Installation 990-92234-001 1/2023
Galaxy VX Lithium-ion BMS Power Supply Kit
(GVXOPT002)
What’s in This Document
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................1
Safety Precautions .....................................................................................2
Electrical Safety....................................................................................5
Battery Safety.......................................................................................6
Torque Specifications .................................................................................7
Install the Lithium-ion BMS Power Supply Kit GVXOPT002 ................7
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar with
it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER will result inindicates a hazardous situation which, if not avoided,
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING could result inindicates a hazardous situation which, if not avoided,
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com
As standards, specifications, and design
change from time to time, please ask for
confirmation of the information given in this
publication.
© 2023 – 2023 . All rightsSchneider Electric
reserved.
Galaxy VX Lithium-ion BMS Power Supply Kit (GVXOPT002)
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
CAUTION
CAUTION could result inindicates a hazardous situation which, if not avoided,
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on this
UPS system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
2 990-92234-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS Galaxy VX Lithium-ion BMS Power Supply Kit (GVXOPT002)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free of
conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
990-92234-001 3
Produktspecifikationer
Varumärke: | Apc |
Kategori: | UPS |
Modell: | Galaxy VX GVXOPT002 |
Färg på produkten: | Zwart |
Vikt: | 8300 g |
Bredd: | 211.8 mm |
Djup: | 503.6 mm |
Höjd: | 549.6 mm |
Snäll: | PC |
Vormfaktor: | Full Tower |
Antal USB 2.0-portar: | 2 |
Inbyggda högtalare: | Nee |
Ljudingångar: | Ja |
Ljudutgång: | Ja |
Material: | SGCC |
Antal 2,5" fack: | 2 |
Antal 5,25" fack: | 3 |
Antal 3,5" fack: | 7 |
Hårddiskstorlekar som stöds: | 2.5, 3.5 " |
Antal expansionsplatser: | 7 |
Moderkortsformfaktorer som stöds: | ATX, Micro ATX |
Sidofönster: | Ja |
Maximal CPU-kylarhöjd: | 157 mm |
Maximal grafikkortslängd: | 400 mm |
Maximalt antal främre fläktar: | 1 |
Främre fläktar som stödjer diametrar: | 120 mm |
Maximalt antal fläktar överst: | 1 |
Toppfläktar som stöder diametrar: | 120 mm |
Max antal bakre fläktar: | 1 |
Bakre fläktar stödjer diametrar: | 120 mm |
Installerade bakre fläktar: | 1x 120 mm |
Antal främre fläktar installerade: | 1x 120 mm |
Maximalt antal sidofläktar: | 2 |
Sidofläktar som stödjer diametrar: | 120 mm |
Maximalt antal bottenfläktar: | 1 |
Bottenfläktar som stöder diametrar: | 120 mm |
Behöver du hjälp?
Om du behöver hjälp med Apc Galaxy VX GVXOPT002 ställ en fråga nedan och andra användare kommer att svara dig
UPS Apc Manualer
18 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
13 Oktober 2024
4 Oktober 2024
UPS Manualer
- UPS AEG
- UPS IKEA
- UPS HP
- UPS Siemens
- UPS LC-Power
- UPS Tripp Lite
- UPS Energenie
- UPS Voltcraft
- UPS Emerson
- UPS Adj
- UPS Digitus
- UPS LevelOne
- UPS Eaton
- UPS Jung
- UPS CyberPower
- UPS Block
- UPS Avocent
- UPS Minuteman
- UPS Maruson
- UPS V7
- UPS Salicru
- UPS Equip
- UPS Approx
- UPS SurgeX
- UPS Murr Elektronik
- UPS Altronix
- UPS Ditek
- UPS Bxterra
- UPS Middle Atlantic
- UPS FSP
- UPS Atlantis Land
- UPS PowerWalker
- UPS FSP/Fortron
- UPS Online USV
Nyaste UPS Manualer
24 Oktober 2024
22 Oktober 2024
22 Oktober 2024
22 Oktober 2024
20 Oktober 2024
18 Oktober 2024
11 Oktober 2024
9 Oktober 2024
9 Oktober 2024
6 Oktober 2024