Enda ET4420 Bruksanvisning

Enda Termostat ET4420

Läs nedan 📖 manual på svenska för Enda ET4420 (7 sidor) i kategorin Termostat. Denna guide var användbar för 4 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/7
ETx420-E-25032019
1. / 4
ENDA ET SERIES PID TEMPERATURE CONTROLLER
Thank you for choosing temperature controller.ENDA ET SERIES PID
Input Type
J (Fe-CuNi) Thermocouple
(Fe-CuNi)L Thermocouple
J (Fe-CuNi) Thermocouple
(Fe-CuNi)L Thermocouple
K (NiCr-Ni) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt 0Rh-Pt)1 Thermocouple
R (Pt13Rh-Pt) Thermocouple
EN 60584
DIN 43710
EN 60584
DIN 43710
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
Accuracy
0, % ( )5 of full scale
0, % ( )5 of full scale
0, % ( )5 of full scale
0, % ( )5 of full scale
0, % ( )5 of full scale
0, % ( )5 of full scale
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
0, % ( )5 of full scale
0, % ( )5 of full scale
1 digit
1 digit
0, % ( )5 of full scale 1 digit
0, % ( )5 of full scale 1 digit
PT100 Resistance thermometer
PT100 Resistance thermometer
EN 60751
EN 60751
0,2% ( )of full scale 1 digit
0,2% ( )of full scale 1 digit
Temperature Range
°C °F
- 99.9... 00.01 6
-30.0....600.0°C
-30.0....600.0°C
-30.0...999.9°C
-30.0...400.0°C
-200...600
-30....600°C
-30....600°C
-30...1300°C
-30....400°C
-40...1700°C
-40...1700°C
°C
°C
...-22.0 .999.9 °F
...-22.0 .999.9 °F
...-22.0 .999.9 °F
. 752-22.0 ... .0 °F
- 99.9... .1 999 9
... 2 2-22 . 37 °F
... 752-22 ...
...-40 .3092
...-40 .3092
-328... 112.1
... 1112-22 . °F
... 1112-22 . °F
°F
°F
°F
°F
°F
110V AC +%10 -%20, 230V AC +%10 -%20, 50/60Hz 24V AC %10, 50/60Hzor ±
Max. 5VA
Power : , Si : 1 ²connector 2.5mm²' screw-terminal gnal connector ,5mm screw-terminal conenction.
EEPROM ( )minimum 10 years
Max. 100ohm
1 bit2
00ms1
Relay : 250V AC, (resistive load), Selectable as NO+NC Control or Alarm2 output.8A
C/A2 output
SSR output Max 20mA 24Volt
OUTPUTS
Life expectancy for relay
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
EN 61326-1: 2013
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
CONTROL
Control type Single set-point and alarm control
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Adjustable between 0 and 100 . If Pb=0.0 , On-O control is selected.% % %
and 125 secondsAdjustable between 1
Relay : 250V AC, (resistive load), NO (Selectable as Alarm1 or Cooling Control output).8A
Mechanical 30. Mio; Electrical 100.000 operation. 250V AC, 8A (resistive load).
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
Ambient/storage temperature
Max. Relative humidity
0 ... +50 /°C -25... +70°C (with no icing)
Rated pollution degree According to EN 60529 Front panel : IP65, Rear panel : IP20
Do not use the device in locations subject to corrosive and ammable gases.
Relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
A1 output
Hysteresis
Output power
1 and 50Adjustable between °C/F
The ratio of power at a set point can be adjusted between 0 and 100% %
HOUSING
Housing type Suitable for ush-panel mounting according to DIN 43 700.
