digit display is defined as:
br1 = Output Breaker L1-L2; br2 = Output Breaker L2-L3; br3 = Output Breaker L3-L1
Breaker 1 Tripped
IP Address Display
At any time, you can press and hold both Mode and Enter buttons for 2 seconds to show the IP
address of the connected SNMP card. The 3 digit display will show “IP“. The 2 digit display to the right
of it will show one IP address digit at a time until it shows the entire IP address. Decimal points and
colons will be shown as hyphens. The display Note: This display supports IPv4 AND IPv6 addresses.
will automatically transition back to whatever mode it came from after displaying the IP address.
Breaker 2 Tripped
Breaker 3 Tripped
Note: Total of six breakers br1-br6
F C
F C
F C
I P I
16-01-031-933588.indb 17 3/22/2016 4:14:23 PM

18
5. Using the Digital Display
5.2 Navigating Config Menus and Submenus (Configuration)
While in any Display Menu, press and hold Mode button for 2 seconds to enter the first Config
menu. Press Mode button to cycle to the next Config menu. Press and hold Mode button for 2
seconds to switch to Display menus.
Temperature Unit Options
Hold Enter button for 2 seconds to switch
between options. The letter in the 2-digit
display indicates the selected unit, C for
Celsius and F for Fahrenheit.
Hold Enter button for 2 seconds to switch
between Source A and Source B. The letter in
the 2-digit display indicates the selected source.
Note: If both sources are available, the unit will
transfer to the preferred source immediately once the
setting is changed.
When enabled, the Auto Scroll function cycles
through the output load circuit currents
(C1, C2, C3) menus in 4-second intervals.
“y” indicates the function is enabled; “n”
indicates that it is disabled. Pressing any
button interrupts the auto scroll function,
allowing the user to navigate between menu
options. If no button is pressed, there is a 10
second timeout and auto scroll will resume
from the current menu.
Preferred Source Selection
Auto Scroll Enable/Disable
C – F
P S S
C – F
P S S
F
A
C
2 Seconds
2 Seconds
2 Seconds
16-01-031-933588.indb 18 3/22/2016 4:14:24 PM

19
5. Using the Digital Display
LED Brightness
Hold the Enter button for 2 seconds to scroll through each brightness option. The number in the
2-digit display is defined as: 1=25%; 2=50%; 3=75%; 4=100%.
Note: The default brightness option is 4 (100%).
LED Test
Hold Enter button for 2 seconds to start an
LED test. All LEDs will illuminate for 6 seconds.
Temperature Unit Options (Page 18)
4
i
2
3
2 Seconds
2 Seconds
2 Seconds
2 Seconds
8.8.8. 8 8
2 Seconds
16-01-031-933588.indb 19 3/22/2016 4:14:24 PM

20
6. Configuration and Operation
6.1 Automatic Transfer Switch
When the Source A and Source B inputs are both connected to power sources, the ATS operates
as an Automatic Transfer Switch, providing redundant input power for high availability applications.
The ATS will distribute power from the preferred input source under normal operating conditions
and switch to the other input source under abnormal conditions. The default preferred source is
Source A (Refer to the section for instructions on Navigating Config Menus and Submenus
changing the preferred source). The ATS will switch to the preferred source whenever it is “Good”
according to the ATS input voltage definitions (see section 6.1.2).
6.1.1 Preferred Configuration
The Automatic Transfer Switch function provides increased availability when the Source A and
Source B inputs of the ATS are connected to separate power sources. For maximum availability, it
is recommended when using UPS systems that the UPS systems are matching with pure sine wave
output for the Source A and Source B input power sources. The automatic transfer switch function
will be compromised if the Source A and Source B inputs are connected to the same utility power
source.
Source B
Power Source
Source B
Input Cord
Equipment
Loads
Source A
Input Cord
Source A
Power Source
Power Strip
Utility AUtility B
ATS
208V
~
/ L1 - L2
5 OUTPUT
BREAKER
16-01-031-933588.indb 20 3/22/2016 4:14:25 PM

