Ariston Thermo Alteas One Net Bruksanvisning
Ariston Thermo
Pannor & pannor
Alteas One Net
Läs nedan 📖 manual på svenska för Ariston Thermo Alteas One Net (76 sidor) i kategorin Pannor & pannor. Denna guide var användbar för 4 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare
Sida 1/76

CONDENSING WALL-HUNG GAS BOILER
Country of Destination: GB/IE
INSTALLATION AND SERVICING INSTRUCTIONS
HOT WATER HEATING RENEWABLES I I
G.C.N.: (30 kW)47-116-91
G.C.N.: (35 kW)47-116-92
Including
CUBE Room Sensor
wireless
ALTEAS ONE Net

INDEX
Overview ............................................................................................3
General Information ........................................................................4
Advice for the Installer....................................................................4
CE Labelling ......................................................................................4
Data Plate Symbols .........................................................................4
Safety Regulations ..........................................................................5
Product description ........................................................................7
Control Panel ....................................................................................7
Display ................................................................................................8
Overall View ......................................................................................8
Overall Dimension ...........................................................................9
Minimum Clearances ......................................................................9
Installation ......................................................................................10
Reference Standards .................................................................... 10
Installing the Boiler ........................................................................ 13
Gas Connection .............................................................................. 14
Water Connection .......................................................................... 14
Instructions for Opening the Casing and Performing an
Internal Inspection .................................................................... 14
Underfl oor heating ........................................................................ 15
Water circuit diagram ....................................................................16
Connecting the Flue ...................................................................... 17
Fitting the Coaxial Flue (Ø 60/100 Horizontal) ...................... 18
Fitting the 5” Flue (Ø 80/125 Horizontal / Vertical) ...............19
Fitting the Coaxial Flue (Ø 60/100 Vertical) ...........................20
Fitting the Twin Pipe (Ø 80/80) ...................................................21
Electrical Connections .................................................................24
Peripheral Unit Connection ........................................................ 24
Room Thermostat Connection ...................................................25
Electrical Diagram ........................................................................ 26
Commissioning ............................................................................. 27
Initial Preparation .......................................................................... 27
Electricity Supply .......................................................................... 27
Filling the Heating System ......................................................... 27
Filling of the DHW System .......................................................... 27
Gas Supply ..................................................................................... 27
Water Treatment ............................................................................ 27
Start-up procedure ........................................................................29
First ignition
(deaeration cycle and automatic calibration ........................ 29
Maximum heating power adjustment ...................................... 33
Checking slow ignition power ................................................... 33
Heating ignition delay adjustment ........................................... 33
Table summarising changes ...................................................... 33
Gas changeover ............................................................................ 34
AUTO Function ............................................................................... 35
Boiler Protection Devices ..........................................................36
Boiler Protection Devices............................................................36
Table summarising error codes ................................................. 37
Anti-Frost Device ........................................................................... 37
Technical Area .............................................................................. 38
Accessing the Menus ...................................................................38
Maintenance ..................................................................................45
General Comments ......................................................................45
Operational Test ............................................................................ 45
Draining procedures.....................................................................45
Cleaning the primary exchanger .............................................. 45
Cleaning the trap .......................................................................... 46
Maintenance Guide ..................................................................... 47
General Access ............................................................................. 47
Electrical Unit .................................................................................48
Hydraulic Unit ................................................................................50
Burner Unit ......................................................................................60
Annual Maintenance .................................................................... 64
Technical Information ................................................................. 66
Technical Data GENUS ONE NET .............................................66
ERP Data GENUS ONE NET ....................................................... 67
Product fi che GENUS ONE NET ................................................68
Product fi che CUBE WIFI ............................................................68
Package Label - Instuctions to fi lling ....................................... 69
Package fi che ................................................................................ 70
Benchmark Commissioning Checklist .................................... 73
Benchmark Service Interval Record ........................................ 74

/ 3
OVERVIEW
These instructions are suitable for Alteas One Net boilers :
Do not forgot to complete the Benchmark Commissioning Checklist!
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers
are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in
accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of
the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with
Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the
Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage
and promote the Scheme. Visit www.centralheating.co.uk for more information.
To The Installer
As part of the commissioning of this appliance it is vital that the Benchmark Commissioning Checklist is completed and
given to the Householder. Please ensure that your customer is aware of the importance of keeping the Commissioning
Checklist and Service Interval Record safe to document the product’s history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
ARISTON recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.
CUSTOMER CARE
ARISTON, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing
high quality products and a high quality after sales service.
Advice on installation or servicing can also be obtained by contacting the ARISTON Technical and Customer Service
Departments at High Wycombe.
TECHNICAL DEPARTMENT CUSTOMER SERVICE DEPARTMENT
Tel: 0333 240 7777 Tel: 0333 240 8777
Fax: 01494 459775 Fax: 01494 459775
WARRANTY
The manufacturer’s warranty is for 12 years from the date of purchase. The warranty is invalidated if the appliance is
not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer.
To assist us in providing you with an effi cient after sales service, please register the warranty online at www.ariston.
co.uk
CAUTION
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person
only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent
Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations,
reference should also be made to the current ETCI rules for electrical installation.
All GAS SAFE registered installers carry a GAS SAFE ID card, and have a registration number. Both should be
recorded in your boiler Benchmark Commissioning Checklist. You can check your installer is GAS SAFE registered
by calling GAS SAFE directly on:- 0800 408 5500.
Improper installation may cause damage or injury to individuals, animals and personal property for which the
manufacturer will not be held liable. To ensure effi cient and safe operation it is recommended that the boiler is serviced
annually by a competent person.
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent
person.
Please refer to the terms and conditions of warranty in the user manual which are also available on our website.
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland

4 /
OVERVIEW
CE labelling
The CE mark guarantees that the appliance conforms to the
following directives:
- 2016/426/EU
relating to gas appliances
- 2014/30/EU
relating to electromagnetic compatibility
- 92/42/CEE
relating to energy effi ciency
- 2014/35/EU
relating to electrical safety
- 2009/125/CE
Energy related Products
- 813/2013
Commission regulation (EU)
Advice for the installer
This appliance is designed to produce hot water for domestic
use.
It should be connected to a heating system and a distribution
network for domestic hot water, both of which must be compatible
with its performance and power levels.
The use of the appliance for purposes other than those
specifi ed is strictly forbidden. The manufacturer cannot be held
responsible for any damage caused by improper, incorrect and
unreasonable use of the appliance or by the failure to comply
with the instructions given in this manual.
Installation, maintenance and all other interventions must be
carried out in full conformity with the governing legal regulations
and the instructions provided by the manufacturer. Incorrect
installation can harm persons, animals and possessions; the
manufacturing company shall not be held responsible for any
damage caused as a result. The boiler is delivered in a carton.
Once you have removed all the packaging, make sure the
appliance is intact and that no parts are missing. If this is not the
case, please contact your supplier.
Keep all packaging material (clips, plastic bags, polystyrene foam,
etc.) out of reach of children as it may present a potential hazard.
In the event of a fault and/or malfunction, turn the appliance
off, turn off the gas cock and do not attempt to repair it yourself.
Contact a qualifi ed professional instead.
Before any maintenance or repair work is performed on the
boiler, make sure you have disconnected it from the electricity
supply by switching the external bipolar switch to the “OFF”
position and removing the fuse.
All repairs, which should only be performed using original spare
parts, should be carried out by a qualifi ed professional. Failure
to comply with the above instructions could compromise the
safety of the appliance and invalidate all liability on the part of
the manufacturer.
In the event of any maintenance or other structural work in the
immediate vicinity of the ducts or fl ue gas exhaust devices and
their accessories, switch the appliance off by switching the
external bipolar switch to the “OFF” position and shutting off the
gas control valve. When the work has been completed, ask a
Symbols used on the data plate
MIN
Q
MA
X
P
60/80° C
1
2
5
4
3
3
6
7
19
8
9
10 11
12
14
15
16 17 18
13
20
21
22
1
Legend :
1. Brand
2. Manufacturer
3. Boiler model
Serial number
4. Commercial reference
5. Certifi cation number
6. Destination country
Gas category
7. Gas setting
8. Installation type
9. Electrical data
10. Maximum domestic hot
water pressure
11. Maximum heating pressure
12. Boiler type
13. NOx class / Effi ciency
14. Input rating nominal
heating
15. Power ouput heating
16. DHW specifi c fl ow rate
17. Boiler output effi ciency
18. Input rating nominal DHW
19. Gases which may be used
20. Minimum ambient
temperature for use
21. Max. central heating
temperature
22. Max. domestic hot water
temperature
ATTENTION!!
THE INSTALLATION AND FIRST
IGNITION OF THE BOILER MUST BE
PERFORMED BY GAS SAFE REGISTERED
ENGINEER IN COMPLIANCE WITH
GAS SAFETY (INSTILLATION & USE)
REGULATIONS AND ALL OTHER NATIONAL
REGULATIONS REGARDING INSTALLATION,
AND IN CONFORMITY WITH ANY
REQUIREMENTS ESTABLISHED BY LOCAL
AUTHORITIES AND PUBLIC HEALTH
ORGANISATIONS.
AFTER THE BOILER HAS BEEN INSTALLED,
THE INSTALLER MUST ENSURE THAT THE
END USER RECEIVES THE DECLARATION
OF CONFORMITY AND THE OPERATING
MANUAL, AND SHOULD PROVIDE ALL
NECESSARY INFORMATION AS TO HOW
THE BOILER AND THE SAFETY DEVICES
SHOULD BE HANDLED.
qualifi ed technician to check the effi ciency of the ducting and
the devices.
Turn the boiler off and turn the external switch “OFF” to clean
the exterior parts of the appliance.
Clean using a cloth dampened with soapy water. Do not use
aggressive detergents, insecticides or toxic products. If the
appliance is used in full compliance with current legislation, it
will operate in a safe, environmentally-friendly and cost-effi cient
manner.
If using kits or optional extras, make sure they are authentic.

/ 5
OVERVIEW
Install the appliance on a solid wall which is not
subject to vibration.
Noisy operation.
When drilling holes in the wall for installation
purposes, take care not to damage any electrical
wiring or existing piping.
Electrocution caused by contact with live
wires. Explosions, fi res or asphyxiation caused
by gas leaking from damaged piping.
Damage to existing installations.
Flooding caused by water leaking from
damaged piping.
Perform all electrical connections using wires
which have a suitable section.
Fire caused by overheating due to electrical
current passing through undersized cables.
Protect all connection pipes and wires in order to
prevent them from being damaged.
Electrocution caused by contact with live
wires. Explosions, fi res or asphyxiation caused
by gas leaking from damaged piping.
Flooding caused by water leaking from
damaged piping.
Make sure the installation site and any systems
to which the appliance must be connected comply
with the applicable norms in force.
Electrocution caused by contact with live wires
which have been installed incorrectly.
Damage to the appliance caused by improper
operating conditions.
Use suitable manual tools and equipment (make
sure in particular that the tool is not worn out
and that its handle is fi xed properly); use them
correctly and make sure they do not fall from
a height. Replace them once you have fi nished
using them.
Personal injury from the falling splinters or
fragments, inhalation of dust, shocks, cuts,
pricks and abrasions.
Damage to the appliance or surrounding
objects caused by falling splinters, knocks and
incisions.
Use electrical equipment suitable for its intended
use (in particular, make sure that the power
supply cable and plug are intact and that the
parts featuring rotary or reciprocating motions
are fastened correctly); use this equipment
correctly; do not obstruct passageways with the
power supply cable, make sure no equipment
could fall from a height. Disconnect it and replace
it safely after use.
Personal injury caused by falling splinters
or fragments, inhalation of dust, knocks,
cuts, puncture wounds, abrasions, noise and
vibration.
Damage to the appliance or surrounding
objects caused by falling splinters, knocks and
incisions.
Make sure any portable ladders are positioned
securely, that they are suitably strong and that
the steps are intact and not slippery and do not
wobble when someone climbs them. Ensure
someone provides supervision at all times.
Personal injury caused by falling from a height
or cuts (stepladders shutting accidentally).
Make sure any rolling ladders are positioned
securely, that they are suitably strong, that the
steps are intact and not slippery and that the
ladders are fi tted with handrails on either side of
the ladder and parapets on the landing.
Personal injury caused by falling from a height.
During all work carried out at a certain height
(generally with a difference in height of more
than two metres), make sure that parapets are
used to surround the work area or that individual
harnesses are used to prevent falls. The space
where any accidental fall may occur should be
free from dangerous obstacles, and any impact
upon falling should be cushioned by semi-rigid or
deformable surfaces.
Personal injury caused by falling from a height.
Make sure the workplace has suitable hygiene
and sanitary conditions in terms of lighting,
ventilation and solidity of the structures.
Personal injury caused by knocks, stumbling
etc.
Protect the appliance and all areas in the vicinity
of the work place using suitable material.
Damage to the appliance or surrounding
objects caused by falling splinters, knocks and
incisions.
SAFETY REGULATION
Key to symbols:
Failure to comply with this warning
implies the risk of personal injury, in some
circumstances even fatal
Failure to comply with this warning
implies the risk of damage, in some
circumstances even serious, to property,
plants or animals.

