Eltako FSR14M-2x Bruksanvisning

Läs nedan 📖 manual på svenska för Eltako FSR14M-2x (2 sidor) i kategorin Inte kategoriserad. Denna guide var användbar för 2 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/2
Impulse switch relay with 2 channels and
active power measurement. 1+1 NO contact
not potential free 16A/250V AC, 230V LED
lamps up to 600W, incandescent lamps 2000W.
Bidirectional. Only 0.9 watt standby loss.
Modular device for DIN-EN 60715 TH35 rail
mounting. 2 modules = 36 mm wide, 58 mm
deep.
Supply voltage 230 V.
Connection to the Eltako-RS485 bus. Bus
cross wiring and power supply with jumper.
The instantaneous power is measured sepa-
rately for each channel and transferred to the
bus - e.g. for transfer to an external computer
and also sent to the wireless network via the
FAM14.
The maximum current as a sum over both
contacts is 16A, so a fuse with a maximum
of 16A is required at L.
Contact switching in the zero crossing to
protect the contacts and the lamps.
If supply voltage fails, the switching state is
retained. When supply voltage is restored,
the device is switched off in de ned mode.
The channels can be taught-in as ES and/
or ER channel separately from each other.
Scene control:
Several channels of one or several FSR14M-2x
devices can be switched on or off in a scene
by one of the four signals of a pushbutton
with double rocker taught-in as a scene
button.
Central commands on PC are sent using the
RS485 bus actuator
2-channel impulse switch
FSR14M-2x
with active power measurement
GB
Temperature at mounting location:
-20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity:
annual average value <75%.
30 014 039 - 1
Only skilled electricians may install this
electrical equipment otherwise there is
the risk of re or electric shock!
Function rotary switches
Use the rotary switches to teach-in the
buttons and test the 2 channels as required.
For normal mode, the middle and lower rotary
switches are then set to AUTO. With the
upper rotary switch the EW time (0-120 sec-
onds) is directly set for relays or the RV time
(0-120 minutes) for impulse switches for all
channels if necessary.
When FBH wireless motion/brightness sen-
sors (masters) (EEP A5-08-01) are taught-in,
the switching threshold is de ned separately
for each channel using the upper rotary
switch. The switching threshold switches the
lighting on or off depending on the bright-
ness (in addition to motion) (from approx.
30 lux in position 0 to approx. 300 lux in
position 90).
If FBH devices (slaves) are taught-in in Posi-
tion 120, they are only evaluated as motion
detectors.
Several FBH devices are interlinked per
channel. If an FBH signals 'motion', the NO
contact closes. Only when all FBH devices
signal 'no motion' does the NO contact open
after the preset RV time. When an FBH is
taught-in, the RV time only applies to the FBH.
Press the ON side of a direction push-button
for 2 seconds to switch it on permanently.
Signals are not evaluated by the FBH.
Press the OFF side of a direction pushbutton
for 2 seconds to switch it off permanently.
Signals are not evaluated by the FBH.
Press the direction pushbutton brie y to
re-evaluate FBH signals.
Wireless Building Visualisation and Control
Software GFVS. To do this, teach-in one or
several FSR14M-2x devices.
Semiautomatic motion detection with
taught-in wireless motion sensor FB65B
factory setting (EEP A5-07-01): Press the
pushbutton to switch on. This starts a
release delay time of 5 minutes during
which the device switches on again if motion
is detected. When no further motion is de-
tected, the device switches off automati cally
after 5 minutes in addition to the set RV time.
The actuator then reacts to motion for a
further 5 minutes and may switch back on
automatically. After this time expires, the
device must be switched on again by press-
ing the pushbutton. You can switch the
device off at any time by pressing the push-
button. Motion is then no longer evaluated.
Fully automatic motion detection with
taught-in wireless motion sensor FB65B:
If the actuator is not to switch on automati-
cally when motion is detected, e. g. in rooms
without daylight, replug the jumper to 'active'
on the FB65B device. When no further motion
is detected, the device switches off automat-
ically after a release delay time of 5 minutes
in addition to the set RV time. Press the
push button at any time to switch the device
on or off. When motion is detected, the
device switches on again automatically.
When wireless brightness sensors
(EEP A5-06-01, -02, -03) are taught-in, de ne
the switching threshold separately for each
channel using the top rotary switch. The
switching threshold switches the lighting on
or off depending on the brightness (from
approx. 0 lux in positi on 0 to approx. 50 lux
or 900 lux in position 120). A hysteresis of
approx. 300 lux is permanently set for switch
on/off.
An additionally set RV time is not taken into
account.
Only one FBH master or FHD60SB (EEP A5-
06-01) is taught-in per channel. However, one
FBH (masters) or FHD60SB (EEP A5-06-01)
can be taught-in in several channels.
When wireless window/door contacts FTK
(EEP D2-00-01, F6-10-00, A5-14-01, -03, -09, -0A)
are taught-in, different functions can be set