21
6. Configuration and Operation
6.1.2 Automatic Transfer Switch Source Selection
The ATS will power up and supply output if at least one of the inputs is greater than the minimum
startup voltage. In normal operation, when both sources are of equal quality (“fair” or “good”), the
unit will select the preferred source according to the preferred source selection setting (Refer to
section 5.1 Navigating Config Menus and Submenus). If the currently selected source degrades
to a quality less than the currently unselected source, the unit will transfer to the better quality
source. If the currently unselected source improves in quality greater than the currently selected
source, the unit will transfer to the better quality source.
Note: In the event of a voltage loss on one of the 3-phase input conductors, the loads connected to the failed
phase conductor will transfer to the alternate source. The remaining load will follow and transfer to the alternate
source within 1 second. If both sources have mixed levels of stability in their phases, the ATS will select the
source of each phase on the basis of best available. If one of the sources has all 3 phases return to “good”
quality, the unit will then transfer all phases to that source.
Input Voltage Ranges
Nominal Voltage 208V
Minimum Startup Voltage 163V
Good Voltage Range 172-241V
Fair Voltage Range 144-171V
Bad Voltage Range 0-143V
6.1.3 Quick Test
After installing the ATS/power strip and connecting equipment, you
may test the Automatic Transfer Switch function by temporarily
disabling the preferred AC input (default is Source A). The ATS will
then switch from the preferred input to the alternate input. When
the preferred input resumes supplying power, the ATS will switch
back to the preferred input.
Note: The two inputs must be connected to separate sources of utility
power. The automatic transfer switch function will be compromised if the
two inputs are connected to the same power source. Do not perform a test
with equipment that must remain in productive operation. Any test
procedure must prepare for the contingency that the equipment may lose
power. Do not test the ATS by detaching power cords which are connected
to live power sources, as this eliminates the connection to ground and
places your equipment at risk.
Preferred Source (A) Active
Alternate Source (B) Active
16-01-031-933588.indb 21 3/22/2016 4:14:25 PM

22
7. Service
Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended
Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on
service, visit www.tripplite.com/support. Before returning your product for service, follow these steps:
1. Review the installation and operation procedures in this manual to ensure that the service
problem does not originate from a misreading of the instructions.
2. If the problem continues, do not contact or return the product to the dealer. Instead, visit
www.tripplite.com/support.
3. If the problem requires service, visit www.tripplite.com/support and click the Request Return
(RMA) link. From here you can request a Returned Material Authorization (RMA) number, which is
required for service. This simple on-line form will ask for your unit’s model and serial numbers,
along with other general purchaser information. The RMA number, along with shipping instructions
will be emailed to you. Any damages (direct, indirect, special or consequential) to the product
incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered
under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have
transportation charges prepaid. Mark the RMA number on the outside of the package. If the
product is within its warranty period, enclose a copy of your sales receipt. Return the product for
service using an insured carrier to the address given to you when you request the RMA.
LIMITED WARRANTY
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects
in material and workmanship for a period of 2 years from the date of initial purchase. If the product should prove
defective in material or workmanship within that period, Seller will repair or replace the product, at its sole
discretion. Service under this Warranty can only be obtained by your delivering or shipping the product (with all
shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609 USA. Seller will pay
return shipping charges. Visit www.tripplite.com/support before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE,
ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET
FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES,
INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY
PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL
DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions
may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from
jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate
or safe for the use intended. Since individual applications are subject to great variation, the manufacturer makes
no representation or warranty as to the suitability or fitness of these devices for any specific application.
8. Warranty and Product Registration
16-01-031-933588.indb 22 3/22/2016 4:14:26 PM

23
8. Warranty and Product Registration
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
PRODUCT REGISTRATION
Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into
a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense. The user must
use shielded cables and connectors with this product. Any changes or modifications to this product not expressly
approved by the party responsible for compliance could void the user's authority to operate the equipment.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been
assigned a unique series number. The series number can be found on the product nameplate label, along with all
required approval markings and information. When requesting compliance information for this product, always
refer to the series number. The series number should not be confused with the marketing name or model number
of the product.
WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)
Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations,
when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:
• Send old equipment for recycling on a one-for-one, like-for-like basis
(this varies depending on the country)
• Send the new equipment back for recycling when this ultimately becomes waste
Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
16-01-031-933588.indb 23 3/22/2016 4:14:26 PM