6 /
OVERVIEW
Handle the appliance with suitable protection
and with care.
Damage to the appliance or surrounding
objects from shocks, knocks, incisions and
squashing.
During all work procedures, wear individual
protective clothing and equipment.
Personal injury caused by electrocution, falling
splinters or fragments, inhalation of dust,
shocks, cuts, puncture wounds, abrasions,
noise and vibration.
Place all debris and equipment in such a way
as to make movement easy and safe, avoiding
the formation of any piles which could yield or
collapse.
Damage to the appliance or surrounding
objects from shocks, knocks, incisions and
squashing.
All operations inside the appliance must be
performed with the necessary caution in order to
avoid abrupt contact with sharp parts.
Personal injury caused by cuts, puncture
wounds and abrasions.
Reset all the safety and control functions
affected by any work performed on the appliance
and make sure they operate correctly before
restarting the appliance.
Explosions, fi res or asphyxiation caused by
gas leaks or an incorrect fl ue gas exhaust.
Damage or shutdown of the appliance caused
by out-of-control operation.
Before handling, empty all components that
may contain hot water, carrying out any bleeding if
necessary.
Personal injury caused by burns.
Descale the components, in accordance
with the instructions provided on the safety
data sheet of the product used, airing the
room, wearing protective clothing, avoid mixing
different products, and protect the appliance and
surrounding objects.
Personal injury caused by acidic substances
coming into contact with skin or eyes; inhaling
or swallowing harmful chemical agents.
Damage to the appliance or surrounding
objects due to corrosion caused by acidic
substances.
This appliance can be used by children
aged from 8 years and above and
person with reduced physical, sensory
or mental capabilities or lack of experience
and knowledge if they have been given
supervision or instruction concerning use of
the appliance in a safe way and understand
the hazards involved. Children shall not
play with the appliance. Cleaning and user
maintenance shall not be made by children
without supervision.
If you detect a smell of burning or smoke, keep
clear of the appliance, disconnect it from the
electricity supply, open all windows and contact
the technician.
Personal injury caused by burns, smoke
inhalation, asphyxiation.

/ 7
PRODUCT DESCRIPTION
26/10/15
1,5 bar
AUTO
Central Heating
COMFORT
12:30
40° 70°
10°
20,5° 3
00 02 04 06 08 10 12 14 16 18 20 22 24
1 2 3 4
a
5
b
6
b
7
c
98 10 11
CONTROL PANNEL
Legend:
1. Display
2. WIFI button
(enable / disable / confi gure)
3. Domestic Hot Water adjustment button +/-
4. MODE button
(Operation mode selection summer/winter)
5. COMFORT button
6. ON/OFF button
7. Auto button (To activate Thermoregulation)
8. RESET button
9. Heating temperature adjustument button +/-
10. Keylock
11. Led Blue - Flame presence
Programming key
a. Esc button (Back)
b. Programming keys
c. Ok button programming key

8 /
PRODUCT DESCRIPTION
Overall viewDISPLAY
Date and time
26/10/15 12:30
Keylock active
D.H.W. set temperature and indication of
the set temperature level
42°
C.H. set temperature and indication of the
set temperature level
Warning scheduled maintenance
Heating operation set
Heating operation active
D.H.W. operation set
D.H.W. operation active
Flame detected with indication of power
used
Digital pressure gauge (bar)
Scrolling text displaying operation as
information
Central heating
Error wsignals
The display show the code and
description
ALERT
AUTO function activated
AUTO
Hot Water Comfort activated
COMFORT
CH Schedule programming
(set display: boiler base - see user’s menù)
CH Schedule programming
(set display: boiler complete - see user’s menù)
Internal temperature displayed for
set zone. (with bus device connected
- optional)
External temperature displayed
ECO mode
WIFI active
WIFI connected to the local network,
but without access to the server
WIFI not confi gured
Solar temperature probe connected -
option
26/10/15
1,5 bar
AUTO
Riscaldamento attivo
COMFORT
12:30
60° 82°
10°
20,5° 3
00 02 04 06 08 10 12 14 16 18 20 22 24
1. Flue connector
2. Air relief valve
3. C.H. Flow temperature probe
4. Main heat exchanger
5. Detection Electrode
6. Silencer
7. Secondary heat exchanger
8 Condensate trap
9. C.H. pressure relief valve
10. Gas valve
12. C.H. circuit fi lter
13. Modulating circulation Pump with air release
valve
14. D.H.W. Flow switch
15. Diverter valve
16. Water pressure sensor
17. C.H. Return temperature probe
18. Modulating Fan
20. Combustion Analysis Test Point
1
2
5
6
8
9
10
12
13
14
15
16
17
20
18
4
7
3

/ 9
PRODUCT DESCRIPTION
Overall Dimensions
Minimum clearances
In order to allow easy access to the boiler for maintenance
operations, The boiler must be installed in accordance with the
clearances stated below.
A. Central Heating Flow
B. Domestic Hot Water Outlet
C. Gas Inlet
D. Domestic Cold Water Inlet
E. Central Heating Return
28
745
200
150
315 (24)
385 (30-35)
120 120
200
180
65 6567 67
25745
385 - mod. 30-35
450
053
003
50 50

10 /
INSTALLATION
Reference Standards
In the United Kingdom, the installation and initial start-up of the
boiler must be by a Gas Safe registered installer in accordance
with the installation standards currently in effect, as well as with
any and all local health and safety standards i.e. Gas Safe.
In the Republic of Ireland the installation and initial start-up of
the appliance must be carried out by a Competent Person in
accordance with the current edition of I.S.813 “Domestic Gas
Installations” and the current Building Regulations, reference
should also be made to the current ETCI rules for electrical
installation.
The installation of this appliance must be in accordance with
the relevant requirements of the Local Building Regulations,
the current I.E.E. Wiring Regulations, the by-laws of the local
authority, in Scotland, in accordance with the Building Standards
(Scotland) Regulation and Health and Safety document No. 635,
“Electricity at Work Regulations 1989” and in the Republic of
Ireland with the current edition of I.S. 813 and the Local Building
Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-
hazardous and no special precautions are required when
servicing.
Codes of Practice
Installation should also comply with the following British
Standards Code of Practice (refer to the most recent version):
BS 7593: Treatment of water in domestic hot water
central heating systems
BS 5546: Installation of hot water supplies for
domestic purposes
BS 5440-1: Flues
BS 5440-2: Air supply
BS EN 12831 - BS EN 14336:
Forced circulation hot water systems
BS 6798: Installation of gas fi red hot water boilers
of rated input not exceeding 70kW
BS 6891: Installation of low pressure gas pipes up to 28mm
BS 7671: IEE Wiring Regulations
BS 4814: Specifi cation for expansion vessels
BS 5482: Installation of L.P.G.
Technical Bulletin TB143 Flue Gas Analysis
and in the Republic of Ireland in accordance with the following
codes of practice:
I.S. 813 Domestic Gas Installations
Avoid installing the boiler where the air inlet can be polluted
by chemical products such as chlorine (swimming pool area), or
ammonia (hair dresser), or alkalin products (launderette).
Flue
Detailed information on fl ue assembly can be found in the
“ section.Connecting the Flue”
The boiler must be installed so that the fl ue terminal is exposed
to the free passage of external air at all times and must not be
installed in a place likely to cause nuisance. It must not be
allowed to discharge into another room or space such as an
outhouse or closed lean-to.
Condensing boilers have a tendency to form a plume of water
vapour from the fl ue terminal due to the low temperature of
the fl ue gasses. The terminal should therefore be located with
due regard for the damage or discolouration that may occur
to building within the vicinity and consideration must also be
given to adjacent boundaries, openable windows should also
be taken into consideration when siting the fl ue.
The minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical fl ue terminal
NOTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY CAUSE A TO
NUISANCE AND POSITIONED ENSURE THAT PRODUCTS OF COMBUSTION DO TO
NOT DISCHARGE ACROSS A BOUNDARY
It may be necessary to protect the terminal with a guard, if this
is the case it will be necessary to purchase a stainless steel
terminal guard. Reference should be made to the Building
Regulations for guidance.
Ventilation
The room in which the boiler is installed does not require
specifi c ventilation. If the boiler is installed in a cupboard or
compartment ventilation is not required for cooling purposes.