with the middle rotary switch in position
AUTO 1 to AUTO 4 and linked to maximum 116
FTKs:
AUTO 1 = window closed then output active.
AUTO 2 = window open then output active.
In settings AUTO 3 and AUTO 4 the FTKs
taught-in to a single channel are linked auto-
matically. With AUTO 3 all FTKs must be
closed so that the N/O contact closes (e. g.
for climate control). With AUTO 4 one open
FTK is su cient to close the N/O contact
(e.g. for an alarm signal or to switch on the
power supply for an extractor hood).
One or several FTKs can be taught-in in
several channels to allow several simultane-
ous functions in each FTK.
After a power failure the link is restored by a
new signal to the FTK and a signal on the
next status message 15 minutes later.
An additionally set RV time is not taken into
account.
Vibration sensor (EEP A5-14-05):
If the upper rotary switch was set to position
5 during teach-in, the actuator works as a
two-point switch, with 'vibration' it is
switched on, with 'no vibration' it is switched
off.
If the upper rotary switch was set to position
10 during teach-in, it is switched on with
'Vibration' and automatically switched off
after the time that can be set between 2 and
120 seconds has elapsed. If the upper rotary
switch is set to 0, it is not switched off auto-
matically, but must be switched off manually.
When
FRW, FRWB, FHMB (EEP A5-30-03)
wireless smoke alarms are taught-in, they are
interlinked per channel. When an FRW signals
'smoke', the NO contact closes. Only after all
FRW devices signal 'no smoke' does the NO
contact open.
When eco water probes FWS81 (EEP F6-05-01)
or con
oor water probes (Art. No. 78142) are
taught-in with FTM wireless transmitter (Art.-
No. 78143) from AFRISO, a variety of functions
can be set using the middle rotary switch in
Positions AUTO 1 to AUTO 4.
AUTO 1 = 'no water', then NO contact closed.
AUTO 2 = 'water', then NO contact closed.
In Positions AUTO 3 and AUTO 4 the water
probes taught-in to a single channel are
interlinked automatically. With AUTO 3, all
water probes must signal 'no water' before
the NO contact closes. The NO contact opens
when a water probe signals 'water'.
With AUTO 4, the NO contact closes when a
water probe signals 'water'. Only when all
water probes signal 'no water' does the NO
contact open.
An additionally set RV time is ignored.
The LED below the upper function rotary
switch performs during the teach-in process
according to the operation manual. It shows
control commands by short  ickering during
operation.
Technical data
Rated switching capacity 16A/250V AC
each contact2)
230V LED lamps up to 600 W 3)
I on ≤ 120 A/5 ms
Incandescent lamp and 2000 W
halogen lamp load1) 230V
Fluorescent lamp load with KVG* 1000 VA
in lead-lag circuit or
non compensated
Fluorescent lamp load with KVG* 500 VA
shunt-compensated or with EVG*
Compact  uorescent lamps 15x7 W
with EVG* and 10x20 W
energy saving lamps
Standby loss 0,9 W
(active power)
1
) Applies to lamps of max. 150 W.
2) The maximum current as a sum over both contacts is
16A, so a fuse with a maximum of 16A is required at L.
3)
Due to different lamp electronics and depending on
the manufacturer, the maximum number of lamps
may be limited, especially if the wattage of the
individual lamps is very low (e.g. with 2 W LEDs).
* EVG = electronic ballast units;
KVG = conventional ballast units
Typical connection
L
N
BUS BUS
2
1
N
Hold
FAM14
BUSBUS
Teaching-in wireless sensors in
wireless actuators
All sensors must be taught-in in the
actuators so that they can detect and
execute commands.
Teaching-in actuator FSR14M-2x
The teach-in memory is clear on delivery
from the factory. To ensure that a device
was not previously taught-in, clear the
complete memory:
Turn the middle rotary switch to ALL (or to
CLR 1..2) if you only want to clear one
channel and also turn the lower rotary
switch to the required channel). The LED
ashes at a high rate. Within 10 seconds,
turn the upper rotary switch three times
to right stop (turn clockwise) and back
again.
The LED stops  ashing and goes out after
2 seconds. All taught-in sensors/ probes
or channel sensors/probes are cleared.
Clear individual taught-in sensors in the
same way as in the teach-in procedure,
except that you set the middle rotary
switch to CLR instead of LRN, and operate
the sensor. The LED previously  ashing at
a high rate goes out.
120 = teach in FBH (slave) and FRW;
3. Set the middle rotary switch to LRN.
The LED ashes at a low rate1.
4. Press the sensor to be taught-in.
The LED goes out.
For FTK, FB65B, vibration sensors and
water sensors, no teach-in position
needs to be observed for the upper rotary
switch.
For and rotary switches GFVS no teach-in
position needs to be observed. On teach-
in, the actuator automatically sends a
con rmation telegram when it receives a
device address and the upper rotary
switch on the FAM14 is turned to Pos. 2.
To teach-in further sensors, turn the
middle rotary switch brie y away from
position LRN. Continue the procedure
from pos 1.
A pushbutton (rocker end) can only
execute the same last taught-in function
of different channels of a FSR14M-2x.
Different pushbuttons can execute
different functions of one or more
channels of a FSR14M-2x.
After teaching-in, set the middle and