1. Instrucciones de Seguridad 25
Importantes
2. Instalación 26
2.1 Instalación del ATS 26
2.2 Instalación de la Barra 27
de Contactos
2.3 Conexión de la Barra 27
de Contactos al ATS
2.4 Conexión del ATS 28
2.5 Conexión a Red del ATS 28
3. Características 29
4. Pantalla Digital 31
5. Uso de la Pantalla Digital 34
5.1 Menúes de Pantalla 34
de Navegación y Sub Menúes
5.2 Menúes de Configuración 41
de Navegación y Sub Menúes
6 43. Configuración y Operación
6.1 Switch de Transferencia 43
Automática
7. Servicio 45
8. Garantía 46
English 1
Français 47
24
Manual del Propietario
PDU360AT6G60
(Número de Serie: AG-013D)
PDU Trifásico Monitoreable de 1U para Rack
con Switch de Transferencia Automática (ATS)
PDU3V602D354, PDU3V602D354A,
PDU3V602D354B
(Número de Serie: AG-013E)
Barra de Contactos Trifásica Vertical
1111 W. 35th Street, Chicago, IL 60609 EE UU • www.tripplite.com/support
Copyright © 2016 Tripp Lite. Todos los derechos reservados.
16-01-031-933588.indb 24 3/22/2016 4:14:26 PM

25
CONSERVE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse
durante la instalación, operación y almacenamiento de este producto.
La omisión en la observancia de estas instrucciones y advertencias
puede afectar la garantía del producto.
• La Barra de Contactos proporciona la conveniencia de múltiples tomacorrientes, pero NO
proporciona protección contra sobretensiones o ruido en la línea para los equipos conectados.
• Use solo con la Serie PDU3V60XXXXX de Tripp Lite con protección contra sobrecorriente. La
protección contra sobrecorriente por PDU consta de seis breakers de doble polo de 20A, 240V
CA (2 por fase).
• No exceda las siguientes especificaciones del equipo:
• La carga equilibrada total máxima para Salidas 1 y 2 es de 13.9A por banco cuando está
alimentado por un ATS (Switch de Transferencia Automática) trifásico con una entrada
especificada de 48A.
• El Switch de Transferencia Automática y la Barra de Contactos están diseñados solo para uso en
interiores en un entorno controlado lejos de humedad excesiva, temperaturas extremas,
contaminantes conductivos, polvo o luz del sol directa.
• Mantiene la temperatura ambiente interior entre 0° C y 45° C [32° F y 113° F].
• El Switch de Transferencia Automática y la Barra de Contactos deben ser instalados solamente
por un técnico calificado.
• No intente instalar el Switch de Transferencia Automática o la Barra de Contactos en una
superficie inestable o insegura.
• Instale conforme a los estándares de los código eléctricos locales. Asegúrese de usar para la
instalación la protección adecuada contra sobrecorriente, de acuerdo con la especificación de la
clavija o del equipo.
• Conecte el Switch de Transferencia Automática a un tomacorriente que esté de acuerdo a sus
códigos locales de construcción y que esté correctamente protegido contra corrientes excesivas,
cortocircuitos y fallas de conexión a tierra.
• Los tomacorrientes eléctricos que suministran energía al equipo deben instalarse cerca al
equipo y ser fácilmente accesibles.
• No conecte el Switch de Transferencia Automática a un toma corriente que no esté a tierra o
cables de extensión o adaptadores que eliminen la conexión a tierra.
• Asegúrese de proporcionar un dispositivo local de desconexión, que sea fácilmente accesible, en
cualquier modelo que esté instalado permanentemente sin una clavija.
• Nunca intente instalar equipos eléctricos durante una tormenta eléctrica.
• El equipo individual conectado a la Barra de Contactos no debe consumir más corriente que la
de la especificación de cada tomacorriente individual.
• La carga total conectada a la Barra de Contactos no debe exceder la capacidad de carga
máxima del Switch de Transferencia Automática.
• No intente modificar las clavijas o cables de alimentación del Switch de Transferencia
Automática o de la Barra de Contactos.
• No perfore ni intente abrir ninguna parte del gabinete del Switch de Transferencia Automática o
de la Barra de Contactos. No tiene partes a las que el usuario pueda dar servicio.
• No intente usar el Switch de Transferencia Automática o la Barra de Contactos si se daña
cualquier parte.
• No se recomienda el uso de este equipo en aplicaciones de soporte de vida en donde la falla de
este equipo pueda consecuentemente causar la falla del equipo de soporte de vida o afectar
significativamente su seguridad o efectividad. No use este equipo en presencia de una mezcla
inflamable de anestésicos con aire, oxígeno u óxido nitroso.
1. Instrucciones de Seguridad Importantes
16-01-031-933588.indb 25 3/22/2016 4:14:26 PM

