Theben theLuxa S180 BK Bruksanvisning

Theben Rörelsedetektorer theLuxa S180 BK

Läs nedan 📖 manual på svenska för Theben theLuxa S180 BK (4 sidor) i kategorin Rörelsedetektorer. Denna guide var användbar för 9 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/4
1
theLuxa S150 WH 1010500
theLuxa S150 BK 1010501
theLuxa S180 WH 1010505
theLuxa S180 BK 1010506
309691 01
Motion detector
EN
1. Essential safety instructions
Danger of death through electric shock or fire!
Installation should only be carried out by a pro-
fessional electrician!
WARNING
The device conforms with EN 60669-2-1 when correctly
installed
IP 55 in accordance with EN 60529
Designated use
Motion detector for automatic lighting control dependent
on presence and brightness
Suitable for installation on external walls
Suitable for entrances, garages, gardens, corridors, parks,
etc.
Only intended for installation outside of arm‘s reach
Disposal
Dispose of the motion detector in an environmentally sound
manner (electronic waste)
2. Description
2 potentiometers
for setting time
(min) and bright-
ness (lux)
Motion detector
with sensor head
3. Connection
WARNING
Danger of death through electric shock!
Disconnect power source!
Cover or shield any adjacent live components.
Ensure device cannot be switched on again!
Check power supply is disconnected!
Earth and bypass!
!
The device can be manually activated with a circuit breaker.
After releasing the button (return of power) the device swit-
ches on (for at least 40 secs or for the time set on the device).
4. Installation
If applicable, use optional corner bracket (9070902,
9070903) or spacer frame (9070906, 9070907) for exible
installation as well as cable insertion from side or top/
bottom.
230V
Disconnect power source.
2
Make marks for the holes on the wall (with en-closed drill
template/base).
Drill holes.
Ø
6 mm
60 mm
Feed cable through the seal of the base.
Fasten base (and spacer frame) to the wall.
brown
brown
Phase
Switched
phase
Neutral
conductor
Neutral
conductor
Earthing
conductor
Earthing
conductor
blue
blue
green/yellow
Connect the individual wires to the appropriate terminal.
Tighten screws.
Click!Click!
Plug motion detector into base and click in.
Connect motion detector to power supply.
Dismantling
Using the screwdriver, carefully loosen the snap-in hook at
the side and pull the device forward.
Installation instructions
As the detector reacts to variations in temperature, avoid the
following situations:
Do not direct motion detectors at objects with highly reec-
tive surfaces such as mirrors etc.
Do not install motion detectors near heat sources such as
heating outlets, air conditioning systems, lamps etc.
Do not direct the motion detector at objects that turn in the
wind such as curtains, large plants etc.
Take account of motion direction during test run.
10
20
30
40
40
10
20
30
40
40
10
20
30
40
40
3 m
5 m
12 m
150°
6 m
3 m
5 m
12 m
180°
6 m
Recommended installation height: 2 – 4 m
Crosswise detection area: 12 m (crosswise to the detector)
Frontal detection area: 5 m (in front of the detector)
Detection angle: 150°/18
5. Direction test and alignment
The walk test is used to test the detection range and to res-
trict it if necessary.
Set the potentiometer time (min) to test.
3
The motion detector now only reacts to movement (indepen-
dent of brightness).
Crosswise to the detection area. After the motion detector
has detected a movement, it switches on for 2 s.
Note direction of motion during the test.
0
2
Sec
2 sec
Test
210
20
30s
test
min
Align motion detector with sensor head
The sensor head can be turned by 30° downwards and
by 90° to left and right.
30˚
30
90 90
6. Setting
The motion detector has two potentiometers underneath for
setting the time (min) and brightness (lux).
15 100
7
10
lux
210
20
30s
test
min
Set brightness (lux)
You can set different brightness values (lux) with the
potentiometer.
If you want to change the preset brightness (15 lux default)
Set potentiometer to desired brightness (5 – 1000 lux).
15 100
7
10
lux
teach-in 1000 Lux
5 Lux 500 Lux
7 Lux 100 Lux
10 Lux
15 Lux
50 Lux
15 Lux
or want a specic brightness value to be learned using the
teach-in function
At the desired brightness set the potentiometer to . The
value will be learned after 15 s.
Leave potentiometer at position .
Set time (min)
If the motion detector detects no further movement, it swit-
ches off after the set time.
If you want to change the preset time (2 min default)
Set potentiometer to desired time (0.5 s – 20 min).
210
20
30s
test
min
test 20 min
1 s 15 min
30 s 10 min
1 min
2 min
5 min
2 min
If you want to use the pulse function (e.g. for a staircase light
time switch)
Set potentiometer to position . The motion detector
is switched on for < 1 s, then off for 9 s. If it detects a
movement again, it switches on again for 1 s.
7. Caractéristiques techniques
Operating voltage: 230 V AC, +10 % –15 %
Frequency: 50 Hz
Standby: < 1 W
Detection angle: 150°/180°
Detection area: crosswise: max. 12 m,
frontal: max. 5 m
Installation height: 2 – 4 m
Creep under protection: yes
Brightness setting range: 5–1000/∞ lux
Switching period range: 5 s – 20 min
Permissible ambient temperature: –25 °C to +45 °C
Protection class: II
Protection rating: IP 55 in accordance with
EN 60529
Switching capacity: 10 A (cos = 1)ϕ
6 A (cos ϕ = 0.6)
3 AX (cos ϕ = 0.3)
Min. switching capacity: 10 mA
Switching contact: μ-Contact 230 V AC
LED lamps <2 W 25 W
LED lamps >2 W <8 W 90 W

Produktspecifikationer

Varumärke: Theben
Kategori: Rörelsedetektorer
Modell: theLuxa S180 BK

Behöver du hjälp?

Om du behöver hjälp med Theben theLuxa S180 BK ställ en fråga nedan och andra användare kommer att svara dig