Product Documentation
IP Router
Art. No.: IPR 200 REG
ALBRECHT JUNG GMBH & CO. KG
Volmestrasse 1
D-58579 Schalksmühle
GERMANY
Telephone: +49 2355 8060
Fax: +49 2355 806204
e-mail: kundencenter@jung.de
Internet: www.jung.de
2
1. Safety instructions
Electrical equipment must only be installed and mounted by qualified
electricians.
When connecting KNX interfaces, detailed knowledge through KNX training is
required.
The manufacturer shall not be liable for any costs or damage incurred by the
user or third party through the use this device, misuse or disturbances of the
device or user equipment.
Any unauthorized changes and modifications to the equipment will render the
warranty null and void!
The manufacturer shall not be liable for damage arising from improper use.
2. Installation and connection
Operation of the KNXnet/IP router requires:
One of the following power supplies with at least 1 Watt power output:
Safety extra-low voltage of 20 to 30 VDC (direct voltage)
Safety extra-low voltage of 16 to 24 VAC (alternating voltage)
"Power over Ethernet" (IEEE 802.3af), Class 1
A 10/100 Mbit compatible Ethernet connection
A KNX/EIB bus connection
3. Commissioning
3.1 Description of functions
The interface has the following functionalities:
LED display for communication, Ethernet communication and programming
mode
Configuration via ETS
Max. 5 connections to IP terminal devices, e.g. for simultaneous visualisation
and configuration
Supply from network line Power-over-Ethernet to IEEE 802.3af , through – –
separate voltage supply or the auxiliary voltage output of the KNX voltage
supply.
Electrical isolation between KNX and IP network
3.2 Configuration
In the ETS project, an appropriate device must be created and configured.
Activate programming mode: Press programming button.
The programming LED lights up.
Program a physical address with the aid of the ETS.
The programming LED goes out .
Label the device with the physical address.
Load application data into the device with the aid of the ETS.
3
3.3 Physical address of the data interface
A direct connection to the KNX can be established from a PC or other data
processing equipment (e.g. visualisation units) in the network via an IP data network
and the KNX IP interfaces. This allows access to the bus from any point in the IP
data network.
The ETS3 (from version 3.0c) enables the configuration of KNX installations via the
existing IP data network and uses the IP interface such as a conventional serial
RS232 or USB data interfaces for communication with the bus. This also includes the
downloading of bus devices or the group bus monitor function (no support of the bus
monitor mode).
For communication via KNXnet/IP Tunnelling and / or ObjectServer, the device must
use a virtual physical address for each connection. These additional physical
addresses must not be identical with the physical address of the device and must not
be used by any other bus device either. In the ETS, the virtual physical addresses
should be allocated by dummy devices. The additional addresses for the KNXnet/IP
Tunnelling can either be assigned manually in the ETS by the communication
settings or automatically by the device itself. To configure the communication
interface (physical interface of the first tunnel connection) in the ETS 5, the following
steps must be carried out.
In ETS 5, on the tab, open the subitem Bus Connections -> Interfaces
If the IP interface is online in the same network as the commissioning PC, this will
already be shown here, otherwise it can be created using the "New" button.