INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 1 of 6
Component Guide
TOOL LIST
#2 Philliips Screwdriver
5/16” Socket Wrench
3/8” Socket Wrench
1/4” Socket Driver
(1) Hardware Kit
(not shown)
(1) Switch Support Bracket
CDE3
(installed in Net-Access
Server Cabinet)
Modular ToR Switch Inlet Duct
(CDE3)
Cisco Nexus 3900 Series Switch
(reference)
(2) Chassis Side Bracket
(1) Switch Ducting
(with hinged perforated door)
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 2 of 6
Determine Location of Switch Ducting and Switch Support Bracket
NOTES: Front to back span of equipment rails may need to be adjusted to accomodate your switch. Front to rear rail spacing
requirements range from 24.0" TO 30.5". Equipment installed directly below CDE3 may impede routing of switch power cord if installed
prior to CDE3.
Switch Ducting and Switch Support Bracket components of CDE3 require (4) rack spaces for installation. Switch Ducting and Switch Sup-
port Bracket are to be installed at the same vertical rack position. CDE3 components are to be installed prior to switch installation and are
designed to support the switch. (CDE3 ducting system
ONLY requires use of primary Cisco rack mount brackets. Cisco supplied switch
cradle or extension brackets are not compatible with CDE3.)
Grounding Cage Nut
(green)
Cage Nut
(installed)
Intended
Mounting
Location
(4 rack spaces)
3 RU Switch
(reference; port side of
switch faces Hot Aisle)
Install Cage Nuts
Insert (3) cage nuts per Front and Rear equipment rail at CDE3 component mounting locations (12 total cage nuts are to be installed). (1)
grounding cage nut (green) must be installed in (1) Front and (1) Rear equipment rail opposite each other on Left or Right Hand side. The
view below depicts cage nut locations for front and rear equipment rails on Left Hand Side of Cabinet
Switch Ducting
Switch Support Bracket
Intended
Mounting
Location
(4 rack spaces)
Intended Mounting Location
(4 rack spaces)
Perforated Door of Switch Ducting
(faces Cold Aisle)
FRONT OF
CABINET
REAR OF
CABINET
FRONT OF
CABINET REAR OF
CABINET
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2016 V00029KB
Page 3 of 6
Install Switch Ducting
Position Switch Ducting so that the perforated door of ducting faces the cold aisle and the mounting holes of Switch Ducting align with cage
nuts in equipment rails . Secure Switch Ducting to equipment rails using (5) #12-24 Phillips screw, (5) #12 External (installed on page 2)
Tooth Washers and (1) hex head grounding screw on front rail. Ensure that hex head grounding screws (green; use 5/16” socket wrench)
fasten into grounding cage nuts.
(1) #12-24 Hex Head
Grounding Screws
(use 5/16” socket wrench)
Switch Ducting
Perforated Door of Switch Ducting
(faces Cold Aisle)
Install Switch Support Bracket
Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails (installed on
page 2). Secure Switch Support Bracket to Rear equipment rails using (5) #12-24 Phillips screw, (5) #12 External Tooth Washers. (1) hex
head grounding screw on rear rail. Ensure that hex head grounding screws fasten into grounding cage (green; use 5/16” socket wrench)
nuts.
Grounding Cage Nut
(green)
Cage Nuts
(installed)
(5) #12-24 Phillips Screws
(1) #12-24 Hex Head
Grounding Screws
(use 5/16” socket wrench)
Cage Nuts
(installed)
Grounding Cage Nut
(green)
Switch Support
Bracket
FRONT OF
CABINET REAR OF
CABINET
FRONT OF
CABINET
(5) #12 External Tooth Washers
(5) #12-24 Phillips Screws
(5) #12 External Tooth Washers