Sida 1/1
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com
49400436A0 04 1910
01976
Actuator with output 1-10 V d.c. 30 mA for driver LED control, relay
output 12-24 V 10 A, power supply 12-24 V~ 50-60 Hz, or 12-24 V
d.c., installation on DIN rail (60715 TH35), occupies 3 modules of
17.5 mm. Version for MARINE applications.
Actuator for driver LED with 1-10 V control. The device is controlled by a rocker
push-buttons. The device’s maximum output current is 30 mA.
CHARACTERISTICS.
• Rated supply voltage: BUS 29 V
• Input: 10 mA
• Auxiliary supply: 12-24 V~ ± 10% or 12-24 V d.c. ± 10% (SELV)
• Consumption:
- 12 V ~: 600 mA 12 V d.c.: 250 mA
- 24 V ~: 350 mA 24 V d.c.: 120 mA
• Dissipated power: 4 W
• Distance between actuator and LED driver: 10 m max with twisted cable
• Terminals:
- TP BUS
- 12-24 V~ 50-60 Hz, 12-24 V d.c.
- relay contacts (NO, C)
- control 1-10 V
• NO relay output
• Controllable loads at 12-24 V~ or 12-24 V d.c:
- resistive loads: 10 A (20.000 cycles)
- LED spot lights: 10 A (20.000 cycles)
• Operating temperature: -5 °C - +45 °C (for indoor use)
• 3 modules of 17.5 mm.
CONNECTIONS.
The wire diagram (bottom right) shows an example of a connection with an LED
driver. Depending on the type of LED driver used, the connection of terminal to +
the LED driver through the relay contacts integrated in device 01976 may not be
necessary; in this case, connect terminal directly to the electric phase.+
The feeding circuit of the relay output must be protected against overloads by a
fuse with rated current not higher than 12 A.
CONFIGURATION.
FOR DETAILS OF INSTALLATION AND CONFIGURATION, SEE THE By-me
SYSTEM INSTRUCTIONS MANUAL.
• Functional blocks: 1; the block can belong to at most 4 groups.
• Selecting the functional block (configuration), when the control unit, during group
creation, requires pressing the device button:
- press the configuration button, the red LED will light up;
- with the red LED on, the control unit will configure the functional block; at the end
of this operation the red LED will go out.
PARAMETERS.
• adjustment speed: low, medium or high;
• LED always off or on only with dimmer on;
• Parameter offset: minimum output voltage adjustable from 1 to 2 V (default value
1,2 V).
• Default parameters: dimmer actuator with medium adjustment speed, LED
always off and offset of minimum output voltage.
SCENARIOS.
The actuator can belong to up to 4 different scenarios and, for each scenario, save
the status to retrieve when activating the scenario.
INSTALLATION RULES.
Installation should be carried out by qualified personnel in compliance with the current
regulations regarding the installation of electrical equipment in the country where the
products are installed.
For further instructions, please refer to the manual enclosed with the control panel.
CONFORMITY TO STANDARDS.
EMC directive. Standards EN 50428, EN 50491.
For MARINE use, this device has been submitted to the following tests:
IEC 60068-2-52 - Test Kb: Salt mist, cyclic (sodium, chloride solution),
IEC 60068-2-6 - Test Fc: Vibration (sinusoidal)
ACTUATOR 1-10V
10 12-24VA
01976
12-24V 10 12-24VA
NO C
BUS
By-me CONF.
1-10V 30mA
FRONT VIEW AND CONNECTIONS.
Configuration Led.
Configuration button.
BUS lineConnection to
the LED driver
C
NO
12-24 V~
12-24 V dc
ACTUA R 1-10VTO
10A 12-24V
01976
12-24V 10A 12-24V
NO C
BUS
By-me CONF.
1-10V 30mA
+ -
LED Driver
LED
Lamp
FUSE
+
-
+
-
1-10 V
bus line
12-24 V
+ -
EXAMPLE OF CONNECTION.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must not
be included with other general waste at the end of its working life. The user must take the worn product
to a sorted waste center, or return it to the retailer when purchasing a new one. Products for disposal can
be consigned free of charge (without any new purchase obligation) to retailers with a sales area of at least
400 m2, if they measure less than 25 cm. An efficient sorted waste collection for the environmentally friendly
disposal of the used device, or its subsequent recycling, helps avoid the potential negative effects on the
environment and people’s health, and encourages the re-use and/or recycling of the construction materials.
This device complies with part 15 of the Rules (with the limits for a Class B FCC
digital device). Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause undesiderable
operation.
REACH (EU) Regulation no. 1907/2006 Art.33. The product may contain traces
of lead.