lower rotary switches to AUTO and turn
the upper function rotary switch to the
required time. For taught-in window/door
contacts FTK, note that the middle rotary
switch must be in the required setting
AUTO 1 to 4.
Teach in scenes
Up to 4 scenes are being saved with a
previously taught-in scene pushbutton.
1. All 2 channels of the impulse switch can be
turned on or off individually with a
previously taught-in universal-, direction-,
or central pushbutton as it is desired for
one scene.
2. The switch state is saved within 60 seconds
when you press one of the four rocker ends
of the doublerocker scene button for longer
than 3 seconds but shorter than 10 seconds.
3. If more scenes have to be saved return
back to point 1.
Recall scenes
Press one rocker of the scene pushbutton
brie y to recall the scene you require.
An additionally set RV time is not taken into
account.
When the middle rotary switch is set to
TEST, the 2 contacts can be closed individually
using the lower rotary switch:
TEST + AUTO = all contacts open,
TEST + 1 = contact 1 closed,
TEST + 2 = contact 2 closed,
TEST + 1..2 = all contacts closed.
Assign device address for the FSR14:
The rotary switch on the FAM14 is set to
position 1, its lower LED  ashes red. The
lower rotary switch of the FSR14 is set to 1..2.
The middle rotary switch of the FSR14 is set
to LRN, the LED  ashes smothly. After the
address of the FAM14 was assigned, its lower
LED  ashes green for 5 seconds and the LED
of the FSR14 goes out.
Delete device con guration:
Set the middle rotary switch to ALL. The LED
ashes nervously. Then turn the upper rotary
switch within 10 seconds 3 times to the left-
most stop (anticlockwise) and turn it back
again. The LED stops  ashing and goes out
after 5 seconds. The factory settings are
restored.
Delete device con guration and
device address:
Set the middle rotary switch to ALL. The LED
ashes nervously. Then turn the upper rotary
switch within 10 seconds 6 times to the left-
most stop (anticlockwise) and turn it back
again. The LED stops  ashing and goes out
after 5 seconds. The factory settings are
restored and the device address deleted.
Measurement of active power from 2W.
The performance data are sent per channel
according to EEP A5-12-01.
Send learning telegram (0x48080D80):
1. Select the desired channel 1 or 2 with the
lower rotary switch.
2. Turn the middle rotary switch to TEST, the
relevant contact closes and the teach-in
telegram is sent.
3. Turn the lower rotary switch back to AUTO,
the contact opens.
4.
Turn the middle rotary switch back to AUTO.
If necessary, also for the other channel.
The power data is sent immediately when
there is a change in power.
If there is no change, the power data is sent
cyclically every 60 seconds.
Con gure FSR14:
The following points can be con gured with
the PC tool PCT14:
ɀ behavior upon return of supply voltage
ɀ teaching-in of wireless pushbuttons and
wireless window handles with single or
double click
ɀ scenes for scene pushbuttons.
ɀ Switch-on and switch-off thresholds for
brightness sensors
ɀ add or change sensors
ɀ power measurement parameters
CAUTION! Don’t forget 'disconnect FAM' in
the PC tool. While the connection from the
PC tool to the FAM14 exists, no wire less
commands are executed.
Teach-in con rmation telegram of another
bus actuator to the FSR14:
As in the teach-in procedure, only set the
middle rotary switch to LRA instead to LRN.
Teach-in 'switch ON' as 'central control button
ON'. Teach-in 'switch OFF' as 'central control
button OFF'.
When an actuator is ready for
teach-in (the LED  ashes at a low
rate), the very next incoming signal
is taught-in. Therefore, make
absolutely sure that you do not
activate any other sensors during
the teach-in phase.
!
Must be kept for later use!
We recommend the housing for
operating instructions GBA14.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 943 500 25
technical-support@eltako.de
eltako.com
02/2023 Subject to change without notice.
Teaching-in sensors
1. Select the required Channel 1, 2 or 1..2
using the lower rotary switch.
2. Use the upper rotary switch to select the
required teach-in function.
0 = teach in 'direction button';
Rocker is completely taught-in automati-
cally when operating the pushbutton.
The side on which the pushbutton is rst
operated is de ned for switching on, the
other side for switching off.
5 = teach in 'universal button ES', 'Vibration
sensor';
10 = teach in 'universal button ER', 'vibration
sensor with time lapse';
15 = teach in 'central control button ON'
with priority;
20 = teach in 'central control button OFF'
with priority;
Central buttons have priority as long as
they are pressed.
30 = teach in 'scene button';
Scene buttons (double rocker) are taught-
in in fully automatic mode. 'Save scenes'
as described further on.
45 = teach in 'central control button ON';
90 = teach in 'central control button OFF';
Manuals and documents in further
languages
http://eltako.com/redirect/FSR14M-2x
1. App 2. 3.
www.

Produktspecifikationer

Varumärke: Eltako
Kategori: Inte kategoriserad
Modell: FSR14M-2x

Behöver du hjälp?

Om du behöver hjälp med Eltako FSR14M-2x ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad Eltako Manualer

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer