Owner’s Manual
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed
during the installation, operation and storage of this product. Failure to
heed these instructions and warnings may affect the product warranty.
1
1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/support
Important Safety Instructions
• ThePDUprovidesconvenientmultipleoutletsbutitDOESNOTprovidesurgeorlinenoise
protectionforconnectedequipment.
• ThePDUisdesignedforindooruseonlyinacontrolledenvironmentawayfromexcessmoisture,
temperatureextremes,conductivecontaminants,dustordirectsunlight.
• DonotconnectthePDUtoanungroundedoutletorextensioncordsoradaptersthateliminatethe
connectiontoground.
• Useofthisequipmentinlifesupportapplicationswherefailureofthisequipmentcanreasonablybe
expectedtocausethefailureofthelifesupportequipmentortosignificantlyaffectitssafetyor
effectivenessisnotrecommended.Donotusethisequipmentinthepresenceofaflammable
anestheticmixturewithair,oxygenornitrousoxide.
• ThepowerrequirementforeachpieceofequipmentconnectedtothePDUmustnotexceedthe
individualoutlet'sloadrating.
• ThetotalpowerrequirementforequipmentconnectedtothePDUmustnotexceedthemaximum
loadratingforthePDU.
• DonotdrillintoorattempttoopenanypartofthePDUhousing.Therearenouser-serviceableparts
inside.
• DonotattempttomodifythePDU,includingtheinputplugsandpowercables.
• DonotattempttousethePDUifanypartofitbecomesdamaged.
• DonotattempttomountthePDUtoaninsecureorunstablesurface.
• Neverattempttoinstallelectricalequipmentduringathunderstorm.
Rack PDU
Metered Models: PDUMV15 and PDUMV20
Basic Models: PDUV15 and PDUV20
Español p. 5 Français p. 9
©2014TrippLite.Allrightsreserved.
14-02-334-933043.indd 1 3/26/2014 11:52:06 AM
2
1B
1A
3
4
5
PDUMV15 and
PDUV15
PDUV20 and PDUMV20
PDUV20 and PDUMV20
1C
3
2
Installation
1A
Zero U Rack Configuration.Attachthethreemountingclips
suppliedwiththePDUtotherackenclosureusingtheincluded
hardware.Themountingclipsshouldbeattachedalonga
verticalplaneatequidistantpointswhichroughlycorrespond
tothecenterandendsofthePDU.Theexactmounting
configurationmayvarydependingontherackandenclosure.If
possible,usepre-existingmountingpointswithinthe
enclosure.
1B
Wall or Under-Counter Configuration.Attachthethree
mountingclipssuppliedwiththePDUtoawallorsimilarflat,
securesurfaceusingtheincludedhardware.Themounting
clipsshouldbeattachedalongaverticalorhorizontalplaneat
equidistantpointswhichroughlycorrespondtothecenterand
endsofthePDU.Ifpossible,usepre-existingmountingpoints.
WARNING: Do not attempt to mount the PDU with the
outlets facing downward; the mounting clips are not
designed to support the weight of the PDU in that manner.
1C
Zero U Rack Configuration (Mounting Buttons). Attachthe
includedmountingbuttonstothePDU.PositionthePDUas
desiredintherackenclosure,alignthebuttonswiththerack
mountingslots,andslidethePDUintoposition.
Note: Regardless of configuration, the user must determine the
fitness of hardware and procedures before mounting. The PDU
and included hardware are designed for common rack and rack
enclosure types and may not be appropriate for all
applications.
2
Attach the PDU to the mounting clips.Usinganassistant,
placearearcornerofthePDUontheinsideedgeofthe
mountingclips,pivotthePDUtowardthealternateinsideedge
andsnapintoplace.
3
Attach the input plug of the PDU to a grounded outlet.
Inserttheplugdirectlyintoagroundedoutletthatdoesnot
shareacircuitwithaheavyelectricalload(suchasanair
conditionerorrefrigerator).
4
Attach equipment to the PDU.Donotexceedtheloadrating
ofthePDU.ThetotalelectricalcurrentusedbythePDUwill
bedisplayedonthedigitalmeterinamperes.
5
Optional Installation (Models PDUV20 & PDUMV20).The
PDUincludesanadapterthatconvertstheL5-20Pinputplug
toa5-20Pinputplug.Theadapterisoptional;thePDUwill
workproperlywithoutconnectingtheadapter.
14-02-334-933043.indd 2 3/26/2014 11:52:08 AM
1 2
7
5
8
4
6
3
3
Features
NEMA 5-15P Input Plug (Models PDUV15 & PDUMV15)
NEMA 5-15R Outlets (Models PDUV15 & PDUMV15)
NEMA L5-20P Input Plug (Models PDUV20 & PDUMV20)
NEMA 5-15/20R Outlets (Models PDUMV20 and PDUV20)
NEMA 5-20P Plug Adapter (Models PDUV20 & PDUMV20): Theadapterconvertstheinput
plugfromNEMAL5-20PtoNEMA5-20P.
Circuit Breaker: IfthecurrentdrawnbytheequipmentconnectedtothePDUexceeds
theMaximumLoadRating,thecircuitbreakerwilltriptopreventpossibledamage.Whenthe
circuitbreakertrips,itsplungerwillpopup.Disconnectexcessequipmentandallowthebreakerto
coolatleastoneminutebeforedepressingtheplungertoresetthebreaker.
Ammeter (Models PDUMV15 and PDUMV20 only): Thetotalelectricalcurrentusedbythe
PDUwillbedisplayedonthedigitalmeterinamperes.
Illuminated Power Switch with Cover (Models PDUMV15 and PDUMV20 only)
1
2
3
4
5
6
7
8
14-02-334-933043.indd 3 3/26/2014 11:52:09 AM