26
2.1 instalación del Switch de Transferencia Automática (ATS)
instale su equipo es un rack o gabinete de rack de 4 postes. Antes de la instalación, el usuario
debe determinar la adecuación de los accesorios y procedimientos. Si los accesorios y
procedimientos no son adecuados para su aplicación, póngase en contacto con el fabricante de su
rack o gabinete. Los procedimientos descritos en este manual son para tipos comunes de racks y
gabinetes y pueden no ser apropiados para todas las aplicaciones.
Nota: Cada conjunto de riel lateral de broche consta de un soporte de instalación de gabinete y un riel de canal
interno. Para facilidad de instalación, los rieles de canal internos vienen preinstalados en la unidad del ATS.
2. Instalación
1 Alinee las pestañas del soporte posterior
con lo orificios cuadrados de instalación del
gabinete 1A y empuje los ganchos metálicos
a través de los orificios de instalación 1B.
Empuje el soporte posterior hacia el poste
del soporte del gabinete para que las
pestañas azules encajen firmemente en el
soporte 1A. Alinee las pestañas frontales del
soporte con lo orificios cuadrados de
instalación del frente del gabinete y empuje
los ganchos metálicos a través de los
orificios de instalación. Finalmente, empuje
el soporte frontal hacia el poste del soporte
del gabinete para que las pestañas azules
encajen firmemente en el soporte 1B.
2 Repita el paso uno para el segundo soporte
de instalación en el lado opuesto del
gabinete.
3 Una vez fijos ambos soportes de instalación
en el gabinete, asegure los soportes
posteriores usando los tornillos M5X10L
incluidos.
4 Alinee los rieles de canal internos acoplados
al ATS con los soportes de instalación.
Deslice entonces la unidad en el conjunto
de riel. Usando un desatornillador, fije los
tornillos de instalados en el panel del ATS al
gabinete.
1A
1B
3
4
16-01-031-933588.indb 26 3/22/2016 4:14:27 PM

27
2.2 Instalación de la Barra de Contactos
Nota: Las barras de contactos requieren un ancho
de instalación de 4" dentro del rack. Para instalación
sin herramienta, los botones de instalación vienen
preinstalados en la barra de contactos. Un segundo
juego de orificios para instalación por botón en la
barra de contactos permite otras ubicaciones en el
rack.
Coloque la barra de contactos como desee
dentro del gabinete, alinee los botones con las
ranuras de instalación del rack y deslice la
barra de contactos hacia abajo a su posición.
Su modelo puede variar ligeramente del de la imagen.
2. Instalación
2.3 Conexión de la Barra de Contactos al ATS
La barra de contactos tiene dos clavijas de 8
conductores. Cada cable está etiquetado
como Output 1 y Output 2. El cable etiquetado
Output 1 debe conectarse al tomacorriente
Output 1 del ATS; El cable etiquetado Output
2 debe conectarse al tomacorriente Output 2
del ATS.
La barra de contactos tiene además un cable
de detección de circuito de 6 conductores que
requiere conexión de la barra de contactos a
la unidad ATS.
Su modelo puede variar ligeramente del de la imagen.
16-01-031-933588.indb 27 3/22/2016 4:14:28 PM

28
2. Instalación
2.4 Conexión del ATS
2.4.1 Conexión de las Clavijas de
Entrada del ATS
Nota: El ATS viene equipado con dos alimentaciones
trifásicas de CA: Fuente A y Fuente B. Fuente A es la
fuente preferida (primaria) predeterminada. Para
instrucciones sobre el cambio de la fuente preferida,
consulte la sección 5.2 Menúes de Configuración
de Navegación y Sub Menúes. Las instrucciones de
conexión siguientes asumen que la Fuente A es la
fuente preferida.
Conecte la clavija de alimentación de la
Fuente A A a una fuente de alimentación
trifásica de CA preferida. Bajo condiciones de
operación normales, el ATS distribuirá la
alimentación de CA desde la fuente de entrada
de la Fuente A. Conecte la clavija de
alimentación de la Fuente B B a una fuente
alternativa de energía de CA con conexión a
tierra. No enchufe la entrada de la Fuente B
en la misma fuente de alimentación que la
entrada de la Fuente A. El ATS distribuirá la
alimentación de CA desde la entrada de la
Fuente B solo si la entrada de la Fuente A no
está disponible o es inestable.
2.4.2 Conexión del Equipo
a la Barra de Contactos
No exceda el valor nominal de carga de la barra
de contactos. La corriente eléctrica total
utilizada por cada fase de la barra de contactos
aparecerá en el medidor digital en amperes.
2.5 Conexión a Red del ATS
El ATS proporciona monitoreo remoto y más mediante un navegador de red, telnet y sistemas de
administración de red basados en SNMP.
Su ATS puede recibir la asignación de su dirección IP mediante los métodos de direccionamiento
del servidor DHCP (dinámico) o estático (manual). Si no está seguro de cuál método usar, póngase
en contacto con su administrador de red para asistencia antes de continuar el proceso de
configuración.
Para obtener más información sobre la configuración y operación del ATS mediante la interfaz del
navegador de red PowerAlert ®, consulte la Guía del Usuario de SNMPWEBCARD visitando
www.tripplite.com/support/SNMPWEBWARD.
Nota: La dirección MAC (una serie de 12 dígitos en el formato: 000667xxxxxx) está impresa en una etiqueta y
pegada al gabinete del ATS. Para la asignación estática de la dirección IP, use el cable de configuración DB9
(73102) incluido con el ATS.
A
B
16-01-031-933588.indb 28 3/22/2016 4:14:28 PM