/ 11
INSTALLATION
Gas Supply
The gas installation and tightness testing must be in accordance
with the requirements of BS6891. Ensure that the pipe size is
adequate for demand including other gas appliances on the
same supply.
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and
must be in accordance with current I.E.E. regulations. It must
also be possible to be able to completely isolate the appliance
electrically. Connection should be via a 3 amp double pole fused
isolating switch with contact separation of at least 3mm on both
poles. Alternatively, a fused 3 amp, 3 pin plug and unswitched
socket may be used, provided it is not used in a room containing
a bath or shower. It should only supply the appliance.
Water Supply
The boiler is suitable for sealed systems only. The maximum
working pressure for the appliance is 6 bar. All fi ttings and
pipework for the appliance should be of the same standard. If
there is a possibility of the incoming mains pressure exceeding 6
bar, particularly at night, then a suitable pressure limiting valve
must be fi tted.
The boiler is designed to provide hot water on demand to
multiple outlets within the property. If there is a requirement
for greater demands, for example if the boiler has several
bathrooms and cloakrooms, a vented or unvented hot water
storage system may be used.
Showers
Any shower valves used with the appliance should be of a
thermostatic or pressure balanced type. Refer to the shower
manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given
in BS 7593 (Treatment of water in domestic hot water central
heating systems); the following notes are given for general
guidance.
If the boiler is installed on an existing system, any unsuitable
additives must be removed.
Under no circumstances should the boiler be fi red before the
system has been thoroughly fl ushed; the fl ushing procedure
must be in line with BS 7593.
We highly recommend the use of a fl ushing detergent
appropriate for the metals used in the circuit.
In hard water areas or where large quantities of water are in the
system the treatment of water to prevent premature scaling of
the main exchanger is necessary.
The formation of scale heat compromises the effi ciency of the
thermic exchanger because small areas of scale cause a high
increase of the temperature of the metallic walls and therefore
add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it
is necessary to treat the water with an appropriate corrosion
inhibitor.
Any treatment of water by additives in the system for frost
protection or for corrosion inhibition has to be absolutely
suitable for all metals used in the circuit.
The use of a corrosion inhibitor in the sysem is recommended
to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check
carefully that they are compatible with the metals used in the
circuit.
ARISTON suggests the use of suitable anti-freeze products,
which will prevent rust and incrustation taking place.
Periodically check the pH balance of the water/anti-freeze
mixture of the boiler circuit and replace it when the amount
measured is out of the range stipulated by the manufacturer (7
< pH < 8).
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under-fl oor systems, the use of plastic pipes without protection
against penetration of oxygen through the walls can cause
corrosion of the systems metal parts (metal piping, boiler etc),
through the formation of oxides and bacterial agents.
To prevent this problem it is necessary to use pipes with an
“oxygen proof barrier”, in accordance with standards DIN
4726/4729. If pipes of this kind are not used, keep the system
separate by installing heat exchangers of those with a specifi c
system water treatment.
Ariston suggests the installation of a magnetic fi lter on every
installation.
IMPORTANT
Failure to carry out the water treatment procedure will
invalidate the appliance warranty.
System Controls
The boiler is electrically controlled and is suitable for most
modern electronic time and temperature controls. The addition
of such external controls can be benefi cial to the effi cient
operation of the system. The boiler connections for external
controls are 12V DC and so only controls of 12V DC that have
voltage free contacts should be used. (page 25).
ARISTON supply a range of wired and wireless system controls.
Contact your supplier for more details.
Location
The boiler can be installed on any suitable internal wall
(suitable sound proofi ng may be required when installing
onto a stud partition wall). Provision must be made to allow
for the correct routing of the fl ue and siting of the terminal to
allow the safe and effi cient removal of the fl ue products. A
compartment or cupboard may be used provided that it has
been built or modifi ed for this purpose. It is not necessary to
provide permanent ventilation for cooling purposes. Detailed
recommendations are given in BS 5440 Part 2. If it is proposed
that it is to be installed in a timber framed building then reference
should be made to IGEM Document, IGE/UP/7 or advice sought
from Gas Safe.
Where a room sealed appliance is installed in a room
containing a bath or shower, the appliance and any electrical
switch or appliance control, utilising mains electricity should
be situated specifi cally in accordance with current IEE Wiring
Regulations.
For unusual locations, special procedures may be necessary.
BS 6798 gives detailed guidance on this aspect.
Codensate Discharge
The condensate discharge hose from the boiler must have
a continuous fall of 2.5o and must be inserted by at least
50mm into a suitable acid resistant pipe - e.g. plastic waste or

12 /
INSTALLATION
overfl ow pipe. The condensate discharge pipe must have a
minimum diameter of 22mm, must have a continuous fall and
preferably be installed and terminated to prevent freezing.
The discharge pipe must be terminated in a suitable position:
i) Connecting into an internal soil stack (at least 450mm above
the invert of the stack). A trap giving a water seal of at least
75mm must be incorporated into the pipe run, there also
must be an air beak upstream of the trap.
ii) Connecting into the waste system of the building such as
a washing maching or sink trap. The connection must be
upstream of the washing machine/sink. If the connection is
downstream of the waste trap then an additional trap giving
a minimum water seal of 75mm and an air break must be
incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level
iv) Into a soakaway
Note: If any condensate pipework is to be installed externally
then it should be kept to a minimum and be insulated with a
waterproof insulation and have a continuous fall. The total
length of external pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be
found below.
1. Internal termination of condensate drainage pipe to internal
stack.
2. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste) and condensate siphon.
3. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste - proprietary fi tting).
4. External termination of condensate drainage pipe via
condensate siphon
Tund si h
trap
T i hund s
trap
T i hund s
Tund si h
Ext l i l gth erna p pe en
ma 3 mex. tres
( t i l t )mus be nsu a ed
Condensate Discharge
Push fi t the fl exible condensate pipe into the outlet spigot on
the appliance. Cut to length and locate outlet into a tundish