Dimensions ET4420 : G48XY48XD87MM ET7420 : G72XY72XD97MM
ET8420 : G48XY96XD87MM ET9420 : G96XY96XD50MM
Weight Approx. 400g after packing (250g for ET4420).
Self extinguishing plastics.
Enclosure material
While cleaning the device, solvents (thinner, , acid etc.) or must not be used.gasoline corrosive materials
Selectable dual setpoint.
Selectable thermocouple types.
Automatic calculation of PID parameters (SELFTUNE).
Selftune for automatic PID calculation or
manually enter PID parameters if known.
Three different specications can be assigned to digital input.
Three different specications can be assigned to F function key.
Soft-Start feature.
Selectable SSR control output.
C/A2 Relay output programmable as secondary alarm or control output.
A1 Relay output programmable as primary alarm or PID cooling output.
Selectable heating/cooling control.
Zero point input shift.
In case of sensor failure, manually, periodical or auto-periodical control can be selected.
RS485 ModBus protocol communication feature (optional).
CE marked according to European Norms.
A1
C/A2
SSR
TEMPERATURE CONTROLLER
ET 9420
ENDA
PV
SV
SET
FC/A SET
ET 8420
ENDA
TEMPERATURE CONTROL LER
SET
C/A SET F
C/A2
SSR A1
PV
SV
TEMPERATURE CONTROLLER
ENDA
ET 7420
C/A2
SSR
A1
PV
SV
F
C/A SET
SET
TEMPERATURE CONTROLLER
ENDA
C/A SET F
SET
E 442T 0
C/A2
A1
SSR PV
SV
1200
1200
Order Code : ET
1
1 - Size
4420.....48x48x87mm
7420.....72x72x97mm
8420.....48x96x87mm
9420.....96x96x50mm
2 -
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC /
7-24V AC
Supply Voltage 3 -
RS..... RS-485
....
...
( )
Blank
Modbus (Optional)
Modbus Available
Optional / Specify at order
N/A
2 0
2 3
4
Read this document carefully before using this device. The guarantee will be expired by device demages if you don't attend to the directions in
the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages.
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9
english
C.E.c,t.
C.E.c.t. E..P.S.
C.E.P.S.
C.E.c.t Auto.
= Faulty sensor control type.
If , in the case of probe
failure according to proportional
value of the parameter control is performed.
If in the case of probe
failure, the fault found and recorded before
the last setpoint control with the control
percentage is performed.
=
=
SET
C SET/A C SET/A
SET
F
F
F
Entering from the "Programming Mode" to the "Running Mode" :
If no key is pressed within 20 seconds during "Programming Mode", the data is stored au
Alternatively, the same function occurs rst pressing key is pressing "Programm
are pressing together, data is recorded and "Running mode" is entered.
FFF
F
F
C.s.Lo.
0
C.s.Hi.
600
C. pb
4.0
C. ti
4.0
C. td
1.00
C.p.st
0
C.Hys
2
C. Ct.
1
s.s.t.s.
0
C.E.p.s.
0
C.E.C.t.
E.PS.
Con.o.
inp.t.
J
Unit
°C
fltr.
5
C.o.sE
C-A2
offs.
0
d.Adr.
1
baud
9.60
d.in.C.
nonE
F.kE.C.
off
A1.S.L
0
A1.S.H
600
A1.HY
2
A1.tP.
INDE.
A1.St.
hi.
A1.Er.
ON
A1.PB
0
A1.ti
0
A1.td
0
A1.Ct
1
A1.ps
0
A1.Ep
0
A2.S.L
0
A2.S.H
600
A2.HY
2
A2.tP
INDE.
A2.St.
hi.
A2.Er.
ON
s.t.us
SET
CSET
Pid.t.
25
s.tun.
s.t.us
SET
SET
CSET
CSET
400
25
Al1.o. Al2.o. Conf.. s.tun
