Tripp Lite PDU3VSR6L1530 Bruksanvisning
Tripp Lite
Elskena
PDU3VSR6L1530
Läs nedan 📖 manual på svenska för Tripp Lite PDU3VSR6L1530 (72 sidor) i kategorin Elskena. Denna guide var användbar för 7 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare
Sida 1/72
1
Owner’s Manual
3-Phase Switched 0U Power
Distribution Units
(Phase, Bank and Outlet Measurements)
208V MODELS
PDU3VSR6L2120 • PDU3VSR6L2130 • PDU3VSR6H50
(Series Number: AG-00BC) (Series Number: AG-00BA) (Series Number: AG-00BA)
PDU3VSR6L1530 • PDU3VSR6G30
(Series Number: AG-00BA) (Series Number: AG-00BA)
400V MODELS
PDU3XVSR6G20
(Series Number: AG-00BD)
Important Safety Instructions 2
Installation 3
Digital Display 6
Using the Digital Display 8
Features 15
Configuration and Operation 17
Service 17
Warranty and Warranty 18
Registration
Español 19
Français 37
Русский 55
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2014 Tripp Lite. All rights reserved.
14-04-275-9332F8.indb 1 4/30/2014 4:29:16 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during
the installation, operation, and storage of this product. Failure to heed these
instructions and warnings may affect the product warranty.
• The PDU provides convenient multiple outlets, but it DOES NOT provide surge or line noise
protection for connected equipment.
• The PDU is designed for indoor use only in a controlled environment away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
• The power requirement for each piece of equipment connected to the PDU must not exceed
the individual outlet’s load rating.
• The total power requirement for equipment connected to the PDU must not exceed the
maximum load rating for the PDU.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
• Do not attempt to modify the PDU, including the input plugs and power cables.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to signicantly
affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a ammable anesthetic mixture with air, oxygen or nitrous oxide.
• Never attempt to install electrical equipment during a thunderstorm.
• Keep indoor ambient temperature between 32°F and 122°F (0°C and 50°C).
• Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
• The PDU must be installed by a qualied technician only.
• Install in accordance with National Electrical Codes. Be sure to use the proper over current
protection for the installation, in accordance with the plug rating/equipment rating.
• The electrical sockets supplying power to the equipment shall be installed near the equipment
and be easily accessible.
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
14-04-275-9332F8.indb 2 4/30/2014 4:29:16 PM
1-1 1-2
1-4
1-3
1-5
A
B
3
Installation
Mounting the PDU
Note: The illustrations may differ somewhat from your PDU model. Regardless of configuration, the user must
determine the fitness of hardware and procedures before mounting. The PDU and included hardware are designed
for common rack and rack enclosure types and may not be appropriate for all applications. Exact mounting
configurations may vary. Screws for attaching the mounting brackets to the PDU are included. Use only the screws
supplied by the manufacturer or their exact equivalent.
Note: Mounting buttons come preinstalled to the PDU for toolless mounting.
1-1 To attach the mounting brackets to the
PDU, remove the mounting buttons.
1-2 Attach the mounting brackets to the
PDU with the included screws.
1-3 Attach the PDU to a vertical rail in
your rack or rack enclosure. (Use the
mounting hardware that came with your
rack or rack enclosure to attach the
mounting brackets to the rail.)
1-4 To reinstall the mounting buttons for
toolless mounting, remove the mounting
brackets then install the mounting
buttons onto the PDU. Position the PDU
as desired in the rack enclosure, align
the buttons with the rack mounting
slots, and slide the PDU into position.
Note: Be sure to insert the 2 buttons into either
the upper hole at of the PDU or into each end
the lower hole at of the PDU.each end
1-5 To install the PDU with its outlets facing
the rear of the rack, use the included
PDUMVROTATEBRKT accessory. First,
attach the mounting button A to the
V-shaped bracket B using the included
screw and washer. Then, use the
button-mount slot to attach the bracket
to the PDU and the mounting button to
attach the PDU to the rack. The bracket
effectively repositions the mounting
brackets allowing for the PDU outlets to
face the rear of the rack.
14-04-275-9332F8.indb 3 4/30/2014 4:29:18 PM
Produktspecifikationer
Varumärke: | Tripp Lite |
Kategori: | Elskena |
Modell: | PDU3VSR6L1530 |
Behöver du hjälp?
Om du behöver hjälp med Tripp Lite PDU3VSR6L1530 ställ en fråga nedan och andra användare kommer att svara dig
Elskena Tripp Lite Manualer
22 September 2024
14 September 2024
14 September 2024
28 Augusti 2024
28 Augusti 2024
26 Augusti 2024
17 Augusti 2024
15 Augusti 2024
13 Augusti 2024
11 Augusti 2024
Elskena Manualer
- Elskena Apc
- Elskena Brennenstuhl
- Elskena Nedis
- Elskena Caliber
- Elskena Eminent
- Elskena DataVideo
- Elskena Energenie
- Elskena Hama
- Elskena GoGEN
- Elskena Steren
- Elskena Ufesa
- Elskena Konig
- Elskena Eaton
- Elskena CyberPower
- Elskena Ewent
- Elskena HQ
- Elskena ATen
- Elskena Kindermann
- Elskena StarTech.com
- Elskena Oregon Scientific
- Elskena Kopp
- Elskena Furman
- Elskena Legrand
- Elskena Panduit
- Elskena V7
- Elskena Bachmann
- Elskena Kondator
- Elskena Geist
- Elskena Salicru
- Elskena Bauhn
- Elskena Adam Hall
- Elskena Panamax
- Elskena Altronix
- Elskena Middle Atlantic
- Elskena Tecnoware
Nyaste Elskena Manualer
15 Oktober 2024
15 Oktober 2024
1 Oktober 2024
30 September 2024
29 September 2024
26 September 2024
26 September 2024
26 September 2024
24 September 2024
23 September 2024