Installation Guide APC Smart-UPS Ultra
External Battery Pack SRTL50RMBP1U-LI
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
installation and maintenance of the Smart-UPS and batteries.
Read the user documentation to become familiar with the equipment before trying to install or operate
it.
Read these instructions carefully and look at the equipment to become familiar with the device before trying to
install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol either to aDanger” or “Warning” safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid possible injury or death.
Product Handling Guidelines
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb
APC Smart-UPS Ultra External Battery Pack SRTL50RMBP1U-LI2
Safety and General Information
Connect only SELV circuits to all the communication ports.
The External Battery Pack (XLBP) typically lasts for 10 years. Environmental factors impact the life of the
battery module. Elevated ambient temperatures, poor quality utility power causing frequent short duration
discharges will shorten the life of the battery module.
Replace the XLBP immediately if the unit indicates battery replacement is necessary.
Replace the XLBP at least every 10 years or at the end of its service life, whichever is earlier.
The XLBP is user replaceable. If attempting to replace the XLBP:
Use only APC XLBPs.
Do not use third-party XLBPs as replacements.
APC Smart-UPS Ultra XLBP uses NMC chemistry Lithium Ion batteries. Under normal use and handling,
there is no contact with the internal components of the XLBP.
Do not drive nails into the XLBP.
Do not strike the XLBP with a hammer.
Do not stand on the XLBP.
Do not short circuit XLBP.
Do not place or use the XLBP near heat or fire.
Do not use a dropped, damaged or deformed XLBP.
Do not use the XLBP to power other equipment.
CAUTION: A battery can present a risk of electric shock and burns by high short-circuit current.
CAUTION: Before installing or replacing the XLBPs, remove conductive jewelry such as chains, wrist
watches and rings. High energy through conductive materials could cause severe burns.
CAUTION: Do not crush or dispose off the XLBP in a fire. The cells may explode.
CAUTION: Do not open or tamper with the XLBP enclosure. Doing so will expose the cell terminals which
pose an energy hazard.
CAUTION: Do not open the XLBP. Released chemical is harmful to the skin and eyes. It may be toxic.
CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
Package Contents
Inspect the contents upon receipt. Notify the carrier and dealer if there is damage.
External battery pack (XLBP). Ground cable
Flat head screws (8x) to secure the
rack-mount brackets and the
extensions for the stabilizer
brackets
Rail kit Extension for stabilizer
brackets.
Rack-mounting
brackets.
(8)
(10)(8) (2)
APC Smart-UPS Ultra External Battery Pack SRTL50RMBP1U-LI 3
Specifications
For additional specifications, refer to our web site, www.apc.com.
Environmental
Physical
Battery Module
Temperature Operating 0 to 40 °C (32 to 104 °F)
Storage -15 to 45 °C (5 to 113 °F)
Maximum
Elevation
Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non-condensing
International Protection Code IP20
NOTE:
Charge the XLBP immediately upon first installation.
Charge the XLBP at least once in 12 (twelve) months during storage.
Environmental factors impact battery life. Elevated ambient temperatures, high humidity, poor quality mains power
causing frequent short duration discharges, will shorten battery life.
The XLBP is heavy. Follow all lifting guidelines.
Unit weight without packaging (approx.) 19.50 kg (43 lbs)
Unit weight with packaging (approx.) 24.50 kg (54 lbs)
Unit dimensions without packaging
Height x Width x Depth
43 x 432 x 560 mm
(1.69 x 17.00 x 22.04 in.)
Unit dimensions with packaging
Height x Width x Depth
198 x 564 x 764 mm
(7.80 x 22.20 x 30.08 in.)
The model and serial numbers are on a small label located on the rear panel.
WARNING
RISK OF CHEMICAL HAZARD AND EXCESSIVE SMOKE
Replace the XLBP at least every 10 years or at the end of its service life, whichever is earlier.
Replace the XLBP immediately when the UPS indicates battery replacement is necessary.
Replace with the same type as originally installed in the equipment.
Failure to follow these instructions can result in death or serious injury.
Battery type Lithium-Ion
Number of battery modules 1
Voltage of each battery module 50.4 V
Total voltage of the XLBP 50.4 V
Ah rating 18.85 Ah
XLBP cable length 500 mm