If key is pressed while holding key, the "Programming Mode" is enabled.
C.s.lo.= C / A2 Output Control setpoint
value lower limit.
Adjustable between 0 and C.s.Hi.
C.s.Hi.= C / A2 Output Control setpoint
value upper limit.
Adjustable between and Upper
scale value.
C.s.Lo.
C. Pb
C. Pb
= C / A2 Output P
%0 %100
= %0 On-O
roportional band
value.
Adjustable between .0 and .0.
If .0, control is selected.
C.Hys
C. Pb
= C / A2 Output Hysteresis output
value.
Adjustable between 1 and 50 °C.
If = 0, this parameter is active.
C. ti
C. ti
C. Pb
= C / A2 Output value
=
If
Integral .
Adjustable between 0 and 100.0 minutes.
0.0,integral impact is disable.
parameter is dierent from
“0”, this parameter appears.
C. td
C. td
C. Pb
= C / A2 Output value
=
Derivative .
Asjustable between 0.00 and 25.00 minutes.
0.0, derivative time is disabled.
If parameter is dierent from”0”,
this parameter appears.
C. Ct.
C. Pb
= C / A2 Output Period time.
Adjustable between 1 and 250 second.
parameter is dierent is dierent
from“0”, this parameter appears.
C.E.P.s.
C.E.c.t E.PS. C. Pb 0.0
C. Pb 0.0
C.E.P.S 0
= In the case of probe failure, C / A2
output adjustable between
= or = is
selected, this parameter is activated.
In the case of failure, if = (ON/O
Control) and = output will be O,
if dierent from “0” value, output will be ON.
percentage %0
and %100.
If
S.S.t.S. = Soft Start timer set value.
This parameter indicates the time to
reach set point value when the device is
rst ene gised.r
Adjustable between 0 and 250 minutes.
If 0 is selected, soft start feature will be
enable and the device reaches set point
value quickly.
Pb = 0, so start feature will
be disable .
Setting ft
d
C.p.st =
and
At C / A2 Set value, C/A1 percent of
power.
Adjustable between 0% 100%.
a1.s.l= Alarm1 set value lower limit.
parameter value.
Adjustable between and0 A1.S.H
a1.s.H= Alarm1 set value upper limit.
Adjustable between parameter value
and upper scale value.
A1.S,L
a1.Hy=Hysteresis of the Alarm1 output.
Adjustable between 1 and 50 C.°
A1.tp
indE.
dE.
bAnd
bAn.i
= Alarm1
= Independent
= alarm
= Band alarm (Band)
=
Type of .
Six kinds of functions can be selected.
alarm
Deviation
Band with inhibition
in.Co.
rE.Co
= A1 output independent cooling
control
= A1 output relative cooling control
A1.st.
Hi
= Alarm1 output situation.
If Alarm1 output outputis above
the Alarm1 set value ; on.
= A1
lo
A1.tP. in.Co. rE.Co.
= A1
para
output is above the Alarm1 set
value ; o.
meter , or is
selected; this parameter is not seen.
A1.Er.
on
= Alarm
output probe failure; on.
1 probe failure situation.
= A1
off
A1.tP. in.Co. rE.Co.
= A1 output probe failure; o.
parameter, or is
selected, this parameter is not seen.
A1.Pb
A1.Pb
A1.tP. in.Co. rE.Co.
=
0 and
= 0 , On-O control is selected.
A1 output,value of proportional
band.
Adjustable between % 100%.
%
parameter, or is
selected,this parameter is activated.
A1.ti
A1.ti
A1.tp. in.Co. rE.Co.
A1.Pb
=
=
and if dierent from “0” ,
A1 output integral value.
Adjustable between 0.0 and 100.0 minute.
0.0 eect of integral disable.