29
3. Características
ATS Switch de Transferencia Automática
(PDU360AT6G60)
Barra de Contactos (PDU3V602D354, PDU3V602D354A, PDU3V602D354B)
1 Tomacorrientes de la Barra de Contactos: Estos tomacorrientes IEC C13 y C19
monofásicos reciben energía de las conexiones de alimentación trifásica de la Fuente A o la
Fuente B del ATS. Estos tomacorrientes no son controlables.
2 Cable de Alimentación de la Barra de Contactos: El cable
de 7 conductores tiene un conector de 8 posiciones que se
acopla directamente al ATS.
3 Entrada de la Fuente A y la Fuente B del ATS: Los cables
están acoplados permanentemente al ATS y tienen clavijas
IEC 309 60A Azul (3P + T).
4 Pantalla Digital: Muestra el estado de la fuente, valores
medidos, modos de pantalla y otra información. Consulte la
sección de para explicación detallada de los Pantalla Digital
indicadores y pantallas.
5 Botón de Restaurar SNMP: Para reiniciar la tarjeta de red
del ATS, oprima por 3 segundos el botón de restaurar.
Reiniciar la tarjeta de red no borrará los parámetros de red o
interrumpirá la alimentación de CA. El botón de restauración
está hundido. Use un clip para papel u otro objeto adecuado
para oprimirlo.
* Se muestra el modelo PDU3V602D354B. El aspecto puede variar según el modelo.
386 7
5
11 11 12
10
4
102 9 9
1
IEC 309 60A Blue (3P + E)
16-01-031-933588.indb 29 3/22/2016 4:14:30 PM

30
3. Características
6 Interfaz de Red: Use el conector RJ-45 para conectar el ATS a la red con
un cable patch Ethernet estándar. El LED de Estado A y el LED de Liga B
indican condiciones de operación, como se muestra en la siguiente tabla.
Estos puertos no son compatibles con aplicaciones de PoE (Energía sobre
la Ethernet).
Condiciones de operación de la red
A Color del LED de Estado B Color del LED de Liga
Apagado Tarjeta no inicializada Sin conexión de redApagado
Verde permanente Tarjeta inicializada y
operativa
Destellando en
ámbar
Conexión de red de 100
Mbps
Destellando en
ámbar Error - Tarjeta no inicializada Destellando en verde Conexión de red de 10 Mbps
7 Puerto de Configuración: Use este puerto para proporcionar una conexión directa de
terminal a una computadora con un programa de emulación de terminal. Con el ATS se
incluye un cable serial. Si necesita ordenar un cable de repuesto, comuníquese con el
Soporte al cliente de Tripp Lite al www.tripplite.com/support.
8 Puerto ENVIROSENSE: Use este puerto para conectar un sensor ambiental ENVIROSENSE
de Tripp Lite para proporcionar un monitoreo remoto de temperatura/humedad y una interfaz
de contacto seco para controlar y monitorear dispositivos de alarma, seguridad y
telecomunicaciones. Para información de pedidos, visite www.tripplite.com.
Nota: No conecte un teclado o mouse a este puerto.
9 Breaker: Cada carga de salida monofásica (seis bancos de carga de salida) tiene su propio
breaker magnético de doble polo. Si la carga del equipo conectado excede la Especificación
Máxima de Carga para esa fase, el breaker se disparará. Desconecte el equipo excesivo antes
de restaurar el(los) breaker(es).
10 Tornillo de Conexión a Tierra: Úselo para conectar cualquier equipo que requiera una
conexión de tierra a chasís.
11 Receptáculo de Concordancia de ATS: Este receptáculo acepta solamente el conector de
8 posiciones en el cable de alimentación de la barra de contactos.
Nota: El tomacorriente etiquetado Output 1 en el ATS debe coincidir con el cable Output 1 de la barra de
contactos y el etiquetado Output 2 en el ATS debe coincidir con el cable Output 2 de la barra de
contactos.
12 Detección del Breaker: El cable de seis posiciones de la barra de contactos se conecta al
ATS y permite al ATS detectar el estado de ENCENDIDO / APAGADO de los breakers de la
barra de contactos.
A B
16-01-031-933588.indb 30 3/22/2016 4:14:30 PM

