Hoffman A36X2E5410 Bruksanvisning

Hoffman Eluttag A36X2E5410

Läs nedan 📖 manual på svenska för Hoffman A36X2E5410 (4 sidor) i kategorin Eluttag. Denna guide var användbar för 3 personer och betygsatt med 4.5 stjärnor i genomsnitt av 2 användare

Sida 1/4
Single and Mulit-Door Disconnect Enclosure
A26M1
© 2010 Pentair Technical Products PH 763 422 2211 • hoffmanonline.com 87573762Rev. D P/N 87573563
ENCLOSURE ALTERATIONS AND HANDLING
Hoffman cannot assure the safety or effectiveness of any alterations or additions
not made by Hoffman Enclosures Inc. However, the following information
may be helpful. These instructions do not eliminate the need to consult with
equipment manufacturers and to observe all regulatory agency procedures and
safe practices to assure the proper electrical and mechanical function of Hoffman
products in each particular application.
REPAINTING
See “Instructions for Repainting Hoffman Standard Paint Finishes”, part number
23155002. Available at www.hoffmanonline.com.
STRAIGHTENING STUDS WHEN INSTALLING PANEL
Simply position the panel on the studs that line up properly and pry the other
studs into position with a suitable screwdriver inserted through the panel holes.
REMOVING HINGE PINS FROM CONTINUOUS HINGES
This operation requires at least two people. It is best accomplished by using a
small diameter punch to drive the hinge pin toward the bottom of the enclosure.
When the hinge pin protrudes about two inches below the bottom hinge barrel,
bend the end of the pin 1805 so it is shaped like the letter “J”. Use an electric
or air powered vibrating hammer tted with a tool which has a hole in the end
to t over the hinge pin. Drive the hinge pin out while opening and closing the
door. Reinstall the hinge pin, straighten the pin, and drive it in with the vibrating
hammer while opening and closing the door. Most hinge pins have one end
chamfered; start the chamfered end rst when reinstalling the pin.
PRINT POCKET OPTIONS
The print pocket on the door can be inverted or removed entirely.
LIFTING ENCLOSURES BY EYEBOLTS
To lift an enclosure which has eyebolts or mounting feet, use all the eyebolts and
top mounting feet provided. Arrange the chains or cables with spreader bars so
the chains or cables are lifting straight up from the eyebolts or top mounting feet.
© 2010 Pentair Technical Products PH 763 422 2211 • hoffmanonline.com 87573762- 2 -
LOCKWASHER USAGE
1. Install the enclosed external toothed lockwasher under one of
the nuts securing the panel to ensure bonding between the panel
and enclosure.
HUB INSTALLATION
1. Use only CSA approved, watertight, rigid conduit hubs that are
designed to t into standard conduit openings.
2. Conduit entry can be made in the top or bottom end or through
the side walls of this enclosure.
3. Use a hole saw or Greenlee-type punch to cut the required
holes (see the table below for the hole size and at surface area
required).
4. Install the hub according to the hub manufacturer’s instructions.
Trade Size of Conduit Recommended Diameter of
Opening
Recommended Minimum
Diameter of Flat Surface
1/2 7/8 1-3/16
3/4 1-3/32 1-1/2
1 1-23/64 1-7/8
1-1/4 1-23/32 2-3/8
1-1/2 1-31/32 2-5/8
2 2-15/32 3-1/4
2-1/2 3 3-3/4
3 3-41/64 4-7/16
3-1/2 4-5/32 4-15/16
4 4-11/16 5-7/16
5 5-25/32 6-3/8
6 6-29/32 8
Units: Inch
© 2010 Pentair Technical Products PH 763 422 2211 • hoffmanonline.com 87573762- 3 -

Produktspecifikationer

Varumärke: Hoffman
Kategori: Eluttag
Modell: A36X2E5410

Behöver du hjälp?

Om du behöver hjälp med Hoffman A36X2E5410 ställ en fråga nedan och andra användare kommer att svara dig




Eluttag Hoffman Manualer

Eluttag Manualer

Nyaste Eluttag Manualer