parameter, or is
selected
this parameter is activated.
A1.td
A1.td
A1.tp. in.Co. rE.Co.
A1.Pb
=
= .
and if dierent from “0”,
this parameter is activated.
A1 output derivative value.
Adjustable between 0.00 and 25.00 minute.
0.00 eect of derivative disable
parameter or is
selected
A1.Ct
A1.tp. in.Co. rE.Co.
A1.Pb
=
and if dierent from “0”,
this parameter is activated.
A1 output period time.
Adjustable between 1 and 250sec.
parameter or is
selected
A1.Ps
A1.tp. in.Co. rE.Co.
A1.Pb
=
and
and if dierent from “0”,
this parameter is activated.
At A1 Set value, A1 output percent
of power.
Adjustable between 0% 100%.
parameter or is
selected
A1.Ep
A1.tp. in.Co. rE.Co.
= At A1 Set value, A1 output percent
of power.
Adjustable between 0%-100%.
parameter or is
selected, this parameter is activated.
In SSR output devices, if
parameter is dierent
from , this menu
appears.
co.SE
C-A2
a2.s.l= Alarm
parameter value.
2 set value lower limit.
Adjustable between and0 A2.S.H
a2.s.H= Alarm2 set value upper limit.
Adjustable between parameter
value and upper scale value.
A2.S,L
a2.Hy= Hysteresis of the Alarm2
output.
Adjustable between 1 and 50 C.°
A2.tp
indE.
dE.
bAnd
bAn.i
=
= Independent
= Deviation
= Band alarm
=
Type of Alarm2.
Four kinds of functions can be
selected.
alarm
alarm
Band with inhibition
A2.st.
Hi
= Alarm2
2 output is above the set
value;on
output situation.
= A
lo= A2 output is above the set value;
o.
A2.Er.
on
= Alarm
2 output probe failure; .
2 probe failure
situation.
= A on
off= A2 output probe failure;o.
inp.t.
Pt.0
Pt.
J.0
j
k.0
k
L.0
L
t.0
t
s
r
= Type of input selection.
= PT100 decimal,
= PT100 Non-decimal,
= J Type decimal,
= J Type Non-decimal,
= K Type decimal,
= K Type Non-decimal,
= L Type decimal,
= L Type Non-decimal,
= T Type decimal,
= T Type,
= S Type,
= R Type, thermocouple selection.
This parameter varies when changing
some parameters.
Unit = The temperature unit.
= °C, = °F
This parameter varies when changing
some parameters.
°C °F
fLtr. = Coecient of digital lter.
Adjustable between 1 and 200.
If this parameter is 1, digital lter runs most
quick. If the parameter is 35, the lter run
most slow. The value of parameter should be
increased in interference.
C.o.sE = Control output selection
C-A2
SSR
= C/A2 (Relay) output selection
= SSR output selection
oFFS.= Oset
-99 99°C, for decimal
values can be adjusted between -10.0 and 10°C.
Normal
value.
Oset value is added to the measuring value.
This feature which is the point of measurement
due to its distance measurement probe, is used
to eliminate errors that might occur.
Adjustable between and
value=0.
D.aDr. = Device address for RS485 connection.
Adjustable between and .
This parameter is active devices with
RS485 communications option.
1 247
baud = ModBus baud rate for RS485 connection
Selectable as; o, 2.4, 4.8, 9.6, 19.20 ve 38.40 .
This parameter is active devices with RS485
communications option.
d.in.C. = Digital input setting parameter.
nonE
C2.S.A.
manu.
C.Ct
m.SEt
dSP.o.
= Digital input is closed.
= if digital input is activated, 2nd set value