31
4. Pantalla Digital
1 LEDs de Estado de la Fuente: Los patrones de los LEDs encendidos indican qué fuente es
preferida, qué fuente está disponible para uso y qué fuente se está usando actualmente.
Consulte la sección de para una explicación de Indicadores LED del Estado de la Fuente
los patrones de los LEDs.
2 LED de Disparo del Breaker: Encendido cuando se ha disparado un breaker.
3 Pantalla de 3 Dígitos: Muestra los valores medidos o calculados Amperaje, Kilowatts, Voltaje,
Porcentaje de Desbalanceo de Potencia, Frecuencia, Factor de Potencia y Temperatura.
4 Botón Enter: Cuando se ha seleccionado un menú usando el Botón de Modo, el Botón Enter
se desplaza a través de los Sub Menúes dentro de cada categoría. Los Sub Menúes son
mostrados por los LEDs indicadores.
Nota: Oprimir simultáneamente los botones Enter y Mode por 2 segundos muestra la dirección IP.
5 LEDs Indicadores: El LED encendido indica qué valor se está mostrando en la pantalla de
3 dígitos.
Amperes (A): La corriente de entrada en la entrada de la Fuente seleccionada (A# o b#) o
en el circuito de Carga de Salida (C#) se muestra en Amperes.
Potencia (kW): La Potencia de Salida para el Circuito Seleccionado de Carga de Salida (C#)
o la Potencia Total de Salida (OP) se muestra en kW.
Voltaje (V): El voltaje de fase a fase de alimentación de la Fuente A o B (A# o b#) o del
Circuito de la Carga de Salida (C#) se muestra en Volts.
Frecuencia (Hz): La frecuencia de la Entrada de la Fuente A o B se muestra en Hz.
Factor de Potencia (PF): El factor de Potencia de la Carga de Salida se muestra como
decimal (de 0 a 1.00).
1 742
3 5 6
16-01-031-933588.indb 31 3/22/2016 4:14:30 PM

32
4. Pantalla Digital
6 Pantalla de 2 Dígitos: Esta pantalla indica qué modo de pantalla está seleccionado:
Fase de Entrada de Fuente (A# o b#), % Desbalanceo (Ub), Circuitos de Salida (C#),
Potencia Total de Salida (OP), Temperatura (tC o tF), o Código de Falla (FC).
Fases de Fuente A (A#): Muestra las mediciones en pantalla para Fuente A. Incluyen
corriente de Fase (A), Voltaje (V) y Frecuencia (Hz).
Fases de Fuente B (B#): Muestra las mediciones en pantalla para Fuente B. Incluyen
corriente de Fase (B), Voltaje (V) y Frecuencia (Hz).
% Desbalanceo (Ub): La pantalla muestra la desviación en porcentaje de desbalanceo de
carga del valor promedio medido. Se muestra el porcentaje para la fase con la mayor
desviación.
Circuitos de Salida (C#): Muestra mediciones para el Circuito de Salida. Incluyen
Corriente (A), Kilowatts (kW), Voltaje (V) y Factor de Potencia (PF).
Potencia Total de Salida (OP): Muestra la potencia total en todos los circuitos de salida.
Temperatura (t): La temperatura ambiente se muestra al seleccionar la opción. Se muestra
la temperatura en Celsius en forma predeterminada, pero puede cambiarse a Fahrenheit.
Código de Falla (FC): El Código de Falla se mostrará solamente si se ha disparado el
breaker.
7 Botón de Modo: Usando este botón, desplácese entre los menúes de Pantalla y
Configuración. La elección de menú de pantalla se muestra en la pantalla de 2 dígitos.
La elección de menú de configuración se muestra en la pantalla de 3 dígitos.
16-01-031-933588.indb 32 3/22/2016 4:14:30 PM

