Jøtul GF 200 DV II
Direct Vent Gas Stove
Installation and
Operation Instructions
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed
by a qualified installer, service agency or
the gas supplier.
In the Commonwealth of Massachusetts,
a carbon monoxide (CO) detector shall
be installed in the same room as the
appliance.
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property damage,
personal injury or loss of life.
This appliance may be installed in an aftermarket,
permanently located, manufactured home or
mobile home, where not prohibited by local codes.
This appliance is only for use with the types of gas
indicated on the rating plate. A conversion kit is
supplied with the appliance.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Jøtul GF 100 DV II
Direct Vent Gas Stove











Installation Requirements
for the Commonwealth of
Massachusetts
THIS PRODUCT MUST BE INSTALLED BY
A LICENSED MASTER OR JOURNEYMAN
PLUMBER OR GAS-FITTER WHEN
INSTALLED IN THE COMMONWEALTH OF
MASSACHUSETTS.
1. If there is not one already present,
on each floor level where there are
bedroom(s), a carbon monoxide
detector and alarm shall be placed in
the living area outside the bedroom(s).
The carbon monoxide detector shall
comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a) Be located in the room that houses
the appliance or equipment;
b) Be either hard-wired or battery
powered or both; and
c) Shall comply with NFPA 720 (2002
Edition).
3. A Product-approved vent terminal
must be used, and if applicable, a
Product-approved air intake must
be used. Installation shall be in strict
compliance with the manufacturer’s
instructions. A copy of the installation
instructions must remain with
the appliance or equipment at the
completion of the installation.
Suggested Tools for Installation and Service
External regulator (for Propane only)
Piping which complies with local code
Manual shut-off valve -
T-Handle required in Massachusetts
Sediment trap - if required by code
Tee joint
Pipe wrench
Pipe sealant
10 mm open end wrench
1/2”, 7/16” open end wrench
Phillips head screwdriver
Flat head screwdriver
1/4” nut driver
Work Gloves
Safety glasses
Torx T-20 screwdriver
Tin snips
THIS OWNER’S MANUAL PROVIDES INFORMATION TO
ENSURE SAFE INSTALLATION AND EFFICIENT, DEPENDABLE
OPERATION OF YOUR FIREPLACE INSERT. PLEASE READ
THESE INSTRUCTIONS IN THEIR ENTIRETY AND MAKE THEM
AVAILABLE TO ANYONE USING OR SERVICING THIS GAS
INSERT.
DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION
OF THIS APPLIANCE OR ITS COMPONENTS. ANY
MODIFICATION OR ALTERATION WILL VOID THE WARRANTY,
CERTIFICATION AND LISTING OF THIS APPLIANCE.
THIS HEATER MUST BE INSTALLED AND MAINTAINED BY A
QUALIFIED SERVICE AGENCY.
We recommend that
our gas products be
installed and serviced by
professionals who are
certified in the U.S. by
the National Fireplace
Institute® (NFI) as NFI
Gas Specialists.
3
138003_Rev_P / Oct.2015
Table of Contents
Specifications, Jøtul GF 100 DV II 4 ..........
Specifications, Jøtul GF 200 DV II 5 .........
General Information 6 ................................
Service Tools .............................................6
Safety Information 7 ..................................
Installation Requirements
Location 7 ................................................
Hearth Protection 7 ...............................
Clearances 8 ...........................................
Mantel & Trim 8 ......................................
Alcove 8 ....................................................
Vent Requirements
Adding Restriction 9 ...............................
Vertical Termination 10 .........................
Horizontal Termination 12 ....................
Vent Terminal Clearances 14 ...............
Mobile Home Installation 15 .....................
Fuel Conversion 15 ........................................
Gas Connection 17 ........................................
Gas Pressure 18 ............................................
High Altitude Adjustment 18 ...................
Air Shutter Adjustment 19 .......................
Wall Thermostat .................................... 20
Remote Control 20 ......................................
Log Set Installation 20 ...............................
System Check 21 ..........................................
Operation 22 .................................................
Maintenance 22 ...........................................
Glass Replacement 22 .............................
Optional Blower 24 .....................................
Illustrated Parts Breakdown 26, 27 ..........
Replacement Parts List 28, 29 ...................
Addendum - Brick Panel Kit 30 ................
Warranty Statement 31 ..............................
Lighting Instructions 35 .............................
Direct Vent Gas Heaters
Manufactured and Distributed by:
Jøtul North America
Gorham, Maine
U.S.A.
Test Standards
This appliance complies with
U.S. and Canadian National
Safety standards and is
tested and listed by Intertek
Testing Services of Middleton,
Wisconsin to ANSI Z21.88-2014, CSA 2.33-2014,
CAN/CGA 2.17-M91, and CSA P.4.-01.2.
DO NOT ATTEMPT TO ALTER OR MODIFY
THE CONSTRUCTION OF THE APPLIANCE
OR ITS COMPONENTS. ANY MODIFICATION
OR ALTERATION WILL VOID THE WARRANTY,
CERTIFICATION AND LISTING OF THIS APPLIANCE.
Jøtul GF 200 DV II Lillehammer
and
DV II Nordic QT Jøtul GF 100
Your stove has a unique serial number stamped on the
rating plate which is to the back of the stove. Please
record the serial number in the space below. You
may also wish to attach your purchase receipt to this
manual for future reference.
MODEL NAME: __________________________________
SERIAL NUMBER:_________________________________
DATE OF PURCHASE:______________________________
AUTHORIZED DEALER:_____________________________
ADDRESS ______________________________________
PHONE: _______________________________________
INSTALLER:_____________________________________
FUEL TYPE:______________________________________
FUEL CONVERSION: No _____ Yes_____