is used.
=
= If the digital input is activated;
temperature indicator mode can be exceed.
Manual mode start in case of digital
outputs are active and and rational output
generated according to period value in
paremeter and percentage value in
parameter.
F.kE.C. = Function key setting parameter.
nonE
C2.S.A .
manu.
dSP.o.
= Function key is closed.
= The function key is used with the 2nd set value.
= Manual mode can be exceed by using the
function key.
= Temperature indicator mode can be exceed by
using function key.
C.typ
HEAt
C.typ. = Control output type
C.typ. HEAt
C.typ. CooL
=
=
means heating control.
means cooling control.
CONNECTION DIAGRAM
Logic output of the instrument is not electrically
insulated from the internal circuits. Therefore, when
using a grounding thermocouple, do not connect the
logic output terminals to the ground.
1)
2)
Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
In accordance with the safety regulations, the power
supply switch shall bring the identication of the
relevant instrument and it should be easily accessible
by the operator.
Note :
Holding screw
0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
ALARM1 AND ALARM2 OUTPUT TYPES
Independent Alarm
A1.tp. indE=
Deviation Alarm
= A1.tp dE.
Band
=
Alarm
A1.tp. bAnd
A1.St. Hi=
A1.St. lo=
=A1.St. Lo
=A1.St. Hi
ASV
SV SV
SV
SV+ASV
SV+ASV
SV-ASV
OFF OFF
OFF
OFF OFF
OFF
-300
300
+300
300
ON ON
ON
ON ON
ON
SV = CONT output set value ASV = Alarm output set value
(ASV min. =-300, ASV maks. = +300)
(ASV min. = 0, ASV ma . = +300)x
(ASV min. = beginning of scale
ASV max. = end of scale) SV =CONT set ASV = AL1 setoutput value output value
a1,Hy A1.Hy
A1.Hy
A1.Hy
=
Band Alarm With Inhibition
A1,tp. bAn.i
ON
ON
OFF
OFF
Beginning
SV =
ASV =
(ASV min. = 0, ASV ma = 300 )
Set point of CONT output
Set point of AL1 output
x.
Band alarm is possible
Band alarm is possible
Beginning
SV
SV
SV+ASV
SV+ASV
SV-ASV
SV-ASV
SET
C SET/A
250
400
C1.SE.
400
C2.SE.
400
a1.SE.
500
a2.SE.
500
m.SEt
50
C1.SE.
400
C2.SE.
400
a1.SE.
500
a2.SE.
500
m.SEt
50
C1.SE.
399
C2.SE.
399
a1.SE.
499
a2SE.
499
m.SEt
49
SET
C SET/A
SETTING UP ALARM CONTROL AND SETPOINT VALUES
3 seconds later
3 seconds later
3 seconds later
3 seconds later
3 seconds later
3 seconds later
If the parameter is set to SSR out,
this parameter is seen.
C.O.SE.
If one of the or parameters are
set to the value, this parameter is seen.
d.in.c. f.kE.c.
C2.S.A.
If one of the or parameters are
set to the value and if is dierent
from 0, this parameter is seen.
d.in.c. f.kE.c.
mAnu. C. Pb
ERROR MESSAGES
pfa
400
400
____
400
----
Temperature sensor
is broken.
Temperature value is
higher than the scale.
Temperature value is
broken or over temperature.
ENDA INDUSTRIAL ELECTRONICS
E - VAC
PID CONTROLLER
T7420 230 - RS
TEMPERATURE
V AC +10% -20%
50/60Hz 7VA
230
C / A2
AC 250V
RESISTIVE
LOAD
8A
A1
AC 250V
RESISTIVE
LOAD
8A
11
12
13
14
15
16
17
SN: XXXXXXXXX
8 6804 07 7 059 55
Made in Turkey
-
+
RS-485
COM.
RS- 485
SSR
OUT
A
B
+
-
TC
+
-
Pt 100
9
8
5
4
3
2
1
10
7
6
DIN