14 /
INSTALLATION
Gas connection
Make sure, using the labels on the packaging and the data plate
on the appliance itself, that the boiler is in the correct country
and that the gas category for which the boiler was designed
corresponds to one of the categories available in the country
where it will be used.
The gas supply piping must be created and measured out in
compliance with specifi c legal requirements and in accordance
with the maximum power of the boiler.
Check that the supplied gas corresponds to the type of gas for
which the boiler was designed (see the data plate located on
the appliance itself).
It is also important to check that the pressure of the gas
(methane or LPG) you will be using to feed the boiler is suitable,
because if it is insuffi cient the power may be reduced, causing
inconvenience for the user.
Water connection
The illustration below shows the connections for the water and
gas attachments of the boiler. See valves confi guration on page
13.
Check that the maximum water mains pressure does not exceed
6 bar; if it does, a pressure reducing valve must be installed.
For the measuring of the pipes and of the heating bodies in the
heating system, the residual head value should be calculated
as a function of the requested fl ow rate, in accordance with the
values shown in the circulation pump graph.
Legend:
A. Central heating Flow
B. Domestic Hot Water Outlet
C. Gas Inlet
D. Domestic Cold Water Inlet
E. Central Heating Return
F. Safety Valve Discharge
H. Drain Valve
I. Condensate discharge
A
B
C
E
D
H
F
I
Instructions for removing the housing and inspecting the
appliance.
Before carrying out any work on the boiler, switch off the power
supply using the external bipolar switch and close the gas tap.
To access the inside of the boiler:
- unscrew the two screws from the front panel ( ), pull the panel a
forwards and uncouple it from the upper pins ( ),b
- pivot the electronic unit by pulling it forwards ( ).c
(a)
CAUTION!!
REMOVE ONLY THE SCREWS SHOWN
IN THE PICTURE
(b)

/ 15
INSTALLATION
To calculate the size of the heating installation, refer to the
"Available pressure" graph below.
Graph representing the available circulation pump pressure
∆T20 oC
0
100
200
300
400
500
600
0 200 400 600 800 1000 1200
mbar
l/h
(c)
Underfl oor heating
For appliances with underfl oor heating, it is possible but not
necessary to fi t a safety thermostat onto the underfl oor heating
outlet. For the electrical connection of the thermostat see the
section on “Electrical connections - pages 26”.
If the outlet temperature is too high, the boiler will stop both
domestic hot water and the heating production and the error
code 1 16 “fl oor thermostat contact open” will appear on the
display. The boiler will restart when the thermostat is closed
during automatic resetting.
If the thermostat cannot be installed, the underfl oor heating
equipment must be protected by a thermostatic valve, or by a by-
pass to prevent the fl oor from reaching too high a temperature.

/ 17
INSTALLATION
Connecting the Flue
Flue System
The provision for satisfactory ue termination must be made as
described in BS 5440-1.
The appliance must be installed so that the ue terminal is ex-
posed to outdoor air.
The terminal must not discharge into another room or space
such as an outhouse or lean-to.
It is important that the position of the terminal allows a free pas-
sage of air across it at all times.
The terminal should be located with due regard for the damage
or discolouration that might occur on buildings in the vicinity, it
must also be located in a place not likely to cause nuisance.
In cold or humid weather water vapour may condense on lea-
ving the ue terminal.
The effect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above
ground or above a at roof to which people have access, then a
suitable stainless steel terminal guard must be tted.
The minimum acceptable spacing from the terminal to obstruc-
tions and ventilation openings are speci ed in Fig. 1.
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
Fig. 1
11 8 mm
1 50 mm
M u L = inim m ength 500 mm
1 80 mm
Fig. 2

18 /
INSTALLATION
Warning
The exhaust gas ducts must not be in contact with or close
to in ammable material and must not pass through building
structures or walls made of in ammable material.
When replacing an old appliance, the ue system must be
changed.
Important
Ensure that the ue is not blocked.
Ensure that the ue is supported and assembled in accordance
with these instructions.
150 mm
118
* Min slope: 1 ˚
1 = 17.5mm per metre˚
150 mm
* pente
Installation without extension
Installation with extension
Level
Level
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents:
1x Silicone O-Ring (60mm)
1x Elbow (90°)
2x Wall Seals (Internal & External)
1x Flue Pipe including Terminal (1 metre - 60/100)
2x Flue Clamps
4x Screws
2x Seals
Once the boiler has been positioned on the wall, t the rubber
ue seal into the internal ue turret (see diagram opposite),
Insert the elbow into the socket and rotate to the required
position. note: It is possible to rotate the elbow 360° on its
vertical axis.
Using the ue clamp, seals and screws supplied (Fig 4) secure
the elbow to the boiler.
The 1 metre horizontal ue kit (3318073) supplied is suitable for
an exact X dimension of 753mm.
Measure the distance from the face of the external wall to
the face of the ue elbow (X - Fig 2), this gure must now be
subtracted from 753mm, you now have the total amount to be
cut from the plain end of the ue.
Draw a circle around the outer ue and cut the ue to the
required length taking care not to cut the inner ue, next cut the
inner ue ensuring that the length between the inner and outer
ue is maintained. (Fig 4).
e.g.
X = 555mm
753-555 = 198mm (Length to be cut from the plain end of the
ue).
Once cut to the required length, ensure that the ue is free from
burrs and reassemble the ue. If tting the ue from inside of
the building attach the outer wall seal to the ue terminal and
push the ue through the hole, once the wall seal has passed
through the hole, pull the ue back until the seal is ush with the
wall. Alternatively, the ue can be installed from outside of the
building, the outer seal being tted last.
Should the ue require extending, the ue connections are push
t, however, one ue bracket should be used to secure each
metre of ue.
Note: See table for maximum and minimum ue runs.
slope
Fig. 3
Note: A Plume management kit is available for 60/100
horizontal termination. Instructions for installation are
supplied with the Plume management kit.

/ 19
INSTALLATION
Fitting the 5” Flue
(Ø 80 / 125 Horizontal/vertical) Once the boiler has been positioned on the wall, it is necessary
to insert the Ø80/125 adaptor (Fig. 5) for both horizontal and
vertical ue runs into the boiler ue socket (not supplied with
ue kit - Part No 3318095).
Push the adaptor onto the boilers ue connection, grease the
seals then add extensions or elbows as required, secure the
adaptor, using the clamp and screws provided.
To t extensions or elbows it is rst necessary to ensure that
the lip seal is tted correctly into the inner ue, once veri ed,
it is simply necessary to push them together, no clamps are
necessary to secure the ue components.
Before proceeding to t the ue, ensure that the maximum ue
length has not been exceeded (See the tables) and that all
elbows and bends have been taken into consideration, for each
additional 90° elbow 1 metre must be subtracted from the total
ue length, and for each 45° 0.5 metres must be subtracted from
the total ue length (the height of the vertical adaptor and a 45°
bend can be seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical ue kit.
1 80 mm
Total length
of Vertical Kit
1240 mm
5" Adaptor
Part no: 3318095
* This length will vary
according to the type
of ashing installed
Useable length
of Vertical ue
575 mm*
Fig. 5
Clamp
Seal
Screws
Fig. 4
Fig. 6 Fig. 7