34
5. Uso de la Pantalla Digital
5.1 Menúes de Pantalla de Navegación y Sub Menúes
(Medición)
Oprima el botón MODE para ir al siguiente menú de pantalla. Oprima el botón Enter para ir al
siguiente sub menú (Amperes, kW, Volts, Hz, PF). Oprima y sostenga por 2 segundos el botón
MODE para cambiar al primer menú de Configuración (Consulte la sección Menúes de
Configuración de Navegación y Sub Menúes). Oprima y sostenga los botones MODE y Enter
durante 2 segundos para mostrar la dirección IP de la tarjeta SNMP conectada. El patrón de
cambio de los menúes se describe a continuación.
Fuente A
Corriente de Fase (L1)
Volts (L1-L2)
Hz (L1-L2)
Nota: Ya que este es un modelo de 208V, los
voltajes mostrados son voltajes de fase a fase
(e.g., A1 en pantalla indica voltaje entre
L1-L2).
i 3.2.
2.0.8
6.0
A i
A i
A i
16-01-031-933588.indb 34 3/22/2016 4:14:31 PM

35
5. Uso de la Pantalla Digital
Volts (L2-L3)
Volts (L3-L1)
Hz (L2-L3)
Hz (L3-L1)
Fuente A
Corriente de Fase (L2)
Fuente A
Corriente de Fase (L3)
i 3.2.
i 3.2.
2.0.8
2.0.8
6.0
6.0
A2
A3
A2
A3
A2
A3
16-01-031-933588.indb 35 3/22/2016 4:14:31 PM

36
5. Uso de la Pantalla Digital
Volts (L1-L2)
Volts (L2-L3)
Hz (L1-L2)
Hz (L2-L3)
Fuente B
Corriente de Fase (L1)
Fuente B
Corriente de Fase (L2)
i 3.2.
i 3.2.
2.0.8
2.0.8
6.0
6.0
16-01-031-933588.indb 36 3/22/2016 4:14:32 PM

37
5. Uso de la Pantalla Digital
Volts (L3-L1)
Hz (L3-L1)
Kilowatts (L1-L2)
Fuente B
Corriente de Fase (L3)
Detección de Desbalanceo de Carga
Desbalanceo de Fase %
Circuito de Carga de Salida
Corriente de Circuito (L1-L2)
i 3.2.
2.0.8
6.0
i 0.0
i 3.2
2.7 5
C i
C i
16-01-031-933588.indb 37 3/22/2016 4:14:33 PM

38
5. Uso de la Pantalla Digital
Voltaje (L1-L2)
Voltaje (L2-L3)
Factor de Potencia (L1-L2)
Factor de Potencia (L2-L3)
Corriente de Circuito (L1-L2) (Pág. 37)
Circuito de Carga de Salida
Corriente de Circuito (L2-L3)
Kilowatts (L2-L3)
2 0 8
2 0 8
i.0 0
i.0 0
C i
C 2
C i
C 2
i 3.2
2.7 5
C 2
C 2
16-01-031-933588.indb 38 3/22/2016 4:14:33 PM

40
5. Uso de la Pantalla Digital
Menú de Código de Falla
El Menú de Código de Falla está disponible solamente cuando se dispara un breaker, causando
que se encienda el LED de disparo del breaker. La pantalla saltará al menú de código de falla y
cambiará automáticamente a través de los breakers disparados (solo se mostrarán breakers
disparados en la secuencia de cambio de menú). La opción de desplazamiento manual de menú
aún está disponible, pero la característica de desplazamiento automático de menú permanecerá
activa dentro del menú de código de falla mientras exista una falla. Si el desplazamiento
automático de menú está desactivado, la pantalla cambiará aún al menú de falla, pero usted debe
desplazarse manualmente a través de cada breaker disparado en forma individual. El número en la
pantalla de 3 dígitos se define como:
br1 = Breaker de Salida L1-L2; br2 = Breaker de Salida L2-L3; br3 = Breaker de Salida L3-L1
Breaker 1 Disparado
Pantalla de Dirección IP
En cualquier momento, puede oprimir y sostener los botones de Mode y Enter durante 2 segundos
para mostrar la dirección IP de la tarjeta SNMP conectada. La pantalla de 3 dígitos mostrará “IP“.
La pantalla de 2 dígitos a la derecha mostrará un dígito de la dirección IP a la vez hasta mostrar
toda la dirección IP. Los puntos decimales y comas se mostrarán como guiones. Nota: Esta
pantalla soporta direcciones IPv4 e IPv6. Después de mostrar la dirección IP, la pantalla regresará
automáticamente a cualquier modo que en el que estuviera antes.
Breaker 2 Disparado
Breaker 3 Disparado
F C
F C
F C
I P I
16-01-031-933588.indb 40 3/22/2016 4:14:34 PM