ENDA INDUSTRIAL ELECTRONICS
E - VAC
PID CONTROLLER
T7420 24 - RS
TEMPERATURE
V AC +10% -20%
50/60Hz 7VA
24
C / A2
AC 250V
RESISTIVE
LOAD
8A
A1
AC 250V
RESISTIVE
LOAD
8A
11
12
13
14
15
16
17
SN: XXXXXXXXX
8 6804 07 7 059 55
Made in Turkey
-
+
RS-485
COM.
RS- 485
SSR
OUT
A
B
+
-
TC
+
-
Pt 100
9
8
5
4
3
2
1
10
7
6
DIN
18
29
716 17
615
310
413
514
ENDA
INDUSTRIAL ELECTRONICS
ET9420-2 VAC-RS
PID CONTROLLER
30
TEMPERATURE
-
8 6 804 07 70 612 9
Made in Turkey
11 12
18
29
716 17
615
310
413
514
-
11 12 18
29
716 17
615
310
413
514
ENDA
INDUSTRIAL ELECTRONICS
ET9420-2 VAC-RS
PID CONTROLLER
4
TEMPERATURE
-
8 68 0 4 07 70 612 9
Made in Turkey
11 12
18
29
716 17
615
310
413
514
-
11 12
-
+
RS-485
COM.
RS- 485
SSR
OUT
A
B
+
-
SN: XXXXXXXXX
15
16
17
18
19
20
21
2 V AC +10% -20%
50/60Hz 7VA
4
C / A2
AC 250V
RESISTIVE
LOAD
8A
A1
AC 250V
RESISTIVE
LOAD
8A
TC
+
-
Pt 100
11
10
7
6
5
4
3
12
8 6 80 40 7 7 0 604 4
Made in Turkey
9
8
DIN
-
+
RS-485
COM.
RS- 485
SSR
OUT
A
B
+
-
SN: XXXXXXXXX
15
16
17
18
19
20
21
2 V AC +10% -20%
50/60Hz 7VA
30
C / A2
AC 250V
RESISTIVE
LOAD
8A
A1
AC 250V
RESISTIVE
LOAD
8A
TC
+
-
Pt 100
11
10
7
6
5
4
3
12
8 6 80 40 7 7 0 604 4
Made in Turkey
9
8
DIN
DIN
9
10
8
ET4420 ET7420 ET8420
ET4420 ET7420 ET8420 ET9420
ET4420 ET7420 ET8420 ET9420
9
10
9
10 12
11
11
12
10
9
10
8
ET9420
8
9
9
10
8
NOTE :
SUPPLY VOLTAGE
F 100 mA
250V AC
230V AC 24V ACor
Supply
Cable Size : 1,5mm²
Line
Neutral
Fuse should
be connected.
Switch
184-253V AC
50/60Hz 7VA
SENSOR INPUT:
For J - K - T- S and R Thermocouples :
Use the correct compensating cable.
Do not make any supplement to cables. Connect
the thermocouple cables to the right places at the
input terminal.
PT100 PT100 PT100
PT100
For PT100 Sensorresistance ( ) :
When using 2-wire PT100 sensor, as shown in the
gures, make 8 and 9 terminals short circuit for
ET4420, ET7420 and ET9420 devices, make 10 and 11
terminals short circuit for ET8420 devices.
ETx420-E-25032019
3. / 4
SN: XXXXXXXXX
INDUSTRIAL ELECTRONICS
ET44 0-
P TEMPERATURE CONTROLLER
2 230V
ID
ENDA
8 680407 715497
C/A2
A1
AC 250V
RESISTIVE LOAD
8A
AC 250V
RESISTIVE LOAD
8A
SSR OUT
DIN
16
8
17
9
10
11
1
12
2
13
3
14
4
15
5
6
7
+
-
2 V AC ±10%
50/60Hz 5VA
30
-
+
TC
PT100
SN: XXXXXXXXX
INDUSTRIAL ELECTRONICS
ET44 -
P TEMPERATURE CONTROLLER
20 230V-RS
ID
ENDA
C/A2
A1
AC 250V
RESISTIVE LOAD
8A
AC 250V
RESISTIVE LOAD
8A
SSR OUT
DIN
16
8
17
9
10
11
1
12
2
13
3
14
4
15
5
6
7
+
-
2 V AC ±10%
50/60Hz 5VA
30
-
+
TC
PT100
-
+
RS- 485
A
B
RS-485 COM.

Produktspecifikationer

Varumärke: Enda
Kategori: Termostat
Modell: ET4420

Behöver du hjälp?

Om du behöver hjälp med Enda ET4420 ställ en fråga nedan och andra användare kommer att svara dig




Termostat Enda Manualer

Enda

Enda ET2011 Bruksanvisning

23 September 2024
Enda

Enda ATC9311 Bruksanvisning

23 September 2024
Enda

Enda ET2411 Bruksanvisning

23 September 2024
Enda

Enda ET2412 Bruksanvisning

22 September 2024
Enda

Enda ET2011-T Bruksanvisning

22 September 2024
Enda

Enda ET4420 Bruksanvisning

22 September 2024

Termostat Manualer

Nyaste Termostat Manualer