20 /
INSTALLATION
Fitting the Coaxial Flue
(Ø 60 / 100 Vertical)
Note: See table for maximum and minimum ue runs.
Contents:
1x Conical Adaptor (60/100mm)
1x Vertical Flue Kit (80/125mm)
The vertical ue kit is supplied with a specially designed
weather proof terminal tted, it can be used either with a at
roof or a pitched roof.
The Vertical ue kits useable lengths with the pitched roof
ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the maximum ue
length has not been exceeded (See the tables) and that all
elbows and bends have been taken into consideration, for each
additional 90° elbow 1 metre must be subtracted from the total
ue length, and for each 45° 0.5 metres must be subtracted from
the total ue length (the height of the vertical adaptor and a 45°
bend can be seen in Fig. 8).
Mark the position of the ue hole in the ceiling and/or roof (see
Fig. 7 for distance from wall to the centre of the ue).
Cut a 130mm diameter hole through the ceiling and/or roof and
t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
To connect the vertical ue kit directly to the boiler, place the
vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust
manifold and secure with the clamp, t the vertical adaptor onto
the vertical starter kit (note: there is no need to use a clamp to
secure this as it is a push t connection), the vertical ue kit must
then be inserted through the roof ashing, this will ensure that
the correct clearance above the roof is provided as the terminal
is a xed height.
Should extensions be required, they are available in 1 metre
(Part No. 3318077), 500mm (Part No. 3318078) and they must be
connected directly to the vertical starter kit before connecting
the adaptor to allow the vertical ue kit to be tted. In the event
that extension pieces need to be shortened, they must only be
cut at the male end and it must be ensured that the inner and
outer ue remain ush.
When utilising the vertical ue system, action must be taken
to ensure that the ue is supported adequately to prevent the
weight being transferred to the appliance ue connection by
using 1 ue bracket per extension.
When the ue passes through a ceiling or wooden oor, there
must be an air gap of 25mm between any part of the ue
system and any combustible material. The use of a ceiling
plate will facilitate this. Also when the ue passes from one
room to another a re stop must be tted to prevent the passage
of smoke or re, irrespective of the structural material through
which the ue passes.
1 80 mm
Vert Adaptor
(supplied with ue kit)
Vertical Starter
Part No: 3318079
* This length will vary
according to the type
of ashing installed
Total length
of Vertical Kit
1355 mm
Useable length
of Vertical ue
690 mm*
Fig. 7
Fig. 8

/ 21
INSTALLATION
Fitting the Twin Pipe (Ø80 / 80)
Note: See table for maximum and minimum ue runs.
Where it is not possible to terminate the ue within the distance
permitted for coaxial ues, the twin ue pipe can be used by
tting a special adaptor to the ue connector and using the
aperture for the air intake located on top of the combustion
chamber.
Always ensure that the ue is adequately supported, using one
ue bracket per extension and avoiding low points. (ARISTON
supply suitable clamps as Part No. 3318015).
To utilise the air intake it is necessary to:
1) Remove the top of the air intake by cutting it with a suitable
knife.
2) Insert the header on the tube or the elbow up until the lower
stop (you do not have to use the washer).
3) Insert the elbow/header in the boiler air intake hole and fasten
it with screws.
The twin ue pipes can be tted with or without additional elbows
and need no clamps, simply ensure that the lip seal is inserted
in the female end of the ue pipe and push the extension piece
fully into the previous section of ue pipe or elbow, check that
the lip seal is not dislodged when assembling the ue (greasing
the seal will aid assembly).
Twin pipe can also be converted back to Coaxial ue to enable
vertical termination with a coaxial kit by using the pipe bridge
(Twin - Coaxial Adaptor - Part No. 3318089). When running the
twin ue pipe vertically.
It is not possible to terminate concentrically horizontally.
Termination is only possible with separate air and exhaust
terminals.
When siting the twin ue pipe, the air intake and exhaust
terminals must terminate on the same wall, the centres of the
terminals must be a minimum of 280 mm apart and the air intake
must not be sited above the exhaust terminal (refer to Fig. 10).
The air intake pipe can be run horizontally, however, the terminal
and the nal 1 metre of ue must be installed either horizontally
or with a slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be
constructed of insulated pipe to prevent condense forming on
the outside of the tube.
Ensure the exhaust tube has a minimum fall back to the boiler of
1 / metre (1 = 17.5mm/metre)˚ ˚
The maximum permissible ue length for twin ue is dependent
on the type of run used (see table on page 23).
For further information relating to ue runs not illustrated, please
contact the Technical Department 0333 240 7777.on

22 /
INSTALLATION
For coaxial systems, the maximum development value,
mentioned in the table below also takes into account an elbow.
For twin ue systems the maximum development value,
mentioned in the table includes the exhaust gas/air intake
terminal.
Twin ue systems outlets should respect the following
instructions:
1- Use the same ø 80 mm ue pipes for the air intakes and
exhaust gas ducts.
2- If you need to insert elbows in the air intake and exhaust gas
ducts, you should consider for each one the equivalent length
to be included in the calculation of developed length.
3- The exhaust gas duct should jut above the roof by at least 0.5
m.
4- The intake and exhaust gas ducts in Type C13 + C53 must be
installed on the same wall, or where the exhaust is vertical
and the air intake horizontal, the terminals must be on the
same side of the building.
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
195
105
120 180
Fig. 9
Fig. 10

/ 23
INSTALLATION
Table of ue gas exhaust duct lengths
S1 = Air intake S2 = Flue gas exhaust
S1 = S2 - Air intake and ue gas exhaust equal lengths
S1 + S2 - Air intake and ue gas exhaust unequal lengths
TYPE C13
TYPE C TYPE C33 53
TYPE C TYPE C33 33
FLUE TYPE
Maximum Extension
Exhaust-air (m) Diameter of pipe
(mm)
ALTEAS ONE NET
30 35
Coaxial System
C13
C33
C43
7 6 ø 60/100
C13
C33
C43
20 24 ø 80/125
Twin-pipe System
S1 = S2
ø 80/80
C13 30 = 30 23 = 23
C33 40 = 40 30 = 30
C43 30=30 23 = 23
C53 S1 + S2
60 45 ø 80/80

24 /
INSTALLATION
Electrical connections
For increased safety, ask a quali ed technician to perform a
thorough check of the electrical system.
The manufacturer is not responsible for any damage caused by
the lack of a suitable earthing system or by the malfunctioning
of the electricity mains supply.
Make sure that the system is able to withstand the maximum
power absorbed by the boiler (this is indicated on the appliance
data plate). Check that the section of the wires is suitable and is
not less 0,75 mm 2
The appliance must be connected to an ef ecient earthing
system if it is to operate correctly.
The power supply cable must be connected to a 230V-50Hz
network, where the L-N poles and the earth connection are all
respected.
Important!
In the event that the power supply cable must be changed,
replace it with one with the same speci cations.
Power supply cable
Important!
The appliance is supplied with a y-lead already
connected, this must be connected to a 240V supply fused
at 3 Amp and must facilitate completed electrical isolation of
the appliance, by use of a fused double pole isolator having a
contact separation of at least 3mm in all poles or alternatively
by means of a 3A fused three pin plug and unswitched
shuttered socket outlet both complying with BS1363.
The use of multiplugs, extension leads or adaptors is strictly
prohibited.
It is strictly forbidden to use the piping from the hydraulic,
heating and gas systems for the appliance earthing connection.
The boiler is not protected against the effects caused by
lightning. If the mains fuses need to be replaced, use 2A rapid
fuses.
Peripheral unit connection
To access peripheral unit connections carry out the following
steps:
- Disconnect the boiler from the power supply
- Remove the casing
- Rotate the control panel while pulling it forwards
- Unhook the two clips to have access to the peripherical
connections and the main P.C.B.
SWHV06
60 mm
N
L
BUS
T B
FLOOR
TA2
SE TNK SOL TA1
CN1
CUBE S NET (standard for CLAS NET ONE)
Wi iF Room Thermost ta
SENSYS
Remot t tie onC rol op( on)
Ou doort
Sensor
Room Thermost ta
1
( )op onti
OK
1 2 3 4 5 6 7
Peripheral connections:
BUS = Remote control connection
FLOOR/TA2 = the under oor heating thermostat or the room
thermostat 2 (selected via parameter 223)
SE = the external sensor.
SOL = Solar temperature probe
TA1 = the room thermostat 1
WARNING!
BEFORE PERFORMING ANY WORK ON
THE BOILER, FIRST DISCONNECT IT FROM
THE ELECTRICAL POWER SUPPLY USING
THE EXTERNAL BIPOLAR SWITCH AND
REMOVE THE FUSE.
BUS
T B
TA2 S NE T K SOL T 1A

