IFM E40211 Bruksanvisning

Läs nedan 📖 manual på svenska för IFM E40211 (3 sidor) i kategorin Inte kategoriserad. Denna guide var användbar för 2 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/3
Operating instructions
SC teach button
E40211
E40212
704653 / 00 05 / 2010
UK
2
1 Functions and features
E40211 Teach button for setting the SC flow sensors with PNP output
E40212 Teach button for setting the SC flow sensors with normally open relay
output
2 Electrical connection
1 2
1: Connector (socket) - connection to SC flow sensor
2: Connector (plug) - connection to supply voltage
E40211
SC E40211
4
1
3
2n.c.
L1
L+
N
L
n.c.
1
2
4
5
3
n.c.
E40212
L1
L+
N
L
SC E40212
4
1
3
2n.c.
n.c.
1
2
4
5
3
n.c. = not connected
3
UK
3 Switch point setting
Press button briefly and release it.
After 1 - 2 s press it again and keep it pressed for the time indicated.
> The flow sensor gives its output signals to the teach button. They are displayed
by the illuminated pushbutton:
Output closed (OUT = 1) button lights
Output closed (OUT = 0) button does not light
1...5> 1 3...67 5 5...65 5
A B D E FC
Button
OUT = 1
OUT = 0
Time window
Duration [s]
Within the time windows A, B, C the output is switched depending on the flow: output closed
(OUT = 1/ button lights) if flow SP / output open (OUT = 0 / button does not light) if flow < SP.
If flow rises or falls within the time windows A, B, C the switching status / display of the il-
luminated pushbutton can change.
In the time windows D, E, F the output is used for feedback signals (-> table below). It does
not react to flow changes.
Time window Operation
A Initialisation of the setting operation.
B Confirmation of the initialisation.
C Setting of the switch point (SP)*
Push of the button in s 5 10 15 20 ... 55 60 65
corresponds to SP in
cm/s min. 10 15 20 ... 55 60 max.
D The last switching status from C is maintained (= internal monitoring).
E Output signal is inverted (= confirmation of the setting);
duration = setting time of the selected switch point
F Output signal is inverted again (= internal monitoring), then this new switch
point is active.
* Accuracy: ± 1s
min.: flow < 10 cm/s; max.: flow > 60 cm/s

Produktspecifikationer

Varumärke: IFM
Kategori: Inte kategoriserad
Modell: E40211
Färg på produkten: Zwart
Bredd: 349 mm
Djup: 183 mm
Höjd: 610 mm
Monteringsmetod: Plafond
Maximal viktkapacitet: 45.4 kg
Harmoniserad systemkod (HS): 83024190

Behöver du hjälp?

Om du behöver hjälp med IFM E40211 ställ en fråga nedan och andra användare kommer att svara dig




Inte kategoriserad IFM Manualer

Inte kategoriserad Manualer

Nyaste Inte kategoriserad Manualer