41
5. Uso de la Pantalla Digital
5.2 Menúes de Configuración de Navegación y Sub Menúes
(Configuración)
Estando en cualquier menú de pantalla, oprima y sostenga el botón de Modo por 2 segundos para
ingresar al primer menú de configuración. Para cambiar al siguiente menú de configuración, oprima
el botón de Modo. Oprima y sostenga por 2 segundos el botón de Modo para cambiar a los
menúes de Pantalla.
Opciones de Temperatura de Unidad
Sostenga el botón Enter por 2 segundos para
cambiar entre opciones. La letra en la pantalla
de 2 dígitos indica la unidad seleccionada, C
para Celsius y F para Fahrenheit.
Sostenga el botón Enter por 2 segundos para
cambiar entre la Fuente A y la Fuente B. La
letra en la pantalla de 2 dígitos indica la
fuente seleccionada.
Nota: Si ambas fuentes están disponibles, la unidad
se transferirá inmediatamente a la fuente preferida,
una vez cambiado el parámetro.
Cuando está activada, la función de
desplazamiento automático de menú cambia a
través de los menúes de corrientes del circuito
de carga de salida (C1, C2, C3) en intervalos
de 4 segundos. “y” indica que la función está
activada; “n” indica que está desactivada.
Oprimir cualquier botón interrumpe la función
de desplazamiento automático del menú,
permitiendo al usuario navegar entre las
opciones del menú. Si ningún botón se
oprime, hay un lapso de vencimiento de 10
segundos y se reiniciará el desplazamiento
automático de los menúes desde el menú
actual.
Selección de Fuente Preferida
Activar/Desactivar Desplazamiento Automático de Pantalla
C – F
P S S
C – F
P S S
F
A
C
2 Segundos
2 Segundos
2 Segundos
16-01-031-933588.indb 41 3/22/2016 4:14:35 PM
Produktspecifikationer
Varumärke: | Tripp Lite |
Kategori: | Elskena |
Modell: | PDU3V602D354B |
Behöver du hjälp?
Om du behöver hjälp med Tripp Lite PDU3V602D354B ställ en fråga nedan och andra användare kommer att svara dig
Elskena Tripp Lite Manualer

22 September 2024

14 September 2024

14 September 2024

8 September 2024

3 September 2024

31 Augusti 2024

30 Augusti 2024

29 Augusti 2024

28 Augusti 2024

28 Augusti 2024
Elskena Manualer
- Elskena Apc
- Elskena Icy Box
- Elskena Brennenstuhl
- Elskena Nedis
- Elskena Eglo
- Elskena Caliber
- Elskena Yato
- Elskena Eminent
- Elskena Vivanco
- Elskena DataVideo
- Elskena Energenie
- Elskena Hama
- Elskena GoGEN
- Elskena Steren
- Elskena Digitus
- Elskena Ufesa
- Elskena Sven
- Elskena Konig
- Elskena Ubiquiti Networks
- Elskena Eaton
- Elskena CyberPower
- Elskena Ewent
- Elskena HQ
- Elskena ATen
- Elskena Kindermann
- Elskena REV
- Elskena Lanberg
- Elskena Anton/Bauer
- Elskena StarTech.com
- Elskena Oregon Scientific
- Elskena Intellinet
- Elskena Kopp
- Elskena Furman
- Elskena Legrand
- Elskena Panduit
- Elskena EVOline
- Elskena V7
- Elskena Bachmann
- Elskena Oehlbach
- Elskena Kondator
- Elskena Geist
- Elskena Salicru
- Elskena Bauhn
- Elskena Adam Hall
- Elskena Panamax
- Elskena Altronix
- Elskena Middle Atlantic
- Elskena Tecnoware
- Elskena Huslog
Nyaste Elskena Manualer

14 Januari 2025

8 Januari 2025

1 Januari 2025

29 December 2024

25 December 2024

7 December 2024

7 December 2024

7 December 2024

7 December 2024

7 December 2024