/ 25
INSTALLATION
Room Thermostat / Remote Clock Connection
To connect a room thermostat, it is necessary to:
1. Open the control panel
2. Loosen the cable clamp using a screwdriver and insert the
wires leading from the room thermostat
3. Connect the wires to the terminals as indicated in the gure
below, removing the link
4. If a remote time clock is to be tted, using a volt free switching
time clock connect the switching wires from the time clock
following points 1 - 3 above
5. If using an external time clock and room thermostat, these
must be connected in series as shown in diagram C,
6. Ensure that they are well connected and not subject to stress
when the control panel is closed
DO NOT CONNECT 240V TO ANY PERIPHERAL CONNECTIONS
Cube Room sensor (wireless) Connection
To connect a room thermostat, read the instructions present in
the kit delivered with the gas boiler.
DO NOT CONNECT 240V TO ANY PERIPHERAL CONNECTIONS
Connector TA on P BC
( o o tage s itchingl w v l w )
Connector TA on P BC
( o o tage s itchingl w v l w )
Connector TA on P BC
( o o tage s itchingl w v l w )

26 /
INSTALLATION
Electrical diagram
For increased safety, ask a quali ed technician to perform a
thorough check of the electrical system.
The manufacturer is not responsible for any damage caused by
the lack of a suitable earthing system or by the malfunctioning
of the electricity mains supply.
BUS
T B
FLOOR
TA2
230 V
SE TNK SOL TA1
230 V 230 V 230 V 230 V 230 V
N L
NL
GAS VA ELV
Modula nti g
fan
Bk
Bk
Modula n c rcula onti g i ti
pump
Br
Bk
Gry
Bk
Bl
Br
Bk
D H W. . .
o s cw wit h
Water
pressure sensor
Diverter valve
Bl
Rd
Wh
Br
Rd
Bl Bl
C. .H return
t tempera ure
probe
C. . wH o
t tempera ure
probe
Rd
Det ti g itiec on/I n on
elec rodet
GAT WE AY WIFI
Bk= Black
Rd = Red
Gr = Green
Bl = Blue
Br = Brown
Wh = White
Gry = Grey

/ 27
COMMISSIONING
Initial preparation
Ariston Thermo UK Ltd support the benchmark initiative.
On pages 77 and 78 of this manual the Benchmark
Commissioning Checklist and Service interval Record can be
found. It is important that this is completed in the presence of
your customer, they are shown how to use it, and it is signed by
them. Please instruct your customer that they must have this
manual with them whenever they contact a service engineer
or us.
Preliminary electrical system checks to ensure electrical safety
must be carried out by a competent person i.e. polarity, earth
continuity, resistance to earth and short circuit.
Electricity supply
- Check that the voltage and frequency of the electricity supply
correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is effi cient.
Filling the Heating System:
ATTENTION!!
CONNECT THE PIPE OF CONDENSATE DISCHARGE
BEFORE REFILLING AND THE DE-AERATION OF THE
HEATING CIRCUIT.
Remove the front casing panel and lower the control panel as
described on page 14.
Open the central heating flow and return cocks supplied with
the connection kit;
Open the manual air vent positioned at the side of the primary
exchanger . The valve is already connected to a discharge (2)
pipe related to the condensate trap.
Close all air release valves on the central heating system;
Gradually open the valves at the filling point (filling loop) until
water is heard to flow, do not open fully;
Open each air release tap starting with the lowest point and
close them only when clear water free of air is visible;
Continue filling the system until at least 1.5 bar registers on the
pressure gauge;
Inspect the system for water tightness and remedy any leaks
discovered.
IMPORTANT!
MANUALLY VENT THE HEAT EXCHANGER THE MANUAL AIR VENT AILURE AT . F
TO VENT ADEQUATELY MAY DAMAGE THE HEAT EXCHANGER (PAGE 8, LEGEND
2).
Filling of the DHW System:
Close all hot water draw off taps;
Open the cold water inlet cock supplied with the connection kit;
Slowly open each draw off tap and close them only when clear
water, free of bubbles, is visible.
Gas Supply:
Inspect the entire installation including the gas meter and test
for tightness. The entire installation should be in accordance
with the relevant standards. In GB this is BS 6891 and in IE this
is the current edition of I.S.813.
The connection on the the appliance is a 15mm 22mm on (
35Kw) nut and olive located at the rear of the gas service cock.
If the gas supply serves other appliances, ensure that an
adequate supply is available both to the boiler and the other
appliances when they are in use at the same time.
Pipe work must be of an adequate size. The final pipe size
must not be smaller than the appliance inlet size.
Open the gas cock (supplied with the connection kit) to the
appliance and check the gas connection on the appliance for
leaks.
Water Treatment:
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given
in BS 7593 (Treatment of water in domestic hot water central
heating systems); the following notes are given for general
guidance;
If the boiler is installed on an existing system, any unsuitable
additives must be removed;
Under no circumstances should the boiler be fired before the
system has been thoroughly flushed; the flushing procedure
must be in line with BS7593.
Firstly fill the central heating system with the power off, and
flush through cold, fill the central heating system again, adding
a flushing detergent, run the boiler on central heating until it
reaches its operating temperature and flush the system, refill
the system with a suitable corrosion inhibitor,
NOTE: FAILURE CARRY OUT THE FLUSHING PROCEDURE WILL RESULT IN THE TO
WARRANTY BECOMING VOID .
2

28 /
COMMISSIONING
FIRST IGNITION OPERATION
1. Check the electrical
supply.
Complete ...........................................
Date . . . . . . . . . . . . . . . . . . . . . . . .
Installer . . . . . . . . . . . . . . . . . . . . .
2. Check the type of gas (change the gas if necessary durung
the Calibration procedure point 8).
Complete ...........................................
3. Check the gas tightness.
Complete ...........................................
7. Measure the gas inlet
static pressure.
Complete ...........................................
4. Check the Flue
Complete ...........................................
5. Fill the installation.
Complete ...........................................
6. Check the hydraulic
water tightness.
Complete ...........................................
8. Carry out the deaeration cycle and automatic calibration procedure (change gas type, if
necessary). Adjusting the CO2 by pressing the RESET button for 5 sec..
Complete ...........................................
9. Set the heating power.
Complete ...........................................
10. Balance the central
heating circuit.
Complete ...........................................
11. Check the operation in
DHW mode.
Complete ...........................................
12. Adjust DHW ow rate on
the boiler (if necessary).
Complete ...........................................
13. Check gas rate.
Complete ...........................................
14. Check the ionisation
current.
Complete ...........................................
15. Explain to the end user
the working of the boiler.
Complete ...........................................
Produktspecifikationer
Varumärke: | Ariston Thermo |
Kategori: | Pannor & pannor |
Modell: | Alteas One Net |
Färg på produkten: | Zwart |
Husmaterial: | Kunststof |
Strömförsörjning: | 12VDC 1A |
Medföljande kablar: | LAN (RJ-45) |
Snabbstartsguide: | Ja |
Antal Ethernet LAN (RJ-45)-portar: | 1 |
DC-spänningsingång: | 12 V |
Certifiering: | FCC, UL\nCablelabs\nRoHS |
Anslutning för nätadapter: | Ja |
Kabelteknik: | 10/100 |
Typ av antenn: | Intern |
Ström LED: | Ja |
Kompatibla operativsystem: | Windows 8/Windows 7/ Windows Vista™, Service Pack 1 or\nlater/ Windows®XP, Service Pack 2 or later/ Mac®10.4 or\nlater (Ethernet Connection Only) UNIX®Linux® |
Modemhastighet: | 1440000 Kbit/s |
Uppströms datahastighet: | 143 Mbit/s |
Nedströms datahastighet: | 680 Mbit/s |
Drifttemperatur (TT): | 0 - 40 °C |
Relativ luftfuktighet i drift (VV): | -30 - 70 procent |
Behöver du hjälp?
Om du behöver hjälp med Ariston Thermo Alteas One Net ställ en fråga nedan och andra användare kommer att svara dig
Pannor & pannor Ariston Thermo Manualer

6 Oktober 2024

29 Augusti 2024

27 Augusti 2024

27 Augusti 2024

26 Augusti 2024

23 Augusti 2024

23 Augusti 2024

22 Augusti 2024

21 Augusti 2024

21 Augusti 2024
Pannor & pannor Manualer
- Pannor & pannor Electrolux
- Pannor & pannor ATAG
- Pannor & pannor Bosch
- Pannor & pannor AEG
- Pannor & pannor Philips
- Pannor & pannor Panasonic
- Pannor & pannor BEKO
- Pannor & pannor Inventum
- Pannor & pannor Junkers
- Pannor & pannor Nefit
- Pannor & pannor Remeha
- Pannor & pannor Siemens
- Pannor & pannor Whirlpool
- Pannor & pannor Vaillant
- Pannor & pannor A.O. Smith
- Pannor & pannor Adler
- Pannor & pannor ACV
- Pannor & pannor Arcelik
- Pannor & pannor GE
- Pannor & pannor Orbegozo
- Pannor & pannor Fagor
- Pannor & pannor Gorenje
- Pannor & pannor Hitachi
- Pannor & pannor Teka
- Pannor & pannor Cata
- Pannor & pannor Hisense
- Pannor & pannor Vox
- Pannor & pannor Hotpoint
- Pannor & pannor Sencor
- Pannor & pannor Midea
- Pannor & pannor De Dietrich
- Pannor & pannor Concept
- Pannor & pannor Solac
- Pannor & pannor Svan
- Pannor & pannor Daikin
- Pannor & pannor Truma
- Pannor & pannor Intergas
- Pannor & pannor Eldom
- Pannor & pannor Guzzanti
- Pannor & pannor Stiebel Eltron
- Pannor & pannor Infiniton
- Pannor & pannor Buderus
- Pannor & pannor Dometic
- Pannor & pannor Elco
- Pannor & pannor Dimplex
- Pannor & pannor Masterwatt
- Pannor & pannor Nibe
- Pannor & pannor Ferroli
- Pannor & pannor Haier
- Pannor & pannor Elba
- Pannor & pannor Corberó
- Pannor & pannor Kelvinator
- Pannor & pannor ETA
- Pannor & pannor Mora
- Pannor & pannor Buffalo
- Pannor & pannor Viessmann
- Pannor & pannor Franke
- Pannor & pannor Camry
- Pannor & pannor Qlima
- Pannor & pannor TTulpe
- Pannor & pannor Jocel
- Pannor & pannor Worcester
- Pannor & pannor Atlantic
- Pannor & pannor Technika
- Pannor & pannor Plieger
- Pannor & pannor Bulex
- Pannor & pannor Tesy
- Pannor & pannor Waeco
- Pannor & pannor AWB
- Pannor & pannor HTW
- Pannor & pannor Quooker
- Pannor & pannor Edilkamin
- Pannor & pannor OSO
- Pannor & pannor Kunft
- Pannor & pannor La Nordica
- Pannor & pannor Clage
- Pannor & pannor Noveen
- Pannor & pannor Joven
- Pannor & pannor Daalderop
- Pannor & pannor Cointra
- Pannor & pannor Baxi
- Pannor & pannor Rommer
- Pannor & pannor Eccotemp
- Pannor & pannor Biasi
- Pannor & pannor Quantum
- Pannor & pannor Morco
- Pannor & pannor Thermor
- Pannor & pannor Sentry
- Pannor & pannor LEMET
- Pannor & pannor Duwaco
- Pannor & pannor Wesen
- Pannor & pannor Khind
- Pannor & pannor Wagaparts
- Pannor & pannor SolarEdge
- Pannor & pannor IQE
- Pannor & pannor Wahlbach
- Pannor & pannor LERAN
- Pannor & pannor Ygnis
- Pannor & pannor Dux
- Pannor & pannor Intellihot
- Pannor & pannor Wijas
- Pannor & pannor Airthereal
- Pannor & pannor Thermoflow
- Pannor & pannor IStore
- Pannor & pannor Apricus
- Pannor & pannor Aquamarin
- Pannor & pannor Rinnai
- Pannor & pannor Sime
- Pannor & pannor Hydrotherm
- Pannor & pannor Kospel
- Pannor & pannor Amtrol
- Pannor & pannor Neopower
- Pannor & pannor Gleamous
- Pannor & pannor AquaMAX
- Pannor & pannor My-PV
- Pannor & pannor EvoHeat
- Pannor & pannor Longvie
- Pannor & pannor Rheem
- Pannor & pannor Mission Air
- Pannor & pannor Solahart
- Pannor & pannor ENEFT
- Pannor & pannor AquaTech
- Pannor & pannor Imarflex
- Pannor & pannor MicroHeat
- Pannor & pannor Noritz
- Pannor & pannor BTI Aqua-Solutions
Nyaste Pannor & pannor Manualer

1 April 2025

31 Mars 2025

13 Mars 2025

10 Mars 2025

10 Mars 2025

4 Mars 2025

4 Mars 2025

27 Februari 2025

27 Februari 2025

27 Februari 2025